DIMENSIONS (ft-in.)
UNIT 16JT
810
812
814
816
818
821
824
828
832
Overall Length A
9-10
9-10
9-10
13-7
13-7
13-7
13-8
13-8
17-6
Overall Width
B
6- 4
6- 4
6- 4
6-2
6-2
6-2
6-7
6-7
6-6
Overall Height C
7- 7
7- 7
7- 7
7-7
7-7
7-7
8-2
8-2
8-4
Height
D*
7- 2
7- 2
7- 2
7-2
7-2
7-2
7-6
7-6
7-1
UNIT 16JT
836
841
847
854
857
865
873
880
Overall Length A
17-6
17- 8
17- 8
17- 8
22-11
22-11
22-11
23- 2
Overall Width
B
6-6
6-11
6-11
7- 4
6-11
6-11
7- 4
7- 7
Overall Height C
8-4
9- 1
9- 1
9- 9
9- 8
9- 8
9- 5
9-11
Height
D*
7-1
7- 5
7- 5
7-10
8- 1
8- 1
7- 8
7-11
DIMENSIONS (mm)
UNIT 16JT
810
812
814
816
818
821
824
828
832
Overall Length A
3000
3000
3000
4140
4140
4140
4165
4165
5335
Overall Width
B
1930
1930
1930
1880
1880
1880
2005
2005
1980
Overall Height C
2310
2310
2310
2310
2310
2310
2490
2490
2540
Height
D*
2185
2185
2185
2185
2185
2185
2285
2285
2160
UNIT 16JT
836
841
847
854
857
865
873
880
Overall Length A
5335
5385
5385
5385
6985
6985
6985
7060
Overall Width
B
1980
2110
2110
2235
2110
2110
2235
2310
Overall Height C
2540
2770
2770
2970
2950
2950
2870
3020
Height
D*
2160
2260
2260
2390
2460
2460
2335
2415
*Standard shipping configuration for sizes 810-880 is one-piece.
Dimension ‘‘D’’ is height of absorber-evaporator section for two-piece shipment. Removal of purge storage tank may reduce height further.
NOTES:
1. All dimensions are approximate and do not take into account absorber-condenser crossover piping if not factory installed as standard.
2. For routine maintenance, allow 3 ft (1 m) clearance on all sides and 6 in. (150 mm) above chiller.
3. For service access, allow clearances as follows:
a. For tube removal, allow space to equal ‘‘A’’ dimension (length) at either end of the chiller.
b. For opening waterbox cover, allow space equal to half of ‘‘B’’ dimension (width) at end of chiller opposite nozzle.
Fig. 3 — Dimensions, 16JT810-880
4