GUIDE SPECIFICATIONS

GENERAL

System Description

Outdoor--mounted, air--cooled, split--system air conditioner unit
suitable for ground or rooftop installation. Unit consists of a hermetic
compressor, an air--cooled coil, propeller--type condenser fan, and a
control box. Unit will discharge supply air upward as shown on
contract drawings. Unit will be used in a refrigeration circuit to match
up to a packaged fan coil or coil unit.

Quality Assurance

— Unit will be rated in accordance with the latest edition of

ARI Standard 210.

— Unit will be certified for capacity and efficiency, and

listed in the latest ARI directory.

— Unit construction will comply with latest edition of

ANSI/ ASHRAE and with NEC.

— Unit will be constructed in accordance with UL

standards and will carry the UL label of approval. Unit

will have c--UL approval.

— Unit cabinet will be capable of withstanding Federal Test

Method Standard No. 141 (Method 6061) 500--hr salt
spray test.

— Air--cooled condenser coils will be leak tested and

pressure tested.

— Unit constructed in ISO9001 approved facility.

Delivery, Storage, and Handling

— Unit will be shipped as single package only and is stored

and handled per unit manufacturer’s recommendations.

Warranty (for inclusion by specifying engineer)

— U.S. and Canada only.

PRODUCTS

Equipment

— Factory assembled, single piece, air--cooled air

conditioner unit. Contained within the unit enclosure is
all factory wiring, piping, controls, compressor,
refrigerant charge Puron

r

(R--410A), and special features

required prior to field start--up.

Unit Cabinet

— Unit cabinet, including louvered coil guard, will be

constructed of galvanized steel, bonderized, and coated
with a powder coat paint.

Fans

— Condenser fan will be direct--drive propeller type,

discharging air upward.

AIR--COOLED, SPLIT--SYSTEM AIR CONDITIONER

24ACB4

1--1/2 TO 5 NOMINAL TONS

— Condenser fan motors will be totally enclosed, 1--phase

type with class B insulation and permanently lubricated

bearings. Shafts will be corrosion resistant.

— Fan blades will be statically and dynamically balanced.
— Condenser fan openings will be equipped with coated

steel wire safety guards.

Compressor

— Compressor will be hermetically sealed.
— Compressor will be mounted on rubber vibration

isolators.

— Compressor will be covered with a sound absorbing

blanket.

Condenser Coil

— Condenser coil will be air cooled.
— Coil will be constructed of aluminum fins mechanically

bonded to copper tubes which are then cleaned,

dehydrated, and sealed.

Refrigeration Components

— Refrigeration circuit components will include liquid--line

shutoff valve with sweat connections, vapor--line shutoff
valve with sweat connections, system charge of Puron

r

(R--410A) refrigerant, and compressor oil.

— Unit will be equipped with high--pressure switch, low

pressure switch and filter drier for Puron refrigerant.

Operating Characteristics

— The capacity of the unit will meet or exceed _____ Btuh

at a suction temperature of _____

_

F/

_

C. The power

consumption at full load will not exceed _____ kW.

— Combination of the unit and the evaporator or fan coil

unit will have a total net cooling capacity of _____ Btuh
or greater at conditions of _____ CFM entering air

temperature at the evaporator at _____

_

F/

_

C wet bulb

and _____

_

F/

_

C dry bulb, and air entering the unit at

_____

_

F/

_

C.

— The system will have a SEER of _____ Btuh/watt or

greater at DOE conditions.

Electrical Requirements

— Nominal unit electrical characteristics will be _____ v,

single phase, 60 hz. The unit will be capable of

satisfactory operation within voltage limits of _____ v to
_____ v.

— Unit electrical power will be single point connection.
— Control circuit will be 24v.

Special Features

— Refer to section of this literature identifying accessories

and descriptions for specific features and available
enhancements.

Copyright 200

9  

Carrier Corp.

S

7310 W. Morris St.

S

Indianapolis, IN 46231

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Catalog No. 24ACB4---

3

PD

Replaces: 24ACB4---

2

PD

Printed in U.S.A.

Edition Date:

02/09

24AC

B

4

Summary of Contents for 24ACB4 Series

Page 1: ...TRY LEADING FEATURES BENEFITS Efficiency S 14 SEER 11 5 12 0 EER S Microtube Technologyt refrigeration system S Indoor air quality accessories available Sound S Sound level as low as 72 dBA S Compress...

Page 2: ...y Installation of this product should follow all manufacturing refrigerant charging and air flow instructions Failure to confirm proper charge and air flow may reduce energy efficiency and shorten equ...

Page 3: ...60 96 m when outdoor unit is above indoor unit and up to 80 ft 24 38 m when the outdoor unit is below the indoor unit Refer to Accessory Usage Guideline below for required accessories See Longline Ap...

Page 4: ...TART X X X X X X X x Accessory See Accessory Usage Guideline for other accessories needed for low ambient cooling applications THERMOSTATS THERMOSTAT SUBBASE PKG DESCRIPTION TP PRH 01 Programmable The...

Page 5: ...imizes the chance of liquid slugging Usage Guideline Required in low ambient cooling applications Required in long line applications Suggested in all commercial applications 5 Cycle Protector The cycl...

Page 6: ...e superheat of the refrigerant gas leaving the evaporator Kit includes valve adapter tubes and external equalizer tube Hard shut off types are available NOTE When using a hard shut off TXV with single...

Page 7: ...cable tables of the NEC ANSI NFPA 70 Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2 Time Delay fuse FLA Full Load Amps LRA Locked Rot...

Page 8: ...8 DIMENSIONS ENGLISH 24ACB4...

Page 9: ...9 DIMENSIONS SI 24ACB4...

Page 10: ...ious examples Wall Wall Wall Wall 24 Service 6 152 4 mm 24 609 6 Service 24 609 6 Service 24 609 6 Service 24 609 6 Service 24 609 6 24 609 6 24 609 6 12 304 8 12 304 8 12 304 8 12 304 8 6 152 4 Note...

Page 11: ...0 FE4ANF002 UI 18200 13 20 16 00 1 3047289 24ACB418A30 FF1ENP018 17800 11 20 13 50 1 3047290 24ACB418A30 FF1ENP024 18000 11 20 13 50 1 3047291 24ACB418A30 FV4BNF002 18200 13 20 16 00 1 3047286 24ACB41...

Page 12: ...80 14 23200 13 00 15 50 1 3047349 24ACB424A30 CSPH 2412A 58MV B C 080 20 23000 13 00 15 50 1 3047350 24ACB424A30 CSPH 2412A 58MV B C 100 20 23200 13 00 15 50 1 3047351 24ACB424A30 CSPH 2412A 58MV B C...

Page 13: ...30 CNPH 3617A 58MV B C 080 20 28800 12 50 15 00 1 3047439 24ACB430A30 CNPH 3617A 58MV B C 100 20 28600 12 50 15 00 1 3047440 24ACB430A30 CNPH 3617A 58MV B C 120 20 28800 12 50 15 00 1 3047389 24ACB430...

Page 14: ...20 14 50 1 3047514 24ACB436A30 CAP 3617A TDR 35400 11 50 14 00 1 3047521 24ACB436A30 CAP 3621A 58CV A X 110 20 35200 13 00 15 00 1 3101885 24ACB436A30 CAP 3621A 58MEB100 20 35400 12 50 15 00 1 3047518...

Page 15: ...16 35800 13 00 15 25 1 3047507 24ACB436A30 CSPH 3612A 58PH 110 20 35800 13 00 15 25 1 3047548 24ACB436A30 CSPH 3612A TDR 35400 12 00 14 00 1 3047554 24ACB436A30 CSPH 4212A 58CV A X 070 12 35200 12 50...

Page 16: ...H 4821A 58MEB100 20 40000 12 50 15 00 1 3101935 24ACB442A30 CNPH 4821A 58MEB120 20 40000 12 50 15 00 1 3047646 24ACB442A30 CNPH 4821A 58MV B C 040 14 39500 12 20 14 50 1 3047647 24ACB442A30 CNPH 4821A...

Page 17: ...048 41500 13 00 15 00 1 3047682 24ACB442A30 FY4ANF042 40000 11 70 13 50 1 3047683 24ACB442A30 FY4ANF048 40500 11 70 13 50 1 3047748 24ACB448A30 CAP 6024A TDR 48000 11 50 14 00 1 3047777 24ACB448A30 CA...

Page 18: ...24ACB448A30 CSPH 6012A 58MV B C 080 20 46000 12 00 14 20 1 3047772 24ACB448A30 CSPH 6012A 58PH 070 16 47500 11 20 13 50 1 3047773 24ACB448A30 CSPH 6012A 58PH 090 16 48000 12 20 14 50 1 3047774 24ACB4...

Page 19: ...50 14 50 1 3047861 24ACB460A30 FX4CN B F 060 59500 12 00 14 00 1 3047860 24ACB460A30 FY4ANB060 59000 11 50 13 50 1 Tested combination EER Energy Efficiency Ratio SEER Seasonal Energy Efficiency Ratio...

Page 20: ...16 22 16 22 1 75 15 33 15 33 1 95 14 37 14 37 2 18 57 13 9 18 63 18 63 1 24 17 86 17 86 1 39 17 06 17 06 1 56 16 22 16 22 1 75 15 33 15 33 1 95 14 37 14 37 2 18 COOLING INDOOR MODEL CAPACITY POWER FU...

Page 21: ...X 090 16 CNPH 2417A 0 99 0 89 58CV A X 090 16 CNPH 3017A 1 00 0 89 58CV A X 090 16 CNPV 2417A 0 99 0 89 58CV A X 090 16 CNPV 3017A 1 00 0 89 58CV A X 090 16 COOLING INDOOR MODEL CAPACITY POWER FURNACE...

Page 22: ...0 93 58CV A X 090 16 CNPH 3617A 0 99 0 93 58CV A X 090 16 CNPV 3017A 0 99 0 93 58CV A X 090 16 COOLING INDOOR MODEL CAPACITY POWER FURNACE MODEL CNPV 3617A 0 99 0 93 58CV A X 090 16 CSPH 3012A 1 00 0...

Page 23: ...70 16 CAP 3617A 1 01 0 94 58PH 070 16 COOLING INDOOR MODEL CAPACITY POWER FURNACE MODEL CNPH 3017A 1 00 0 94 58PH 070 16 CNPH 3617A 1 00 0 94 58PH 070 16 CNPV 3017A 1 00 0 94 58PH 070 16 CNPV 3617A 1...

Page 24: ...16 CNPV 4217A 0 99 0 95 58CV A X 090 16 CAP 3621A 0 98 0 91 58CV A X 110 20 CAP 4221A 0 99 0 91 58CV A X 110 20 CNPV 3621A 0 98 0 94 58CV A X 110 20 COOLING INDOOR MODEL CAPACITY POWER FURNACE MODEL C...

Page 25: ...CAPACITY POWER FURNACE MODEL CAP 3621A 1 00 0 92 58PH 110 20 CAP 4221A 1 01 0 93 58PH 110 20 CNPH 3617A 0 99 0 95 58PH 110 20 CNPH 4221A 1 00 0 92 58PH 110 20 CNPV 3621A 0 99 0 95 58PH 110 20 CNPV 42...

Page 26: ...00 0 96 58CV A X 110 20 CNPH 4221A 0 99 0 97 58CV A X 110 20 CNPH 4821A 1 00 0 96 58CV A X 110 20 COOLING INDOOR MODEL CAPACITY POWER FURNACE MODEL CNPV 4221A 0 99 0 97 58CV A X 110 20 CNPV 4821A 1 00...

Page 27: ...1A 0 99 0 95 58PH 090 16 CAP 4821A 1 00 0 94 58PH 090 16 CNPH 4221A 0 99 0 95 58PH 090 16 CNPH 4821A 1 00 0 92 58PH 090 16 CNPV 4221A 0 99 0 95 58PH 090 16 CNPV 4821A 1 00 0 92 58PH 090 16 CSPH 4212A...

Page 28: ...5 0 91 58CV A X 090 16 CSPH 6012A 0 97 0 93 58CV A X 090 16 CAP 4821A 0 97 0 93 58CV A X 110 20 CAP 6021A 0 98 0 94 58CV A X 110 20 CNPV 4821A 0 96 0 92 58CV A X 110 20 CAP 4824A 0 98 0 94 58CV A X 13...

Page 29: ...NPV 6024A 0 97 0 97 58CV A X 110 20 CSPH 6012A 0 97 0 97 58CV A X 110 20 CAP 6024A 0 98 0 98 58CV A X 135 22 CNPH 6024A 0 97 0 97 58CV A X 135 22 CNPV 6024A 0 97 0 97 58CV A X 135 22 CSPH 6012A 0 97 0...

Page 30: ...2 78 TCG 33 40 31 70 30 00 28 30 26 50 24 70 22 90 20 90 SDT 72 60 81 80 90 90 100 10 109 30 118 60 127 80 137 10 KW 1 01 1 15 1 31 1 49 1 69 1 92 2 16 2 43 24ACB430A30 30 1 11 TCG 27 40 25 90 24 50 2...

Page 31: ...40 127 50 136 50 KW 2 14 2 43 2 76 3 12 3 53 3 97 4 45 4 97 45 7 22 TCG 60 10 57 00 53 90 50 70 47 30 43 80 40 10 36 20 SDT 74 60 83 50 92 50 101 50 110 50 119 50 128 50 137 40 KW 2 15 2 44 2 77 3 13...

Page 32: ...ricated bearings Shafts will be corrosion resistant Fan blades will be statically and dynamically balanced Condenser fan openings will be equipped with coated steel wire safety guards Compressor Compr...

Reviews: