Table 17 — Example of Configuring Dual Chiller Control
SUB-MODE
KEYPAD ENTRY
ITEM
DISPLAY
ITEM EXPANSION
COMMENT
RSET
ENTER
CRST
0
LLDY
5
LAG START DELAY
ENTER
5
Scrolling stops
ENTER
5
Value flashes
10
Select 10
ENTER
10
Change accepted
ESCAPE
LLDY
10
LLBD
168
LEAD/LAG BALANCE DELTA
No change needed. Default set for weekly changeover
LLBL
DSBL
LEAD/LAG BALANCE SELECT
ENTER
DSBL
Scrolling stops
ENTER
DSBL
Value flashes
ENBL
Select Enable
ENTER
ENBL
Change accepted
ESCAPE
LLBL
ENBL
SLVA
0
SLAVE ADDRESS
ENTER
0
Scrolling stops
ENTER
0
Value flashes
6
Select 6
ENTER
6
Change accepted
ESCAPE
SLVA
6
MSSL
MAST
MASTER/SLAVE SELECT
No change needed. Default set for Master
LLEN
DSBL
LEAD/LAG CHILLER ENABLE
ENTER
DSBL
Scrolling stops
ENTER
DSBL
Value flashes
MAST
Select Master
ENTER
LLEN
MAST
Change accepted
ESCAPE
LLEN
MAST
LEAD/LAG CHILLER ENABLE
Item/Value/Units scrolls again
39