DIMENSIONS (ft-in.)
30GT
UNIT SIZE
A
B
C
D
E
F
G
H
190,290A,360A (50 Hz),
360A/B (60 Hz), 390B
11-4
[3454]
4-2
1
⁄
2
[1283]
1-5
5
⁄
8
[448] 6- 3
7
⁄
16
[1916] 7-8
1
⁄
4
[2343] 8
5
⁄
8
[219] 1- 9 [533.4] 6- 4
7
⁄
16
[1941.3]
210,315A,
390A,420A/B
11-3
5
⁄
8
[3444] 4-2
9
⁄
16
[1285] 1-6
7
⁄
16
[468] 5-11
1
⁄
2
[1816] 8-2
9
⁄
16
[2504] 9
1
⁄
2
[242] 1-11 [584]
5-11
1
⁄
2
[1816.2]
Fig. 4 — Dimensions; 30GT190,210,290A,315A,360A (50 Hz),360A/B (60 Hz), 390A/B, 420A/B
NOTES:
1. Unit must have clearances for airflow (from solid sur-
faces) as follows:
Top — Do not restrict in any way
Ends — 5 ft [1524 mm]
Sides — 6 ft [1829 mm]
2. Mounting holes may be used to mount unit to con-
crete pad. They are not recommended for spring iso-
lator location.
3. If spring isolators are used, a perimeter support
channel between the unit and the isolators is
recommended.
4. Dimensions in [
] are in millimeters.
6