Exhibit F Remote signal connection
Unit can be operate by following signals;
1) Non-voltage Normal open contact for start & stop (DC24V 10mA)
Wiring the terminal 324 and 323, connect 170 and 326.
Continuous signal
2) Non-voltage Normal open contact for start (DC24V 10mA)
Wiring the terminal 324 and 323, connect 170 and 326.
Non-voltage Normal open contact for stop (DC24V 10mA)
Wiring the terminal 325 and 323.
Pulse signal
3) Non-voltage Normal open contact for start (DC24V 10mA)
Wiring the terminal 324 and 323, connect 170 and 326.
Non-voltage Normal close contact for stop (DC24V 10mA)
Wiring the terminal 325 and 323.
Pulse signal
4) Continuous signal of DC/AC 24V for start & stop. (Initial setting at factory)
Wiring the terminal 324 and 326. (Those terminals are non-polarity)
Continuous signal
5) Pulse signal of DC/AC 24V for start.
Wiring the terminal 324 and 326. (Those terminals are non-polarity)
Pulse signal of DC/AC 24V for stop.
Wiring the terminal 325 and 326. (Those terminals are non-polarity)
DC/AC 24V
Pulse signal
com
326
326
DC/AC 24V
324
325
325
170
Jump
324
326
170
326
Jump
323
324
325
Jump
323
324
323
324
326
170
4Y1
4Y1
4Y2
4Y1
4Y2