background image

8

ELECTRICAL DATA

UNIT

SIZE

V/PH

OPER VOLTS*

COMPR

FAN

MCA

MIN

WIRE

SIZE†

MIN

WIRE

SIZE†

MAX

LENGTH

ft (m)‡

MAX

LENGTH

ft (m)‡

MAX

FUSE**

or CKT

BRK

AMPS

MAX

MIN

LRA

RLA

FLA

60° C

75° C

60° C

75° C

18---30

208/230/1

253

197

48.0

9.0

0.5

11.8

14

14

66 (20.1)

62 (18.9)

20

24---30

58.3

12.8

0.77

16.8

14

14

46 (14.0)

44 (13.4)

25

30---30

77.0

16.0

1.1

21.1

12

12

57 (17.4)

54 (16.5)

30

36---31

70.0

15.6

1.1

20.6

12

12

60 (18.3)

57 (17.4)

35

42---31

96.0

18.0

1.4

23.9

12

12

52 (15.8)

50 (15.2)

40

48---31

99.0

21.8

1.4

28.7

10

10

69 (21.0)

66 (20.1)

45

60---30

134.0

26.3

1.2

34.1

8

8

89 (27.1)

84 (25.6

50

30---50

208/230/3

253

197

71.0

10.0

1.1

13.6

14

14

65 (19.8)

62 (18.9)

20

36---50

73.0

10.4

1.1

14.1

14

14

61 (18.6)

58 (17.7)

20

42---50

83.1

13.6

1.4

18.4

14

14

48 (14.6)

46 (14.0)

30

48---50

83.1

13.8

1.4

18.7

14

14

48 (14.6)

46 (14.0)

30

60---50

110.0

15.9

1.2

21.1

12

12

66 (20.1)

63 (19.2)

30

36---60

460/3

253

197

38.0

5.8

0.6

7.9

14

14

227 (69.2)

216 (65.8)

10

48---60

41.0

6.2

0.7

8.5

14

14

202 (61.6)

192 (58.5)

10

60---60

52.0

7.8

0.6

10.4

14

14

165 (50.3)

157 (47.9)

15

*

Permissible limits of the voltage range at which the unit will operate satisfactorily

{

If wire is applied at ambient greater than 30

_

C, consult table 310---16 of the NEC (NFPA 70). The ampacity of non---metallic---sheathed cable (NM),

trade name ROMEX, shall be that of 60

_

C conditions, per the NEC (NFPA 70) Article 336---26. If other than uncoated (no---plated), 60 or 75

_

C

insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (NFPA 70).

}

Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.

** Time---Delay fuse.

FLA

--- Full Load Amps

LRA

--- Locked Rotor Amps

MCA ---

Minimum Circuit Amps

RLA

--- Rated Load Amps

NOTE

: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit.

All motors/compressors contain internal overload protection.
Complies with 2007 requirements of ASHRAE Standards 90.1

A--WEIGHTED SOUND POWER

UNIT SIZE

STANDARD

RATING

(dBA)

TYPICAL OCTAVE BAND SPECTRUM (dBA, without tone adjustment)

125

250

500

1000

2000

4000

8000

18---30

69

49.0

57.0

63.0

65.0

61.0

57.5

52.5

24---30

73

51.0

59.5

66.0

68.5

63.5

59.0

53.0

30---30, 50

74

52.5

64.0

68.0

69.0

67.0

64.5

58.5

36---31

73

50.5

62.5

67.0

68.5

66.5

63.5

58.0

36---50, 60

75

53.5

63.0

69.0

71.0

67.0

63.5

58.0

42---31

77

55.0

65.0

71.0

72.0

70.0

67.0

59.5

42---50

79

55.0

67.0

71.0

74.5

70.0

67.0

60.0

48---31

80

59.0

67.0

72.5

75.0

73.5

69.5

61.5

48---50, 60

80

59.5

69.5

74.0

76.0

72.5

69.5

64.5

60---30, 50, 60

77

55.0

63.0

67.5

71.5

68.0

64.0

60.5

NOTE

: Tested in accordance with AHRI Standard 270---08 (not listed in AHRI).

A--WEIGHTED SOUND POWER WITH SOUND HOOD

UNIT SIZE

STANDARD

RATING

(dBA)

TYPICAL OCTAVE BAND SPECTRUM (dBA, without tone adjustment)

125

250

500

1000

2000

4000

8000

18---30

69

50.0

57.0

63.0

64.5

61.0

57.0

51.0

24---30

71

51.5

59.0

65.5

67.5

63.0

58.5

53.0

30---30, 50

73

53.0

64.0

68.0

68.0

66.5

63.5

57.0

36---31

73

52.0

63.0

66.5

68.0

65.5

62.5

56.5

36---50, 60

74

54.0

63.5

68.5

70.0

66.0

63.0

57.0

42---31

77

55.0

65.5

71.0

72.0

70.0

66.0

59.5

42---50

78

56.0

67.0

71.0

73.5

69.5

66.5

60.0

48---31

79

60.0

66.5

72.5

74.5

73.5

69.0

61.0

48---50, 60

79

58.5

69.0

73.5

74.5

71.5

68.0

62.0

60---30, 50, 60

74

55.0

63.5

67.0

69.0

66.5

62.0

57.0

NOTE

: Tested in accordance with AHRI Standard 270---08 (not listed in AHRI).

CHARGING SUBCOOLING (TXV--TYPE EXPANSION DEVICE)

UNIT SIZE---SERIES

REQUIRED SUBCOOLING* ° F (° C)

18---30

13 (7.2)

24---30

13 (7.2)

30---30, 50

9 (5.0)

36---31

14 (7.8)

36---50, 60

9 (5.0)

42---31

15 (8.3)

42---50

13 (7.2)

48---31

17 (9.4)

48---50, 60

13 (7.2)

60---30, 50, 60

15 (8.3)

NOTE

: Subcooling is for field installed TXV (except for 060)

25H

C

D

3

Summary of Contents for 25HCD3

Page 1: ...ion system S Indoor air quality accessories available Sound S Sound level as low as 69 dBA S Sound levels as low as 69 dBA with accessory sound blanket Comfort S System supports Edger Thermidistatt or...

Page 2: ...M Mark indicates a manufacturer s participation in the program For verification of certification for individual products go to www ahridirectory org STANDARD FEATURES Feature 18 24 30 36 42 48 60 Puro...

Page 3: ...e avoiding excessive capacity loss The suction line diameters shown in the chart below are acceptable for HP systems with Puron refrigerant Vapor Line Sizing and Cooling Capacity Losses Puronr Refrige...

Page 4: ...0 250 250 250 250 24000 HP with Puron 3 8 250 250 250 250 250 250 250 30000 HP with Puron 3 8 250 250 250 250 250 250 250 36000 HP with Puron 3 8 250 250 250 250 250 250 250 42000 HP with Puron 3 8 25...

Page 5: ...X X X X X KHALS0401LLS SOLENOID VALVE X X X X X X X X X X X X X X KHASS0606MPK SNOW STAND RACK X X X X X X X X X X X X X KSASH0601COP SOUND BLKT X X X X X X X X X X X X KSASH2101COP SOUND BLKT X X KA...

Page 6: ...mproves compressor lubrication on restart and minimizes the chance of liquid slugging Usage Guideline Required in low ambient cooling applications Required in long line applications Suggested in all c...

Page 7: ...allow for drainage from unit base Usage Guideline Suggested in the following applications Heat pump installations in heavy snowfall areas Heat pump installations in snow drift locations Heat pump ins...

Page 8: ...OTE Control circuit is 24 V on all units and requires external power source Copper wire must be used from service disconnect to unit All motors compressors contain internal overload protection Complie...

Page 9: ...9 DIMENSIONS ENGLISH 25HCD3...

Page 10: ...10 DIMENSIONS SI 25HCD3...

Page 11: ...0 80 10 0 0 0 10 0 20 0 30 0 40 0 50 0 60 0 70 0 80 0 kW BUILDING HEAT LOSS UNIT INTEGRATED HEATING CAPACITY MBTUH OUTDOOR TEMPERATURE 25HCD324 FB4CNF024 25HCD330 FB4CNF030 25HCD336 FB4CNF036 25HCD360...

Page 12: ...2 24 609 6 Service 6 152 4 12 304 8 24 609 6 Service 24 609 6 Service 24 609 6 Service Note Numbers in mm 18 457 2 18 457 2 12 304 8 IMPORTANT When installing multiple units in an alcove roof well or...

Page 13: ...13 0 33 000 3 54 7 7 20 200 2 40 25HCD342 A W 31 FB4CNF042 42 000 11 0 13 0 39 500 3 60 8 0 24 400 2 40 25HCD342 A W 50 FB4CNF042 42 000 11 0 13 0 39 500 3 62 8 0 24 000 2 44 25HCD348 A W 31 FB4CNF048...

Page 14: ...88 11 57 1 28 20 86 11 27 1 44 19 69 10 90 1 62 18 34 10 46 1 82 16 73 9 90 2 04 14 63 9 20 2 23 EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES F C 75 23 9 85 29 4 95 35 105 40 6 115 46 1 125 51 7...

Page 15: ...2 2 35 66 17 95 2 19 34 05 17 45 2 42 32 19 16 87 2 69 30 14 16 21 2 99 27 89 15 49 3 33 25 30 14 64 3 72 EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES F C 75 23 9 85 29 4 95 35 105 40 6 115 46 1...

Page 16: ...22 2 51 25 27 56 3 02 49 14 26 89 3 39 46 67 26 10 3 81 43 93 25 24 4 25 40 90 24 23 4 73 37 53 23 06 5 25 EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES F C 75 23 9 85 29 4 95 35 105 40 6 115 46...

Page 17: ...02 39 75 7 46 72 22 2 72 25 37 51 4 66 68 77 36 22 5 11 65 08 34 87 5 61 61 18 33 45 6 17 56 96 31 94 6 81 52 49 30 36 7 54 2250 57 13 9 61 41 61 41 4 61 58 94 58 94 5 06 56 30 56 30 5 57 53 46 53 46...

Page 18: ...83 10 51 1 33 14 25 12 96 1 37 16 64 16 64 1 41 18 48 18 48 1 45 19 85 19 85 1 47 INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES F C 3 19 4 7 13 9 17 8 3 27 2 i8 37 2 8 47 8 3 57 13 9 67 19 4 EDB F...

Page 19: ...32 21 33 18 95 2 38 24 75 22 52 2 43 28 47 28 47 2 48 32 48 32 48 2 52 35 27 35 27 2 55 INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES F C 3 19 4 7 13 9 17 8 3 27 2 i8 37 2 8 47 8 3 57 13 9 67 19...

Page 20: ...1 77 3 12 28 69 25 48 3 18 34 39 31 29 3 27 38 75 38 75 3 29 43 56 43 56 3 29 48 57 48 57 3 25 INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES F C 3 19 4 7 13 9 17 8 3 27 2 i8 37 2 8 47 8 3 57 13 9...

Page 21: ...43 65 43 5 01 72 49 72 49 5 17 2000 24 22 22 28 4 16 30 94 28 43 4 27 37 68 34 36 4 36 44 80 39 79 4 49 52 40 47 68 4 65 58 81 58 81 4 79 66 40 66 40 4 93 73 04 73 04 5 08 2250 24 72 22 74 4 23 31 51...

Page 22: ...scharging air upward Condenser fan motors will be totally enclosed 1 phase type with class B insulation and permanently lubricated bearings Shafts will be corrosion resistant Fan blades will be static...

Page 23: ...rconnecting refrigerant tube lengths greater than 80 ft 23 4 m and or elevation differences between indoor and outdoor units greater than 20 ft 6 1 m consult Residential Piping and Longline Guideline...

Page 24: ...orp S 7310 W Morris St S Indianapolis IN 46231 Edition Date 03 13 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 25H...

Reviews: