background image

7

Accessory Description and Usage (Listed Alphabetically) -- CONTINUED

10. Outdoor Air Temperature Sensor

Designed for use with Carrier Thermostats listed in this

publication. This device enables the thermostat to display the
outdoor temperature. This device also is required to enable special

thermostat features such as auxiliary heat lock out.

Usage Guideline:

Suggested for all Carrier thermostats listed in this

publication.

11. Outdoor Thermostat

An SPDT temperature--actuated switch which turns on

supplemental electric heaters when outdoor air temperature drops
below a user--selected set point.

Usage Guideline:

Electric supplemental heat applications in non--variable

speed indoor units when electric heat staging is desired.

12. Secondary Outdoor Thermostat

An SPDT temperature--actuated switch which turns on third--stage

of supplemental electric heaters when outdoor air temperature
drops below the second--stage set point.

Usage Guideline:

Outdoor thermostat applications where electric heater is

capable of 3--stage operation.

13. Snow Stand Rack

Coated wire rack which supports unit 18 in. (457.2 mm) above

mounting pad to allow for drainage from unit base.

Usage Guideline:

Suggested in the following applications:

Heat pump installations in heavy snowfall areas.
Heat pump installations in snow drift locations.
Heat pump installations in areas of prolonged
subfreezing temperatures.
All commercial installations.

14. Sound Hood

Wraparound sound reducing cover for the compressor. Reduces the

sound level by about 2 dBA.

Usage Guideline:

Suggested when unit is installed closer than 15 ft.

(4.577 m) to quiet areas, bedrooms, etc.
Suggested when unit is installed between two houses less

than 10 ft. (3.05 m) apart.

15. Thermostatic Expansion Valve (TXV) Bi--Flow

A modulating flow--control valve which meters refrigerant liquid

flow rate into the evaporator in response to the superheat of the
refrigerant gas leaving the evaporator.

Usage Guideline:

Accessory required to meet AHRI rating and system

reliability, where indoor not equipped.
Required in all heat pump applications designed with
Puron refrigerant.

16. Time--Delay Relay

An SPST delay relay which briefly continues operation of indoor

blower motor to provide additional cooling after the compressor
cycles off.

Note:

Most indoor unit controls include this feature. For those that

do not, use the guideline below.

Usage Guideline:

Accessory required to meet AHRI rating, where indoor

not equipped.

25H

C

D

3

Summary of Contents for 25HCD3

Page 1: ...ion system S Indoor air quality accessories available Sound S Sound level as low as 69 dBA S Sound levels as low as 69 dBA with accessory sound blanket Comfort S System supports Edger Thermidistatt or...

Page 2: ...M Mark indicates a manufacturer s participation in the program For verification of certification for individual products go to www ahridirectory org STANDARD FEATURES Feature 18 24 30 36 42 48 60 Puro...

Page 3: ...e avoiding excessive capacity loss The suction line diameters shown in the chart below are acceptable for HP systems with Puron refrigerant Vapor Line Sizing and Cooling Capacity Losses Puronr Refrige...

Page 4: ...0 250 250 250 250 24000 HP with Puron 3 8 250 250 250 250 250 250 250 30000 HP with Puron 3 8 250 250 250 250 250 250 250 36000 HP with Puron 3 8 250 250 250 250 250 250 250 42000 HP with Puron 3 8 25...

Page 5: ...X X X X X KHALS0401LLS SOLENOID VALVE X X X X X X X X X X X X X X KHASS0606MPK SNOW STAND RACK X X X X X X X X X X X X X KSASH0601COP SOUND BLKT X X X X X X X X X X X X KSASH2101COP SOUND BLKT X X KA...

Page 6: ...mproves compressor lubrication on restart and minimizes the chance of liquid slugging Usage Guideline Required in low ambient cooling applications Required in long line applications Suggested in all c...

Page 7: ...allow for drainage from unit base Usage Guideline Suggested in the following applications Heat pump installations in heavy snowfall areas Heat pump installations in snow drift locations Heat pump ins...

Page 8: ...OTE Control circuit is 24 V on all units and requires external power source Copper wire must be used from service disconnect to unit All motors compressors contain internal overload protection Complie...

Page 9: ...9 DIMENSIONS ENGLISH 25HCD3...

Page 10: ...10 DIMENSIONS SI 25HCD3...

Page 11: ...0 80 10 0 0 0 10 0 20 0 30 0 40 0 50 0 60 0 70 0 80 0 kW BUILDING HEAT LOSS UNIT INTEGRATED HEATING CAPACITY MBTUH OUTDOOR TEMPERATURE 25HCD324 FB4CNF024 25HCD330 FB4CNF030 25HCD336 FB4CNF036 25HCD360...

Page 12: ...2 24 609 6 Service 6 152 4 12 304 8 24 609 6 Service 24 609 6 Service 24 609 6 Service Note Numbers in mm 18 457 2 18 457 2 12 304 8 IMPORTANT When installing multiple units in an alcove roof well or...

Page 13: ...13 0 33 000 3 54 7 7 20 200 2 40 25HCD342 A W 31 FB4CNF042 42 000 11 0 13 0 39 500 3 60 8 0 24 400 2 40 25HCD342 A W 50 FB4CNF042 42 000 11 0 13 0 39 500 3 62 8 0 24 000 2 44 25HCD348 A W 31 FB4CNF048...

Page 14: ...88 11 57 1 28 20 86 11 27 1 44 19 69 10 90 1 62 18 34 10 46 1 82 16 73 9 90 2 04 14 63 9 20 2 23 EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES F C 75 23 9 85 29 4 95 35 105 40 6 115 46 1 125 51 7...

Page 15: ...2 2 35 66 17 95 2 19 34 05 17 45 2 42 32 19 16 87 2 69 30 14 16 21 2 99 27 89 15 49 3 33 25 30 14 64 3 72 EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES F C 75 23 9 85 29 4 95 35 105 40 6 115 46 1...

Page 16: ...22 2 51 25 27 56 3 02 49 14 26 89 3 39 46 67 26 10 3 81 43 93 25 24 4 25 40 90 24 23 4 73 37 53 23 06 5 25 EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES F C 75 23 9 85 29 4 95 35 105 40 6 115 46...

Page 17: ...02 39 75 7 46 72 22 2 72 25 37 51 4 66 68 77 36 22 5 11 65 08 34 87 5 61 61 18 33 45 6 17 56 96 31 94 6 81 52 49 30 36 7 54 2250 57 13 9 61 41 61 41 4 61 58 94 58 94 5 06 56 30 56 30 5 57 53 46 53 46...

Page 18: ...83 10 51 1 33 14 25 12 96 1 37 16 64 16 64 1 41 18 48 18 48 1 45 19 85 19 85 1 47 INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES F C 3 19 4 7 13 9 17 8 3 27 2 i8 37 2 8 47 8 3 57 13 9 67 19 4 EDB F...

Page 19: ...32 21 33 18 95 2 38 24 75 22 52 2 43 28 47 28 47 2 48 32 48 32 48 2 52 35 27 35 27 2 55 INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES F C 3 19 4 7 13 9 17 8 3 27 2 i8 37 2 8 47 8 3 57 13 9 67 19...

Page 20: ...1 77 3 12 28 69 25 48 3 18 34 39 31 29 3 27 38 75 38 75 3 29 43 56 43 56 3 29 48 57 48 57 3 25 INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES F C 3 19 4 7 13 9 17 8 3 27 2 i8 37 2 8 47 8 3 57 13 9...

Page 21: ...43 65 43 5 01 72 49 72 49 5 17 2000 24 22 22 28 4 16 30 94 28 43 4 27 37 68 34 36 4 36 44 80 39 79 4 49 52 40 47 68 4 65 58 81 58 81 4 79 66 40 66 40 4 93 73 04 73 04 5 08 2250 24 72 22 74 4 23 31 51...

Page 22: ...scharging air upward Condenser fan motors will be totally enclosed 1 phase type with class B insulation and permanently lubricated bearings Shafts will be corrosion resistant Fan blades will be static...

Page 23: ...rconnecting refrigerant tube lengths greater than 80 ft 23 4 m and or elevation differences between indoor and outdoor units greater than 20 ft 6 1 m consult Residential Piping and Longline Guideline...

Page 24: ...orp S 7310 W Morris St S Indianapolis IN 46231 Edition Date 03 13 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 25H...

Reviews: