GUIDE SPECIFICATIONS

GENERAL

System Description

Outdoor--mounted, air--cooled, split--system heat pump unit
suitable for ground or rooftop installation. Unit consists of a

hermetic compressor, an air--cooled coil, forward--swept blade
propeller--type condenser fan, and a control box. Unit will

discharge supply air upward as shown on contract drawings. Unit
will be used in a refrigeration circuit to match up to a packaged fan

coil or coil unit.

Quality Assurance

— Unit will be rated in accordance with the latest edition of

AHRI Standard 240.

— Unit will be certified for capacity and efficiency, and

listed in the latest AHRI directory.

— Unit construction will comply with latest edition of

ASHRAE and with NEC.

— Unit will be constructed in accordance with UL

standards and will carry the UL label of approval. Unit
will have C--UL approval.

— Unit cabinet will be capable of withstanding Federal Test

Method Standard No. 141 (Method 6061) 500--hr salt
spray test.

— Air--cooled condenser coils are pressure tested and the

outdoor units are leak tested.

— Unit constructed in ISO9001 approved facility.

Delivery, Storage, and Handling

— Unit will be shipped as single package only and is stored

and handled per unit manufacturer’s recommendations.

Warranty (for inclusion by specifying engineer)

— U.S. and Canada only.

PRODUCTS

Equipment

— Factory--assembled, single--piece, air--cooled heat pump

unit. Contained within the unit enclosure is all factory
wiring, piping, controls, compressor, refrigerant charge
Puron

r

(R--410A) refrigerant, and special features

required prior to field start--up.

Unit Cabinet

— Unit cabinet will be constructed of galvanized steel,

bonderized, and coated with a powder coat paint.

Fans

— Condenser fan will be direct--drive propeller type,

forward swept blade, discharging air upward.

AIR--COOLED, SPLIT--SYSTEM HEAT PUMP

25VNA

2 TO 5 NOMINAL TONS

— Condenser fan motors will be totally enclosed, 1--phase

type with class B insulation and permanently lubricated.

— Shafts will be corrosion resistant.
— Fan blades will be statically and dynamically balanced.
— Condenser fan openings will be equipped with coated

steel wire safety guards.

Compressor

— Compressor will be hermetically sealed.
— Compressor will be mounted on rubber vibration

isolators.

— Compressor will be covered with a sound absorbing

blanket.

Condenser Coil

— Condenser coil will be air cooled.
— Coil will be constructed of aluminum fins mechanically

bonded to copper tubes which are then cleaned,
dehydrated, and sealed.

Refrigeration Components

— Refrigeration circuit components will include liquid--line

front--seating shutoff valve with sweat connections,

vapor--line front--seating shutoff valve with sweat
connections, system charge of Puron

r

(R--410A)

refrigerant, POE compressor oil, accumulator, charge

compensator, electronic expansion valve, and reversing
valve.

— Unit will be equipped with high--pressure switch, suction

pressure transducer, and filter drier for Puron

r

refrigerant.

Operating Characteristics

— The capacity of the unit will meet or exceed _____ Btuh

at a suction temperature of _____

_

F (

_

C). The power

consumption at full load will not exceed _____ kW.

— Combination of the unit and the evaporator or fan coil

unit will have a total net cooling capacity of _____ Btuh
or greater at conditions of _____ CFM entering air
temperature at the evaporator at _____

_

F (

_

C) wet bulb

and _____

_

F (

_

C) dry bulb, and air entering the unit at

_____

_

F (

_

C).

— The system will have a SEER of _____ Btuh/watt or

greater at DOE conditions.

Electrical Requirements

— Nominal unit electrical characteristics will be _____ v,

single phase, 60 hz. The unit will be capable of
satisfactory operation within voltage limits of _____ v to

_____ v.

— Unit electrical power will be single point connection.
— Control circuit will be 24v.

Special Features

— Refer to section of this literature identifying accessories

and descriptions for specific features and available

enhancements.

— Infinity control with appropriate software version is

required for full featured operation.

25V

N

A

Summary of Contents for 25VNA

Page 1: ...y accessories available Sound S Sound level as low as 58 dBA in low speed Silencer System II Comfort S Variable speed compressor with capacity range from 40 100 S Air cooled Inverter variable speed drive System requires Infinity Control with Greenspeed capability SYSTXCCUID01 V or SYSTXCCUIZ01 V or newer Reliability S Puronr refrigerant environmentally sound won t deplete the ozone layer and low l...

Page 2: ...proper charge and air flow may reduce energy efficiency and shorten equipment life Use of the AHRI Certified TM Mark indicates a manufacturer s participation in the program For verification of certification for individual products go to www ahridirectory org the environmentally sound refrigerant STANDARD FEATURES FEATURES Unit Size Voltage Series 24 30 36 30 48 30 60 30 Puron Refrigerant X X X X L...

Page 3: ...CATIONS An application is considered Long Line when the refrigerant level in the system requires the use of accessories to maintain acceptable refrigerant management for systems reliability Defining a system as long line depends on the liquid line diameter actual length of the tubing and vertical separation between the indoor and outdoor units For Heat Pump systems the chart below shows when an ap...

Page 4: ...combination and system demand The airflows on these tables are for duct design considerations Duct systems capable of these ranges will ensure the system will deliver full capacity at all outdoor temperatures Minimum and maximum airflows can be adjusted from these numbers in the Infinity Control Heat Pump Setup screen Cooling Comfort Mode Minimum Cooling Dehum or Zoning Size Max Capacity Min Capac...

Page 5: ...M0101EMI ELECTRO MAGNETIC INTERFERENCE KIT X X X X KHALS0401LLS SOLENOID VALVE X X X X KHASS0606MPK SNOW STAND X X X X KSASF0101AAA SUPPORT FEET X X X X KSATX0301PUR TXV X X KSATX0401PUR TXV X KSATX0501PUR TXV X STANDARD CRANKCASE HEATER S S S S x Accessory S Standard Available from RCD CONTROLS SYSTXCCITN01 Infinity Touch Control non Wi Fi SYSTXCCITW01 Infinity Touch Control with Wi Fi Wireless A...

Page 6: ...the chance of liquid slugging Usage Used in low ambient cooling applications Used in long line applications 3 Liquid Line Solenoid Valve LLS An electrically operated shutoff valve which stops and starts refrigerant liquid flow in response to compressor operation It is to be installed at the outdoor unit to control refrigerant off cycle migration in the heating mode Usage Guideline An LLS is requir...

Page 7: ...it Size Voltage Series Typical Octave Band Spectrum without tone adjust ment Min Speed Cooling Max Speed Cooling Min Speed Heating Max Speed Heating 024 30 Freq Hz 1800 RPM 3200 RPM 1800 RPM 5700 RPM 125 62 0 63 0 63 0 73 5 250 57 0 56 5 61 5 63 0 500 54 5 57 5 58 5 66 0 1000 52 0 58 0 54 5 63 5 2000 47 5 54 0 51 5 64 5 4000 44 5 48 0 48 0 59 5 8000 52 5 54 5 54 0 61 5 Sound Rating dBA 58 63 62 71...

Page 8: ...8 DIMENSIONS ENGLISH 25VNA ...

Page 9: ...9 DIMENSIONS SI 25VNA ...

Page 10: ... 70 80 BUILDING HEAT LOSS UNIT INTEGRATED HEATING CAPACITY MBTUH OUTDOOR TEMPERATURE F C 25VNA024 BALANCE POINT WORK SHEET MINIMUM MAXIMUM HEATING CAPACITIES Minimum Capaci es Maximum Capaci es 0 00 2 9 5 9 8 8 23 3 17 8 12 2 6 7 1 1 4 4 10 15 6 21 1 26 7 KW BASED ON INDOOR ENT AIR AT 70 F 21 1 C 25VNA ...

Page 11: ...0 70 80 BUILDING HEAT LOSS UNIT INTEGRATED HEATING CAPACITY MBTUH OUTDOOR TEMPERATURE F C 25VNA036 BALANCE POINT WORKSHEET MINIMUM MAXIMUM DELIVERABLE HEATING CAPACITIES Minimum Capaci es Maximum Capaci es 23 3 17 8 12 2 6 7 1 1 4 4 10 15 6 21 1 26 7 0 0 11 7 KW 2 9 5 9 8 8 BASED ON INDOOR ENT AIR AT 70 F 21 1 C 25VNA ...

Page 12: ...ILDING HEAT LOSS UNIT INTEGRATED HEATING CAPACITY MBTUH OUTDOOR TEMPERATURE F C 25VNA048 BALANCE POINT WORK SHEET MINIMUM AND MAXIMUM HEATING CAPACITIES Minimum Capaci es Maximum Capaci es KW 23 3 17 8 12 2 6 7 1 1 4 4 10 15 6 21 1 26 7 0 0 2 9 5 9 8 8 11 7 14 8 17 6 20 5 BASED ON INDOOR ENT AIR AT 70 F 21 1 C 25VNA ...

Page 13: ...ILDING HEAT LOSS UNIT INTEGRATED HEATING CAPACITY MBTUH OUTDOOR TEMPERATURE F C 25VNA060 BALANCE POINT WORK SHEET MINIMUM AND MAXIMUM HEATING CAPACITIES Minimum Capaci es Maximum Capaci es BASED ON INDOOR ENT AIR AT 70 F 21 1 C KW 0 0 2 9 5 9 8 8 11 7 14 8 17 6 20 5 23 3 17 8 12 2 6 7 1 1 4 4 10 15 6 21 1 26 7 25VNA ...

Page 14: ...rvice 24 609 6 Service 24 609 6 Service 24 609 6 24 609 6 24 609 6 12 304 8 12 304 8 12 304 8 12 304 8 6 152 4 Note Numbers in mm IMPORTANT When installing multiple units in an alcove roof well or partially enclosed area ensure there is adequate ventilation to prevent re circulation of discharge air A07833 25VNA ...

Page 15: ...00 23 200 14 5 20 5 1200 875 33 400 4 40 13 0 31 600 2 54 25VNA048A 30 FE4ANB006 UI 47 500 34 800 13 5 18 3 1500 1100 45 500 4 12 12 5 47 500 2 22 25VNA060A 30 FE4ANB006 UI 56 000 38 000 12 7 18 0 1500 1100 55 500 3 86 12 0 52 500 2 22 Ratings are net values reflecting the effects of circulating fan heat Supplemental electric heat is not included Ratings are based on Cooling Standard 80_F 27_C db ...

Page 16: ...12 CNPH 4221A 0 97 1 05 58CV A X 070 12 CNPH 4321A 0 99 1 03 58CV A X 070 12 CNPH 4821A 0 98 1 04 58CV A X 070 12 CNPH 6024A 0 98 1 04 58CV A X 070 12 CNPH 6124A 0 99 1 04 58CV A X 070 12 CNPV 3617A 0 95 1 05 58CV A X 070 12 CNPV 3717A 0 99 1 04 58CV A X 070 12 CNPV 4217A 0 98 1 05 58CV A X 070 12 CSPH 3612A 0 98 1 04 58CV A X 070 12 CSPH 4212A 0 98 1 04 58CV A X 070 12 CSPH 4812A 0 98 1 04 58CV A...

Page 17: ...24A 0 99 1 02 58MV B C 080 14 CSPH 3612A 0 98 1 06 58MV B C 080 14 CSPH 4212A 0 98 1 05 58MV B C 080 14 CSPH 4812A 0 98 1 04 58MV B C 080 14 CSPH 6012A 0 99 1 04 58MV B C 080 14 CAP 3621A 0 96 1 05 58MV B C 080 20 CAP 4221A 0 97 1 05 58MV B C 080 20 CAP 4224A 0 97 1 05 58MV B C 080 20 CAP 4821A 0 98 1 04 58MV B C 080 20 CAP 4823A 0 98 1 04 58MV B C 080 20 CAP 4824A 0 98 1 03 58MV B C 080 20 CAP 60...

Page 18: ... 04 59 N A080V21 20 CAP 3621A 0 96 1 05 59 N A100V21 20 CAP 4221A 0 97 1 05 59 N A100V21 20 CAP 4224A 0 97 1 04 59 N A100V21 20 CAP 4821A 0 98 1 03 59 N A100V21 20 CAP 4824A 0 98 1 03 59 N A100V21 20 CAP 6021A 0 98 1 04 59 N A100V21 20 CAP 6024A 0 98 1 04 59 N A100V21 20 CNPH 3617A 0 96 1 06 59 N A100V21 20 CNPH 4221A 0 97 1 05 59 N A100V21 20 CNPH 4321A 0 99 1 03 59 N A100V21 20 CNPH 4821A 0 98 1...

Page 19: ...A X 070 12 CNPH 4221A 0 95 1 09 58CV A X 070 12 CNPH 4321A 0 98 1 08 58CV A X 070 12 CNPH 4821A 0 97 1 08 58CV A X 070 12 CNPH 6024A 0 99 1 09 58CV A X 070 12 CNPH 6124A 0 99 1 09 58CV A X 070 12 CNPV 3617A 0 94 1 09 58CV A X 070 12 CNPV 3717A 0 98 1 10 58CV A X 070 12 CNPV 4217A 0 96 1 10 58CV A X 070 12 CSPH 3612A 0 97 1 08 58CV A X 070 12 CSPH 4212A 0 97 1 08 58CV A X 070 12 CSPH 4812A 0 98 1 0...

Page 20: ...0 95 1 06 58MV B C 080 20 CAP 4221A 0 96 1 07 58MV B C 080 20 CAP 4224A 0 95 1 06 58MV B C 080 20 CAP 4821A 0 97 1 08 58MV B C 080 20 CAP 4823A 0 97 1 08 58MV B C 080 20 CAP 4824A 0 97 1 07 58MV B C 080 20 CAP 6021A 0 98 1 08 58MV B C 080 20 CAP 6024A 0 98 1 08 58MV B C 080 20 CAP 6025A 0 98 1 08 58MV B C 080 20 CNPH 3617A 0 94 1 09 58MV B C 080 20 CNPH 4221A 0 95 1 06 58MV B C 080 20 CNPH 4321A 0...

Page 21: ...4824A 0 97 1 07 59 N A100V21 20 CAP 6021A 0 98 1 08 59 N A100V21 20 CAP 6024A 0 98 1 08 59 N A100V21 20 CAP 6025A 0 98 1 08 59 N A100V21 20 CNPH 3617A 0 94 1 08 59 N A100V21 20 CNPH 4221A 0 96 1 07 59 N A100V21 20 CNPH 4321A 0 99 1 06 59 N A100V21 20 CNPH 4821A 0 98 1 07 59 N A100V21 20 CNPH 6024A 0 99 1 07 59 N A100V21 20 CNPH 6124A 0 99 1 07 59 N A100V21 20 CNPV 3621A 0 95 1 08 59 N A100V21 20 C...

Page 22: ...4A 0 98 1 04 58CV A X 090 16 CNPV 4821A 0 96 1 03 58CV A X 090 16 CSPH 4812A 0 96 1 03 58CV A X 090 16 CSPH 6012A 0 98 1 03 58CV A X 090 16 CAP 4821A 0 95 1 02 58CV A X 110 20 CAP 4823A 0 95 1 02 58CV A X 110 20 CAP 4824A 0 95 1 02 58CV A X 110 20 CAP 6021A 0 97 1 02 58CV A X 110 20 CAP 6024A 0 97 1 02 58CV A X 110 20 CAP 6025A 0 97 1 02 58CV A X 110 20 CNPH 4821A 0 96 1 03 58CV A X 110 20 CNPH 60...

Page 23: ...MV B C 100 20 CAP 4823A 0 95 1 06 58MV B C 100 20 CAP 4824A 0 95 1 05 58MV B C 100 20 CAP 6021A 0 97 1 05 58MV B C 100 20 CAP 6024A 0 97 1 05 58MV B C 100 20 CAP 6025A 0 97 1 05 58MV B C 100 20 CNPH 4821A 0 95 1 04 58MV B C 100 20 CNPH 6024A 0 97 1 05 58MV B C 100 20 CNPH 6124A 0 98 1 06 58MV B C 100 20 CNPV 4821A 0 95 1 04 58MV B C 100 20 CNPV 4824A 0 95 1 04 58MV B C 100 20 CNPV 6024A 0 97 1 05 ...

Page 24: ... 155 22 CNPV 6024A 0 98 1 00 58CV A X 155 22 CNPV 6124A 0 99 1 01 58CV A X 155 22 CSPH 6012A 0 98 1 00 58CV A X 155 22 CAP 6021A 0 97 1 06 59 N A080V21 20 CAP 6024A 0 97 1 05 59 N A080V21 20 CNPH 6024A 0 99 1 07 59 N A080V21 20 CNPV 6024A 0 99 1 07 59 N A080V21 20 CSPH 6012A 0 98 1 06 59 N A080V21 20 CAP 6021A 0 97 1 03 59 N A100V21 22 CAP 6024A 0 97 1 03 59 N A100V21 22 CNPH 6024A 1 00 1 06 59 N ...

Page 25: ...0 1 47 26 98 26 98 1 45 30 70 30 70 1 44 75 23 9 26 83 24 41 2 32 23 36 23 36 1 59 26 71 26 71 1 57 30 39 30 39 1 56 INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES F C 3 19 4 7 13 9 17 8 3 27 2 8 EDB F C ID SCFM Capacity MBtuh Total Sys KW ID SCFM Capacity MBtuh Total Sys KW ID SCFM Capacity MBtuh Total Sys KW ID SCFM Capacity MBtuh Total Sys KW Total Integ Total Integ Total Integ Total Integ 2...

Page 26: ...NPH 6024A 1 00 1 02 58CV A X 135 22 CNPH 6124A 0 97 0 98 58CV A X 135 22 CNPV 4324A 0 99 1 00 58CV A X 135 22 CNPV 4824A 1 00 1 04 58CV A X 135 22 CNPV 6024A 1 00 1 02 58CV A X 135 22 CNPV 6124A 0 98 0 96 58CV A X 135 22 CSPH 3612A 1 00 1 07 58CV A X 135 22 CSPH 4212A 1 00 1 04 58CV A X 135 22 CSPH 4812A 1 00 1 03 58CV A X 135 22 CSPH 6012A 0 99 1 00 58CV A X 135 22 CAP 4224A 1 01 1 12 58CV A X 15...

Page 27: ...40 14 CSPH 4212A 1 01 1 07 58MVB040 14 CSPH 4812A 1 00 1 04 58MVB040 14 CSPH 6012A 1 00 1 03 58MVB040 14 CAP 3617A 1 02 1 21 59 N A060V17 14 CAP 3621A 1 02 1 21 59 N A060V17 14 CAP 4221A 1 01 1 13 59 N A060V17 14 CAP 4817A 0 97 1 03 59 N A060V17 14 CAP 4821A 0 98 1 05 59 N A060V17 14 CAP 6021A 0 97 1 02 59 N A060V17 14 CNPH 3617A 1 02 1 25 59 N A060V17 14 CNPH 4221A 1 02 1 17 59 N A060V17 14 CNPH ...

Page 28: ...0V24 22 CNPH 3617A 1 02 1 23 59 N A120V24 22 CNPH 4221A 1 02 1 14 59 N A120V24 22 CNPH 4321A 0 97 0 99 59 N A120V24 22 CNPH 4821A 0 98 1 02 59 N A120V24 22 CNPH 6024A 0 99 1 01 59 N A120V24 22 CNPH 6124A 0 98 1 00 59 N A120V24 22 CNPV 4324A 0 97 0 98 59 N A120V24 22 CNPV 4824A 0 98 1 02 59 N A120V24 22 CNPV 6024A 0 99 1 01 59 N A120V24 22 CNPV 6124A 0 98 0 98 59 N A120V24 22 CSPH 3612A 1 01 1 09 5...

Page 29: ...33 40 33 40 2 07 37 22 37 22 2 04 41 77 41 77 2 02 75 23 9 32 42 29 51 2 57 33 10 33 10 2 23 36 86 36 86 2 20 41 22 41 22 2 17 INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES F C 3 19 4 7 13 9 17 8 3 27 2 8 EDB F C ID SCFM Capacity MBtuh Total System KW ID SCFM Capacity MBtuh Total System KW ID SCFM Capacity MBtuh Total System KW ID SCFM Capacity MBtuh Total System KW Total Integ Total Integ Tot...

Page 30: ...NPH 6124A 0 98 0 99 58CV A X 135 22 CNPV 4324A 1 00 1 00 58CV A X 135 22 CNPV 4824A 1 02 1 06 58CV A X 135 22 CNPV 6124A 0 99 0 98 58CV A X 135 22 CSPH 3612A 1 04 1 11 58CV A X 135 22 CSPH 4212A 1 03 1 07 58CV A X 135 22 CSPH 4812A 1 03 1 06 58CV A X 135 22 CSPH 6012A 0 99 1 00 58CV A X 135 22 CAP 4224A 1 04 1 15 58CV A X 155 22 CAP 4824A 0 99 1 03 58CV A X 155 22 CAP 6024A 0 98 0 99 58CV A X 155 ...

Page 31: ...21A 1 01 1 13 59 N A060V17 14 CAP 6021A 0 99 1 09 59 N A060V17 14 CNPH 3617A 1 04 1 24 59 N A060V17 14 CNPH 4221A 1 05 1 23 59 N A060V17 14 CNPH 4321A 1 01 1 10 59 N A060V17 14 CNPH 4821A 1 03 1 14 59 N A060V17 14 CNPH 6024A 1 02 1 11 59 N A060V17 14 CNPH 6124A 1 01 1 10 59 N A060V17 14 CNPV 3617A 1 08 1 55 59 N A060V17 14 CNPV 3621A 1 08 1 39 59 N A060V17 14 CNPV 3717A 1 03 1 12 59 N A060V17 14 C...

Page 32: ...1 04 1 16 59 N A120V24 22 CNPH 4321A 1 00 1 03 59 N A120V24 22 CNPH 4821A 1 02 1 07 59 N A120V24 22 CNPH 6024A 1 00 1 03 59 N A120V24 22 CNPH 6124A 0 99 1 02 59 N A120V24 22 CNPV 4324A 1 00 1 02 59 N A120V24 22 CNPV 4824A 1 02 1 07 59 N A120V24 22 CNPV 6024A 1 01 1 04 59 N A120V24 22 CNPV 6124A 0 99 1 00 59 N A120V24 22 CSPH 3612A 1 05 1 17 59 N A120V24 22 CSPH 4212A 1 04 1 10 59 N A120V24 22 CSPH...

Page 33: ...50 45 50 2 96 51 68 51 68 3 05 58 38 58 38 3 15 75 23 9 50 35 45 82 4 17 45 11 45 11 3 13 51 18 51 18 3 22 57 74 57 74 3 31 INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES F C 3 19 4 7 13 9 17 8 3 27 2 8 EDB F C ID SCFM Capacity MBtuh Total System KW ID SCFM Capacity MBtuh Total System KW ID SCFM Capacity MBtuh Total System KW ID SCFM Capacity MBtuh Total System KW Total Integ Total Integ Total ...

Page 34: ...22 CAP 4824A 1 00 1 08 59 N A120V24 22 CAP 6024A 0 98 1 04 59 N A120V24 22 CAP 6025A 0 98 1 04 59 N A120V24 22 CNPH 4821A 1 01 1 09 59 N A120V24 22 CNPH 6024A 1 01 1 07 59 N A120V24 22 CNPH 6124A 1 00 1 05 59 N A120V24 22 CNPV 4824A 1 01 1 09 59 N A120V24 22 CNPV 6024A 1 01 1 07 59 N A120V24 22 CNPV 6124A 1 01 1 04 59 N A120V24 22 CSPH 4812A 1 01 1 08 59 N A120V24 22 CSPH 6012A 1 01 1 05 59 N A120...

Page 35: ...30 55 30 4 15 57 05 57 05 3 76 58 51 58 51 3 40 75 23 9 59 99 54 59 5 74 54 83 54 83 4 37 56 50 56 50 3 96 57 89 57 89 3 58 INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES F C 3 19 4 7 13 9 17 8 3 27 2 8 EDB F C ID SCFM Capacity MBtuh Total System KW ID SCFM Capacity MBtuh Total System KW ID SCFM Capacity MBtuh Total System KW ID SCFM Capacity MBtuh Total System KW Total Integ Total Integ Total ...

Page 36: ...1 01 1 11 59MN7A060V21 20 CAP 6024A 1 01 1 11 59MN7A060V21 20 CNPH 6024A 1 02 1 10 59MN7A060V21 20 CNPV 6024A 1 02 1 10 59MN7A060V21 20 CSPH 6012A 1 02 1 10 59MN7A060V21 20 CAP 6021A 1 01 1 09 58MV B C 080 20 CNPH 6024A 1 01 1 09 58MV B C 080 20 CNPH 6124A 1 00 1 07 58MV B C 080 20 CNPV 6024A 1 00 1 08 58MV B C 080 20 HEATING INDOOR MODEL CAPACITY POWER FURNACE MODEL CNPV 6124A 1 04 1 09 58MV B C ...

Page 37: ... with class B insulation and permanently lubricated Shafts will be corrosion resistant Fan blades will be statically and dynamically balanced Condenser fan openings will be equipped with coated steel wire safety guards Compressor Compressor will be hermetically sealed Compressor will be mounted on rubber vibration isolators Compressor will be covered with a sound absorbing blanket Condenser Coil C...

Page 38: ...r units greater than 20 ft 6 1 m consult Residential Piping and Longline Guideline and Service Manual available from equipment distribut or 8 If any refrigerant tubing is buried provide a 6 in 152 4 mm vertical rise to the valve connections at the unit Refrigerant tubing lengths up to 36 in 914 4 mm may be buried without further consideration Do not bury refrigerant lines longer than 36 in 914 4 m...

Reviews: