7
ELECTRICAL DATA
UNIT
SIZE ---
SERIES
V/PH
OPER
VOLTS*
COMPR
FAN
MCA
MIN
WIRE
SIZE
{
MIN WIRE
SIZE
{
MAX
LENGTH
ft. (m)
}
MAX
LENGTH
ft. (m)
}
MAX
FUSE**
or CKT
BRK
AMPS
MAX MIN
LRA
RLA
FLA
60
°
C
75
°
C
60
°
C
75
°
C
18---30
208/230/1
253
197
48.0
9.0
0.5
11.7
14
14
67 (20.4)
64 (19.5)
15
24---30
58.3
13.5
0.5
17.3
14
14
46 (14.0)
43 (13.1)
30
30---30
73.0
14.1
0.5
18.1
14
14
44 (13.4)
41 (12.5)
30
36---30
79.0
16.7
1.2
22.0
12
12
57 (17.4)
54 (16.5)
35
42---30
112.0
17.9
1.2
23.6
12
10
53 (16.2)
50 (15.2)
40
48---30
117.0
21.8
1.2
28.4
10
10
70 (21.3)
67 (20.4)
40
60---30
134.0
26.4
1.2
34.2
8
8
91 (27.7)
86 (26.2)
50
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{
If wire is applied at ambient greater than 30° C, consult table 310---16 of the NEC (ANSI/NFPA 70). The ampacity of non---metallic---sheathed cable (NM),
trade name ROMEX, shall be that of 60° C conditions, per the NEC (ANSI/NFPA 70) Article 336---26. If other than uncoated (no---plated), 60 or 75° C
insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA
70).
}
Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.
** Time---Delay fuse.
FLA
--- Full Load Amps
LRA
--- Locked Rotor Amps
MCA
--- Minimum Circuit Amps
RLA
--- Rated Load Amps
NOTE
: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
All motors/compressors contain internal overload protection.
Complies with 2001 requirements of ASHRAE Standards 90.1
A--WEIGHTED SOUND POWER
UNIT SIZE ---
VOLTAGE,
SERIES
STANDARD
RATING
(dBA)
TYPICAL OCTAVE BAND SPECTRUM (dBA, without tone adjustment)‘
125
250
500
1000
2000
4000
8000
18---30
73
56.0
60.0
65.0
69.0
63.0
60.0
52.5
24---30
74
51.0
60.0
66.5
66.5
64.0
60.0
52.5
30---30
74
53.0
62.0
68.5
69.0
65.5
61.0
54.0
36---30
72
52.0
62.0
65.5
67.5
63.0
61.0
53.5
42---30
74
60.0
65.5
68.5
68.5
65.0
60.0
52.5
48---30
73
59.5
63.5
66.5
67.5
64.0
62.0
55.5
60---30
74
55.5
64.0
67.0
69.0
65.0
60.0
54.5
NOTE
: Tested in accordance with ARI Standard 270---95. (Not listed with ARI).
CHARGING SUBCOOLING (TXV--TYPE EXPANSION DEVICE)
UNIT SIZE---VOLTAGE, SERIES
REQUIRED SUBCOOLING
_
F (
_
C)
18---30
10 (5.6)
24---30
10 (5.6)
30---30
11 (6.1)
36---30
10 (5.6)
42---30
12 (6.7)
48---30
9 (5.0)
60---30
9 (5.0)