5.6 Electric Data
Important notes
Dados obtidos do catálogo técnico de compressores do Fornecedor
1.
Data from the supplier’s technical catalog.
2.
RLA, KW, RLA TOTAL and kW TOTAL refer to nominal operation data with the unit in operation. Suction temperature: 45°F (7.2°C) and
condensation temperature: 130°F (54.4°C) - ARI conditions.
3.
MOPA values shown in the table were calculated taking into consideration the maximum operation values of the unit.
4.
Values show in the KVAr column be dimensioned to the compressors when is necessary to correct the POWER FACTOR to 0,92.
5.
All compressors are Scroll.
Legends
RLA
Nominal Current (Rated Load Amps).
LRA
Locked Rotor Current (Locked Rotor Amps).
MOPA
Maximum recommended capacity for the protection of the fuse against short circuit.
kW
Consumed Rated Power.
FP
Power Factor (without correction to 0.92)
KVAr
Recommended reactive power for the sizing of the bank of capacitors(0.92).
30AJ
Unit
Voltage [ V ] / [Hz]
Compressor
Fan
Additional
technical data
Power supply /
Frequency
Technical Data
Technical Data
Circuit A
Nominal
Min.
Max.
RLA [A] LRA [A]
kW
FP
KVAr
QTDE
RLA [A]
P [CV]
kW
Total
RLA
TOTAL
[A]
kW
TOTAL
[W]
MOPA
[A]
04
ZR47
220/60
198
242
14,3
91,0
4,2
0,76
2,5
1
1,3
1/6
0,123
15,6
4,3
25
380/60
342
418
7,2
46,0
4,2
0,87
1
1
1,3
1/6
0,123
8,5
4,3
16
05
ZR57
220/60
198
242
17,2
124,0
5
0,76
2,1
1
1,3
1/6
0,123
18,5
5,1
25
380/60
342
418
8,2
59,6
5
0,42
1
1
1,3
1/6
0,123
9,5
5,1
25
10
SZ120
220/60
198
242
33,1
237,0
10,8
0,86
5
1
2,2
1
0,75
35,3
11,5
50
380/60
342
418
19,8
160,0
10,8
0,83
5
1
2,2
1
0,75
22,0
11,5
40