background image

Step 3 — Install Accessory Low-Ambient Kit or
Inlet Filter Kit (If Required) —

If the unit will be op-

erated with inlet air to the condenser below 50 F, a low-
ambient damper may be required. The low-ambient kit con-
trols head pressure by discharge dampers on the condenser
fan. The dampers are actuated by a refrigerant-operated pis-
ton connected to the discharge line of the condenser. If low-
ambient accessory will be used, install it at this time (before
final refrigerant and ductwork connections are made).

An accessory filter rack may also be installed on the con-

denser air inlet to help keep the coil clean. This filter rack
should be installed before the ductwork is attached to the
unit, and before unit is mounted against a wall louver (if
required in your specific application).

Refer to installation instructions provided with the acces-

sories for installation details.

Step 4 — Install Rain Drain (See Fig. 7)

IMPORTANT: A rain drain connection MUST BE
USED if any possibility exists of rain water entering
the unit.

The 09BY unit provides a choice of 2 drain locations. Rain

drain connection can be made on either side of the unit. Block
whichever drain is not being used, but DO NOT BLOCK
BOTH drain locations.

A drain kit is provided (shipped in the fan section). This

kit consists of PVC drain fittings to adapt to field-supplied
threaded pipe. Make connections through the unit side panel.
Some applications may require connection to either galva-
nized steel or copper drain pipe; consult local code require-
ments for details.

If unit is located inside the building, the drain connection

near the refrigerant piping can be used for external drainage.
Run drain connection to a trapped drain, and plug unused
connection.

IMPORTANT: NEVER use pipe smaller than

3

4

in.

in the drain run.

For vertical discharge units, provide a rain drain on the

back of the unit.

Pitch drain pipe downward at a slope of at least

1

4

-in. per

ft for proper drainage. Provide tees plugged on one side for
cleanouts. Leave clearance for servicing, and observe all lo-
cal sanitary codes.

Refer to Carrier System Design Manual for additional pip-

ing details.

Step 5 — Complete Refrigerant Piping

GENERAL — All field leak and pressure testing should be
done in accordance with local code requirements. If a local
code does not exist, use ASHRAE (American Society of Heat-
ing, Refrigeration and Air Conditioning Engineers) Stand-
ard 15, Safety Code for Mechanical Refrigeration.

For leak testing procedures, refer to the Carrier ‘‘Refrig-

erant Service Techniques’’ book, Form SFT-01.

For any parts that need to be removed, use a mini tubing

cutter. Perform phos-copper brazing on all field-made con-
nections while protecting adjacent joints from heat.
REFRIGERANT LINE SIZING — Sizing depends on length
of lines between various sections of the refrigerant system.
Consider the amount of liquid lift and drop in the system as
well as proper compressor oil return. Consult Carrier
System Design Manual, Part 3, or Carrier E20-II

t

Refrig-

erant Piping Computer Program for proper piping sizes and
design.

PRESSURE RELIEF — The ASHRAE Standard 15, Safety
Code for Mechanical Refrigeration states: ‘‘Every refriger-
ating system shall be protected by a pressure relief device or
some other means designed to safely relieve pressure due to
fire or other abnormal conditions.’’ Since 09BY condensers
do not have pressure relief devices, one must be field sup-
plied and installed either before the liquid line service valve
or inside the 09BY unit. Each circuit must have its own pres-
sure relief.

If desired, the pressure relief requirement can also be sat-

isfied by installing a fusible plug in the liquid line. To do so,
install a tee in the liquid line with a

1

4

-in. NPT fitting on the

tee side, and install a fusible plug (part no. EK02KK105 or
similar). The temperature rating of the fusible plug should
be between 205 F and 220 F (96 C and 104 C). If a service
valve is used on the liquid line, be sure that both the piping
system and the condenser are protected for relief if all serv-
ice valves are closed. Note that if the condenser is located
indoors, requirements for venting the fusible plug to the out-
doors may apply. Consult local code requirements.

REFRIGERANT RECEIVER — A refrigerant receiver is not
furnished with 09BY condensers and is not recommended
for normal applications.

NOTE: Dimensions in [

] are in millimeters.

Fig. 7 — Rain Drains

8

Summary of Contents for 09BY006

Page 1: ...Follow all safety codes Wear safety glasses and work gloves Keep quenching cloth and fire extinguisher nearby when braz ing Use care in handling rigging and setting bulky equipment ELECTRIC SHOCK HAZARD Separate power sources main and control power circuits are used for these units Be sure both main and control power circuits are disconnected before servicing GENERAL The 09BY air cooled condenser ...

Page 2: ...Fig 1 09BY Unit 008 014 Shown 2 ...

Page 3: ...ONDITIONED SPACE HANGER RODS TO RAIN DRAIN REQUIRED IF RAIN WILL ENTER UNIT TO REFRIGERANT PIPING COMPRESSOR EVAPORATOR UNIT OUT IN OUTSIDE WALL HEIGHT AS REQUIRED FOR WINDOW OR WALL OPENING POWER CONNECTION WALL LOUVERS FIELD SUPPLIED 50BZ 09BY TO RAIN DRAIN REQUIRED IF RAIN WILL ENTER UNIT FLOOR STAND 09BY IN REMOTE APPLICATION WITH DUCTWORK Shown Suspended from Ceiling 09BY DIRECT CONNECTION TO...

Page 4: ...7 16 K 3 51 8 4 01 4 4 75 8 5 31 4 7 01 4 L 1 105 8 2 3 2 3 2 3 2 9 M 0 19 16 0 19 16 0 19 16 0 19 16 0 31 8 N 0 6 0 7 0 7 0 7 0 10 P 2 5 2 9 3 2 3 7 4 6 R 1 2 1 5 1 5 1 5 2 0 Fig 3 Base Unit Dimensions 09BY DIMENSIONS SI DIMENSION 006 mm 008 mm 012 mm 014 mm 016 024 mm A 902 1087 1087 1087 1526 B 500 600 600 600 850 C 1231 1422 1613 1804 2300 D 590 701 701 701 911 E 282 357 357 357 502 F 156 150 ...

Page 5: ...s recommended on the left side 2 ft is the minimum One side of the unit either right left or rear should have the following minimum clearance for removal of the blower shaft UNIT SIZE APPROX SHAFT LENGTH in 006 41 0 008 47 0 012 51 0 014 51 0 016 55 5 024 73 0 Fig 3 Base Unit Dimensions cont CORNER WEIGHTS Lb UNIT SIZE A B C D 006 55 73 59 42 008 61 89 73 44 012 86 114 93 64 014 107 142 114 78 016...

Page 6: ...Pulley Size in 511 16 75 8 65 8 611 16 10 1311 16 Motor Pulley Range in 43 16 51 2 43 16 51 2 4 5 4 5 43 4 6 53 8 65 8 Rpm Range 1365 1566 960 1260 1106 1455 1045 1306 840 1050 686 847 Maximum Fan Rpm 1705 1365 1365 1365 1210 955 Belt Quantity Size 1 A41 1 B46 1 B45 2 A45 2 B88 3 B90 Pulley Center Line Distance in 11 2 12 6 13 6 15 0 13 6 15 0 13 6 15 0 32 6 33 8 30 0 30 7 Fan Shaft mm 20 25 25 25...

Page 7: ...ors Unit may be supported by its 4 corners or a field supplied support rail may be used for each side Size isolators with the corner weights shown in Fig 3 Units may also be suspended from above See Positioning the 09BY Unit section below and Fig 5 for recommended support and isolator mounting Ductwork attached to the condenser should be isolated from the unit with a flexible collar on the inlet a...

Page 8: ... Manual for additional pip ing details Step 5 Complete Refrigerant Piping GENERAL All field leak and pressure testing should be done in accordance with local code requirements If a local code does not exist useASHRAE American Society of Heat ing Refrigeration and Air Conditioning Engineers Stand ard 15 Safety Code for Mechanical Refrigeration For leak testing procedures refer to the Carrier Refrig...

Page 9: ... typical connection of a 2 circuit condenser for use on one circuit Three circuit units 024 may be manifolded in any combi nation of 1 2 or 3 circuits per compressor When manifold ing circuits NEVER CONNECT TWO SEPARATE COM PRESSOR EVAPORATOR CIRCUITSTOGETHER ON THE SAME CONDENSER CIRCUIT Pipe sizes for the com bined circuit should be no smaller than the sizes shown in Table 3 Table 3 Minimum Refr...

Page 10: ...charge openings and another bird screen is provided remove factory supplied screen to reduce static pressure loss Units 09BY006 014 have a factory installed flange to connect ductwork to the con denser air inlet Units 09BY016 and 024 are provided with flanges taped inside the unit for shipping To attach the duct to the unit inlet mount the flange by removing the screws that hold the condenser coil...

Page 11: ...n Table 4 and phases must be balanced within 2 Contact local power com pany for line voltage corrections Never operate a motor where a phase imbalance in supply voltage is greater than 2 Use the following formula to determine the percentage of volt age imbalance Voltage Imbalance max voltage deviation from average voltage 100 x average voltage Example Supply voltage is 240 3 60 AB 243 v BC 236 v A...

Page 12: ... to the national and applicable local codes For field power connections all main power wiring enters the unit through a factory punched access hole under the con trol box Attach power wires to the 3 power connections in the unit control box using field supplied wirenuts Be sure to install a ground wire See Fig 11 CONTROL CIRCUIT POWER WIRING Connect 24 v control wires to the 2 low voltage connecti...

Page 13: ...lt Clean coils with a vacuum cleaner fresh water com pressed air or a bristle brush not wire Backflush coil to remove debris Commercial coil cleaners may also be used to help remove grease and dirt Steam cleaning is NOT rec ommended Units installed in corrosive environments should be cleaned as part of a planned maintenance schedule In this type of application all accumulations of dirt should be c...

Page 14: ... 1154 3 79 1214 4 40 6000 892 2 49 984 2 99 1058 3 48 1163 4 31 1283 5 63 1346 6 17 7000 1040 3 96 1129 4 60 1187 5 17 1255 5 66 1348 6 72 8000 1189 5 91 1274 6 74 1323 7 24 014 5000 777 1 19 894 1 62 990 1 98 1077 2 34 1166 2 73 1258 3 21 6000 932 2 06 1033 2 60 1118 3 04 1196 3 47 1268 3 92 1343 4 35 7000 1088 3 27 1176 3 88 1255 4 45 1323 4 96 8000 1243 4 89 1323 5 61 9000 016 6000 578 0 83 655...

Page 15: ...m cleaner or compressed air Coil can be reached through access panels Inspection Check coil baffles for tight fit to prevent air from bypassing the coil Check panels for air leakage particularly those sealing the fan and coil compartments Check for loose electrical connections oil level proper refrigerant charge and refrigerant piping leaks The 09BY fan motor and fan shaft bearings are permanently...

Page 16: ...il or plugged or restricted air filter and or louvers 2 Airflow is not adequate 1 Check and clean coil filter and louver as required 2 Check airflow and determine if proper subcooling is provided Unit is noisy 1 Airflow is turned too high 2 Belt and pulley are not properly aligned 3 Proper vibration isolation has not been applied 1 Slow down motor and check discharge pressure 2 Check and adjust al...

Page 17: ......

Page 18: ...cturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 2 4 Tab 4a 4a PC 111 Catalog No 530 969 Printed in U S A Form 09BY 2SI Pg 18 9 96 Replaces 09BY 1SI ...

Page 19: ...HAVE THERMOSTAT AND INDOOR FAN CONTROL WIRING CONNECTIONS BEEN MADE AND CHECKED Y N ARE ALL WIRING TERMINALS including main power supply TIGHT Y N HAS CRANKCASE HEATER IF EQUIPPED ON UNIT BEEN ENERGIZED FOR 24 HOURS Y N 09BY UNIT HAS WATER BEEN PLACED IN DRAIN PAN IF REQUIRED TO CONFIRM PROPER DRAINAGE Y N ARE PROPER AIR FILTERS IN PLACE Y N HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGN...

Page 20: ...MEASUREMENTS OIL PRESSURE Where Appropriate SUCTION PRESSURE SUCTION LINE TEMP DISCHARGE PRESSURE DISCHARGE LINE TEMP ENTERING CONDENSER AIR TEMP LEAVING CONDENSER AIR TEMP EVAP ENTERING AIR DB dry bulb TEMP EVAP ENTERING AIR WB wet bulb TEMP EVAP LEAVING AIR DB TEMP EVAP LEAVING AIR WB TEMP COMPRESSOR AMPS CIRCUIT A L1 L2 CIRCUIT B L1 L2 CIRCUIT C L1 L2 NOTES CUT ALONG DOTTED LINE CUT ALONG DOTTE...

Reviews: