background image

13

Low Ambient Cooling

When this unit is operating below 55ºF outdoor temperature,

provisions must be made for low ambient operation.

Infinity Controlled low ambient cooling:

This unit is capable of low ambient cooling without a kit ONLY
when using the Infinity control. A low ambient kit is not

required, and the outdoor fan motor does not need to be replaced

for Infinity controlled low ambient operation.

The Infinity

Control provides an automatic evaporator coil freeze protection

algorithm that eliminates the need for an evaporator freeze
thermostat. Low ambient cooling must be enabled in the User

Interface set up. Fan may not begin to cycle until about 40

_

F

OAT. Fan will cycle based on coil and outdoor air temperature.

Infinity controlled low ambient mode operates as follows:

S

Fan is OFF when outdoor coil temp is < (outdoor air
tempe 3

_

F) or outdoor fan has been ON for 30

minutes. (Fan is turned off to allow refrigerant system
to stabilize.)

S

Fan is ON when outdoor coil temp > (outdoor air
tempe 25

_

F) or outdoor coil temp > 80

_

F or if

outdoor fan has been OFF for 30 minutes. (Fan is

turned on to allow refrigerant system to stabilize.)

S

Low pressure switch is ignored for first 3 minutes
during low ambient start up. After 3 minutes, if LPS

trips, then outdoor fan motor is turned off for 10
minutes, with the compressor running. If LPS closes
within 10 minutes then cooling continues with the

outdoor fan cycling per the coil temperature routine
listed above for the remainder of the cooling cycle. If

the LPS does not close within 10 minutes, then the
normal LPS trip response (shut down cooling operation
and generate LPS trip error) will occur.

Standard Thermostat low ambient cooling mode:

A Low Ambient Pressure Switch kit, Evaporator Freeze
Thermostat and Winter Start Control must be installed for low

ambient operation in standard thermostat mode. The fan motor is

a ball--bearing type and does not need to be changed. A crankcase
heater must be installed. See Product Data for part numbers on

appropriate unit size and series units.

DEFROST

This control offers 4 possible defrost interval times: 30, 60, 90 or
120 minutes. These are selected by dip switches on the unit

control board, or in the Infinity control (if used). The Infinity

Control selection overrides the control board dip switch settings.
Auto defrost is available with Infinity communicating control
only and it must be enabled in the User Interface. Auto defrost

adjusts the defrost interval time based on the last defrost time as
follows:

S

When defrost time is < 3 minutes, the next defrost
interval = 120 minutes

S

When defrost time is 3--5 minutes, the next defrost
interval = 90 minutes

S

When defrost time is 5--7 minutes, the next defrost
interval = 60 minutes

S

When defrost time is > 7 minutes, the next defrost
interval = 30 minutes

The control board accumulates compressor run time. As the
accumulated run time approaches the selected defrost interval

time, the control board monitors the coil temperature sensor for a
defrost demand. If a defrost demand exists, a defrost cycle will be

initiated at the end of the selected time interval. A defrost demand

exists when the coil temperature is at or below 32º F for 4
minutes during the interval.
The defrost cycle is terminated when the coil temperature reaches

65º or 10 minutes has passed.
If the coil temperature does not reach 32 deg. within the interval,
the interval timer will be reset and start over.

NOTE

:

S

Upon initial power up the first defrost interval is
defaulted to 30 minutes. Remaining intervals are at
selected times.

S

Defrost is only allowed to occur below 50ºF outdoor
ambient temperature.

Defrost Hold

In a non--communicating system, if the thermostat becomes
satisfied before the defrost cycle is terminated, the control will

”hold” in defrost mode and finish the defrost cycle on the next
call for heat. Defrost hold is not needed in a communicating

system because the User Interface will complete the defrost cycle

before shutting down the system.

Forced Defrost

Forced defrost can be initiated manually in a non--communicating

system, or by communicated command from a User Interface.
The board contains a 2--pin header labeled FORCED DEFROST

(See Figure 14). To initiate a forced defrost:

S

Manually, short FORCED DEFROST pins for 5
seconds then release

S

If coil temp is at defrost temp of 32º F, and outdoor air
temperature is below 50ºF, a full defrost sequence will
occur

S

If the coil temp or outdoor air temperature do not meet
the above requirements, an abbreviated 30 second

defrost will occur

25H

PA

Summary of Contents for 25HPA Performance Series

Page 1: ...ements 3 Step 4 Operating Ambient 3 Step 5 Elevate Unit 3 Step 6 Install TXV 3 4 Step 7 Make Piping Connections 5 7 Step 8 Make Electrical Connections 7 8 Step 9 Compressor Crankcase Heater 8 Step 10...

Page 2: ...h a suitable warning label INSTALLATION RECOMMENDATIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit away from wi...

Page 3: ...23 3 4 36 1 2 X 40 9 5 8 6 13 16 28 3 4 A05177 Fig 3 Tiedown Knockout Requirements On rooftop applications locate unit at least 6 in above roof surface STEP 4 Operating Ambient The minimum outdoor ope...

Page 4: ...R 22 Indoor Coil 1 Pump system down to 2 psig and recover refrigerant 2 Remove coil access panel and fitting panel from front of cabinet 3 Remove TXV support clamp using a 5 16 in nut driver Save the...

Page 5: ...or coil are exposed to atmosphere they must be evacuated to 500 microns to eliminate contamination and moisture in the system Table 1 Accessory Usage Accessory REQUIRED FOR LOW AMBI ENT APPLICATIONS B...

Page 6: ...ilure to follow this caution may result in equipment damage or improper operation Service valves must be wrapped in a heat sinking material such as a wet cloth while brazing CAUTION UNIT DAMAGE HAZARD...

Page 7: ...tdoor unit has not shifted during shipment Ensure tubes are not rubbing against each other or any sheet metal Pay close attention to feeder tubes making sure wire ties on feeder tubes are secure and t...

Page 8: ...contact with tubing sheet metal etc STEP 9 Compressor Crankcase Heater When equipped with a crankcase heater furnish power to heater a minimum of 24 hr before starting unit To furnish power to heater...

Page 9: ...properly start up system 1 After system is evacuated fully open liquid and vapor service valves 2 Unit is shipped with valve stem s closed and caps installed Replace stem caps after system is opened...

Page 10: ...vice port 3 Measure liquid line temperature by attaching an accurate thermistor type or electronic thermometer to liquid line near outdoor coil 4 Refer to unit rating plate for required subcooling tem...

Page 11: ...ing Operation This product utilizes either a standard indoor thermostat or Infinity communication User Interface With a call for cooling the outdoor fan reversing valve and compressor are energized Wh...

Page 12: ...ater than or equal to 100 deg F S Fifteen second delay at termination of defrost before the auxiliary heat W2 is de energized S Twenty second delay at termination of defrost before the outdoor fan is...

Page 13: ...ches on the unit control board or in the Infinity control if used The Infinity Control selection overrides the control board dip switch settings Auto defrost is available with Infinity communicating c...

Page 14: ...he wiring label diagram This is a 24vac output that is energized whenever the compressor is energized It closes in the compressor off mode to prevent refrigerant migration into the unit through the li...

Page 15: ...cooling continues the control will energize the compressor contactor every 15 minutes If the thermal protector closes at the next 15 minute interval check the unit will resume operation If the therma...

Page 16: ...ir flow Control Fault 45 Outdoor unit control board has failed Control board needs to be replaced Brown Out 24 v 46 The control voltage is less than 15 5v for at least 4 seconds Com pressor and fan op...

Page 17: ...89 84 342 100 95 90 85 349 102 97 92 87 356 103 98 93 88 363 105 100 95 90 370 106 101 96 91 377 107 102 97 92 384 109 104 99 94 391 110 105 100 95 Liquid Pressure at Service Valve Required Subcooling...

Page 18: ...with 550 psig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron refrigerant as with other HFCs is only compatible...

Reviews: