![background image](http://html.mh-extra.com/html/carrier/30gtn/30gtn_service-and-troubleshooting-manual_2560156040.webp)
Table 18 — Example of Compressor Lead/Lag Configuration
SUB-MODE KEYPAD ENTRY
ITEM
DISPLAY
ITEM EXPANSION
COMMENT
OPT2
ENTER
CTRL
0
CONTROL METHOD
CCNA
1
CCNB
0
BAUD
3
LOAD
1
LLCS
1
LEAD/LAG CIRCUIT SELECT DEFAULT: 2 (040-070); 1 (080-420)
ENTER
1
Scrolling stops
ENTER
1
Value flashes
3
Select 3
NOTE: Options 1 and/or 3 not valid for sizes 040-070 with-
out Circuit B accessory unloader installed
ENTER
3
Change accepted
ESCAPE
LLCS
3
LEAD/LAG CIRCUIT SELECT Item/Value/Units scrolls again
Table 19 — Time Clock Mode and Sub-Mode Directory
SUB-MODE
KEYPAD ENTRY
ITEM
DISPLAY
ITEM EXPANSION
COMMENT
TIME
ENTER
HH.MM
XX.XX
HOUR AND MINUTE
Military (00.00-23.59)
DATE
ENTER
MNTH
XX
MONTH
1=Jan, 2=Feb, etc.
DOM
XX
DATE OF MONTH
Range 1-31
DAY
X
DAY OF WEEK
1=Mon, 2=Tue, etc.
YEAR
XXXX
YEAR OF CENTURY
SCHD
ENTER
MON.O
XX.XX
MONDAY OCCUPIED TIME
Range: 00.00 to 23.59
Default: 00.00
MON.U
XX.XX
MONDAY UNOCCUPIED TIME
Range: 00.00 to 23.59
Default: 00.00
TUE.O
XX.XX
TUESDAY OCCUPIED TIME
Range: 00.00 to 23.59
Default: 00.00
TUE.U
XX.XX
TUESDAY UNOCCUPIED TIME
Range: 00.00 to 23.59
Default: 00.00
WED.O
XX.XX
WEDNESDAY OCCUPIED TIME
Range: 00.00 to 23.59
Default: 00.00
WED.U
XX.XX
WEDNESDAY UNOCC TIME
Range: 00.00 to 23.59
Default: 00.00
THU.O
XX.XX
THURSDAY OCCUPIED TIME
Range: 00.00 to 23.59
Default: 00.00
THU.U
XX.XX
THURSDAY UNOCCUPIED TIME
Range: 00.00 to 23.59
Default: 00.00
FRI.O
XX.XX
FRIDAY OCCUPIED TIME
Range: 00.00 to 23.59
Default: 00.00
FRI.U
XX.XX
FRIDAY UNOCCUPIED TIME
Range: 00.00 to 23.59
Default: 00.00
SAT.O
XX.XX
SATURDAY OCCUPIED TIME
Range: 00.00 to 23.59
Default: 00.00
SAT.U
XX.XX
SATURDAY UNOCCUPIED TIME
Range: 00.00 to 23.59
Default: 00.00
SUN.O
XX.XX
SUNDAY OCCUPIED TIME
Range: 00.00 to 23.59
Default: 00.00
SUN.U
XX.XX
SUNDAY UNOCCUPIED TIME
Range: 00.00 to 23.59
Default: 00.00
40
Summary of Contents for 30GTN
Page 6: ...Fig 1 Typical Control Box 080 110 and Associated Modular Units Shown 6 ...
Page 7: ...Fig 2 24 V Control Schematic Unit Sizes 040 070 7 ...
Page 8: ...Fig 3 24 V Control Schematic Unit Sizes 080 110 230B 315B 8 ...
Page 9: ...Fig 4 24 V Control Schematic Unit Sizes 130 210 230A 315A 330A B 420A B 9 ...