Table 15 — Configuration Mode and Sub-Mode Directory (cont)
SUB-MODE
KEYPAD ENTRY
ITEM
DISPLAY
ITEM EXPANSION
COMMENT
OPT2
ENTER
CTRL
X
CONTROL METHOD
Default: 0
0 = Switch
1 = 7 Day Schedule
2 = Occupancy
3 = CCN Control
CCNA
XXX
CCN ADDRESS
Default: 1
Range: 1 to 239
CCNB
XXX
CCN BUS NUMBER
Default: 0
Range: 0 to 239
BAUD
X
CCN BAUD RATE
Default: 3
1 = 2400
2 = 4800
3 = 9600
4 = 19,200
5 = 38,400
LOAD
X
LOADING SEQUENCE SELECT
Default: 1
1 = Equal
2 = Staged
LLCS
X
LEAD/LAG CIRCUIT SELECT
Default: 1 (size 080-420) 2 (size 040-070)
1 = Automatic
2 = Circuit A Leads
3 = Circuit B Leads
LCWT
XX.X
D
F
HIGH LCW ALERT LIMIT
Default: 60
Range: 2 to 60 F
DELY
XX
MIN MINUTES OFF TIME
Default: 0 Minutes
Range: 0 to 15 Minutes
RSET
ENTER
CRST
X
COOLING RESET TYPE
0 = No Reset
1 = 4 to 20 mA Input
2 = Outdoor Air Temperature
3 = Return Fluid
4 = Space Temperature
CRT1
XXX.X °F
NO COOL RESET TEMP
Default: 125 F
Range: 0 to 125 F
CRT2
XXX.X °F
FULL COOL RESET TEMP
Default: 0° F
Range: 0 to 125 F
DGRC
XX.X
D
F
DEGREES COOL RESET
Default: 0° F
Range: −30 to 30 F
DMDC
X
DEMAND LIMIT SELECT
Default: 0
0 = None
1 = Switch
2 = 4 to 20 mA Input
3 = CCN Loadshed
DM20
XXX %
DEMAND LIMIT AT 20 MA
Default: 100%
Range: 0 to 100%
SHNM
XXX
LOADSHED GROUP NUMBER
Default: 0
Range: 0 to 99
SHDL
XXX %
LOADSHED DEMAND DELTA
Default: 0%
Range: 0 to 60%
SHTM
XXX MIN
MAXIMUM LOADSHED TIME
Default: 60 minutes
Range: 0 to 120 minutes
DLS1
XXX %
DEMAND LIMIT SWITCH 1
Default: 80%
Range: 0 to 100%
DLS2
XXX %
DEMAND LIMIT SWITCH 2
Default: 50%
Range: 0 to 100%
LLEN
ENBL/DSBL
LEAD/LAG CHILLER ENABLE
Default: Disable
MSSL
SLVE/MAST
MASTER/SLAVE SELECT
Default: Master
SLVA
XXX
SLAVE ADDRESS
Default: 0
Range: 0 to 239
LLBL
ENBL/DSBL
LEAD/LAG BALANCE SELECT
Default: Disable
LLBD
XXX HRS
LEAD/LAG BALANCE DELTA
Default: 168 hours
Range: 40 to 400 Hours
LLDY
XX MIN
LAG START DELAY
Default: 5 minutes
Range: 0 to 30 minutes
SLCT
ENTER
CLSP
X
COOLING SETPOINT SELECT
Default: 0
0 = Single
1 = Dual Switch
2 = Dual Clock
3 = 4 to 20 mA Input
RL.S
ENBL/DSBL
RAMP LOAD SELECT
Default: Enable
CRMP
X.X
COOLING RAMP LOADING
Default: 1.0
Range: 0.2 to 2.0
Z.GN
X.X
DEADBAND MULTIPLIER
Default: 1.0
Range: 1.0 to 4.0
37
Summary of Contents for 30GTN
Page 6: ...Fig 1 Typical Control Box 080 110 and Associated Modular Units Shown 6 ...
Page 7: ...Fig 2 24 V Control Schematic Unit Sizes 040 070 7 ...
Page 8: ...Fig 3 24 V Control Schematic Unit Sizes 080 110 230B 315B 8 ...
Page 9: ...Fig 4 24 V Control Schematic Unit Sizes 130 210 230A 315A 330A B 420A B 9 ...
Page 75: ......