background image

9

Unloader Test Procedure

The unloader is the compressor internal mechanism, controlled by

the DC solenoid, that modulates between high and low stage.  If it

is suspected that the unloader is not working, the following

methods may be used to verify operation.

1. Operate the system and measure compressor amperage.

Cycle the unloader on and off at 30 second plus intervals at

the thermostat (from low to high stage and back to low

stage).  Wait 5 seconds after staging to high before taking a

reading.  The compressor amperage should go up or down

at least 20 percent.

2. If  the expected result is not achieved, remove the solenoid

plug from the compressor and with the unit running and the

thermostat calling for high stage, test the voltage output at

the plug with a DC voltmeter.  The reading should be 24

volts DC.

3. If the correct DC voltage is at the control circuit molded

plug, measure the compressor unloader coil resistance.  The

resistance should be approximately 330 or 1640 ohms de-

pending on unloader coil supplier.  If the coil resistance is

infinite or is grounded, the compressor must be replaced.

Final Checks

IMPORTANT

: Before leaving job, be sure to do the following:

1. Ensure that all wiring is routed away from tubing and sheet

metal edges to prevent rub

through or wire pinching.

2. Ensure that all wiring and tubing is secure in unit before

adding panels and covers. Securely fasten all panels and

covers.

3. Tighten service valve stem caps to 1/12

turn past finger

tight.

4. Leave Owner’s Manual with owner. Explain system opera-

tion and periodic maintenance requirements outlined in

manual.

5. Fill out Dealer Installation Checklist and place in customer

file.

TROUBLESHOOTING

If the compressor fails to operate with a cooling call, the table

below (Resistance table) can be used to verify if there is any

damage to the compressor windings causing system malfunction.

Table 3 – Winding Resistance

Winding

Winding resistance at 70

_

F +/- 20

_

F

(21.11

_

C +/- 11.11

_

C)

024

 036

 048

 060

Start

(S-C)

1.64

1.54

1.86

1.63

Run

(R-C)

1.30

0.88

0.52

0.39

MAJOR COMPONENTS

2

Stage Compressor

The 2

stage compressor contains motor windings that provide

2

pole (3500 RPM) operation.

Compressor Internal Relief

The compressor is protected by an internal pressure relief (IPR)

which relieves discharge gas into compressor shell when

differential between suction and discharge pressures exceeds and

550 

 625 psi. The compressor is also protected by an internal

overload attached to motor windings.

Compressor Control Contactor

The contactor has a 24 volt coil and is controlled by Y input from

the thermostat

High and Low Pressure Switches

High and low pressure switches are provided in line with the Y

signal to the contactor for protection.

CARE AND MAINTENANCE

For continuing high performance and to minimize possible

equipment failure, periodic maintenance must be performed on this

equipment.
Frequency of maintenance may vary depending upon geographic

areas, such as coastal applications. See Users Manual for

information.

25HCB6

Summary of Contents for 25HCB6 Performance Series

Page 1: ...th a suitable warning label EXPLOSION HAZARD Failure to follow this warning could result in death serious personal injury and or property damage Never use air or gases containing oxygen for leak testi...

Page 2: ...uding adverse weather conditions Clearance Requirements When installing allow sufficient space for airflow clearance wiring refrigerant piping and service Allow 24 in 609 6 mm clearance to service end...

Page 3: ...914 4 mm Outdoor units may be connected to indoor section using accessory tubing package or field supplied refrigerant grade tubing of correct size and condition For tubing requirements beyond 80 ft...

Page 4: ...e BEFORE bolting adapter to valve This helps prevent overheating and damage to plastic washer or o ring For Vapor Service Valve remove valve core from schrader port on Service Valve BEFORE brazing Thi...

Page 5: ...sconnect through power wiring hole provided and into unit control box Connect Ground and Power Wires WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or d...

Page 6: ...Below is a brief summary of the furnace airflow configurations 1 The Y2 call for high stage cooling energizes the Cool tap on the control board The grey wire from cool tap is connec ted to tap 5 on th...

Page 7: ...f Cooling With first stage cooling Y and O are powered on and with second stage cooling Y2 Y and O are powered on The O energizes the reversing valve switching it to cooling position The Y signal send...

Page 8: ...IN HIGH STAGE ONLY Factory charge amount and desired subcooling are shown on unit rating plate Charging method is shown on information plate inside unit To properly check or adjust charge conditions...

Page 9: ...and covers 3 Tighten service valve stem caps to 1 12 turn past finger tight 4 Leave Owner s Manual with owner Explain system opera tion and periodic maintenance requirements outlined in manual 5 Fill...

Page 10: ...hours S Do not install a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plastics and roofing materia...

Reviews: