Carrier 09AZ091-182 Installation, Start-Up And Service Instructions Manual Download Page 13

13

START-UP

Complete Unit Start-Up Checklist on page CL-1 during ini-

tial start-up of this system.

System Evacuation and Dehydration — 

Refer to

GTAC II, Module 4, ‘‘Dehydration for Proper Evacuation and

Dehydration Techniques.’’

Charging Procedure — (Units Matched with
30HX Chillers)

1. An initial refrigerant charge must be added after evacua-

tion to allow the unit to start. Add approximately 2 lb/

nominal ton (0.26 kg/nominal kW) liquid refrigerant

charge to the condenser. This amount of charge should be

sufficient to allow the unit to start. The approximate sys-

tem charges are shown in the installation manual for the

30HX chillers.

2. Raise the compressor discharge to approximately 125 F

(51.7 C) saturated discharge temperature (185 psig

[1276 kPa]) by throttling the condenser air (or water) in-

take.

3. Add liquid charge into the cooler until there is approxi-

mately 18 to 20 F (10.0 to 11.1 C) of system subcooling

(saturated discharge temperature — actual temperature

entering the electronic expansion device [EXD]). When

adding charge, use the 

1

/

4

-in. Schrader-type fitting locat-

ed on the tube going into the bottom of the cooler. This

fitting is located between the EXD and the cooler. When

adding charge during unit operation, always use this port

so that the cooler liquid level sensor can detect the addi-

tional charge and adjust the EXD valve position.
NOTE: Electronic Expansion Device (EXD) refers to

EXV (Electronic Expansion Valve) (30HX076-146 units)

or Economizer (30HX161-271 units).

4. Check for a clear sight glass. If the unit is not fully load-

ed, the sight glass may be flashing. This condition is nor-

mal for a partially loaded unit. If the unit is fully loaded

and the sight glass is flashing, check EXV valve position.

If it is greater than 60% add additional charge.

SERVICE

Fan Guard Removal — 

Remove the eight 

1

/

4

- x 

5

/

8

-in.

self-tapping hex-head screws that hold the fan grille to the

condenser-fan panel, and remove the grille.

Condenser Fan Adjustment

1. Be sure power is off to the condenser-fan motor.
2. Remove the fan guard.
3. Remove the cap, and set screws on the fan hub.
4. Adjust fan. See Fig. 10.
5. Tighten fan hub securely on the motor shaft with set

screw that bears against the key.

6. Replace the permagum sealing material and the rubber

cap over the end of the motor shaft to prevent moisture

from causing fan to rust on the shaft.

7. Replace the fan guard.

Fan Motor Removal

1. Make certain condenser power is off.
2. Remove fan guard and fan.
3. Loosen nut on the motor holding clamp that secures mo-

tor to motor support.

4. Lift motor upward. Remove the fan wheel through the fan

discharge opening. Remove wire connectors.

5. Replace in opposite order. Be sure to check location of

fan in orifice when replacing fan.

MAINTENANCE

Cleaning — 

The 09AZ units should be thoroughly cleaned

inside and out. Frequency of cleaning depends on unit location

and area conditions.

Cleaning Condenser Coils — 

Clean coils with a vac-

uum cleaner, fresh water, compressed air, or a bristle brush (not

wire).

The 09AZ units require very little maintenance. Regular

maintenance should include cleaning the surface of the coil and

checking to make sure that all electrical connections are tight.

All motors have permanently sealed ball bearings that do not

require lubrication. Check for loose electrical connections, oil

level, proper refrigerant charge, and refrigerant piping leaks.

Backflush coil to remove debris. Commercial coil cleaners

may also be used to help remove grease and dirt. Steam clean-

ing is NOT recommended. Wash coil in the opposite direction

of airflow. Units installed in corrosive environments should

be cleaned as part of a planned maintenance schedule. In this

type of application, all accumulations of dirt should be cleaned

off the coil. Condenser-fan motors are drip-proof but not

watertight.

Lubrication — 

Fan motors have permanently lubricated

ball bearings; no additional lubrication is required.

TROUBLESHOOTING

See Table 5 for problems and possible solutions.

To prevent personal injury, be sure wire fan guards are

secured in place over each fan discharge (or that fans are

ducted), before starting the unit.

To prevent personal injury, be sure wire fan guards are

secured in place over each fan discharge before starting the

unit.

Do not use high-pressure water or air to clean condenser

coils. Damage to fins may result.

FILL HOLE IN FAN HUB
WITH PERMAGUM

FAN BLADE

HUB PLATE

HUB

FAN SHAFT

TOP
COVER

1/3 HEIGHT OF FAN
BLADE ABOVE VENTURI LIP

Fig. 10 — Location of Propeller on Motor Shaft

from Outside of Orifice Ring

Downloaded from 

ManualsNet.com

 search engine

Summary of Contents for 09AZ091-182

Page 1: ...d fire extinguisher nearby when brazing Use care in handling rigging and setting bulky equipment Separate power sources main and control power circuits are used for these units Be sure both main and control power circuits are disconnected before servicing Electrical shock could cause personal injury DO NOT USE TORCH to remove any component System contains oil and refrigerant under pressure To remo...

Page 2: ...ing weights dis tance between lifting holes center of gravity and spreader bar dimensions If overhead rigging is not possible place unit on skid or pad for rolling or dragging When dragging pull the pad Do not apply force to the unit When in final position raise from above to lift unit off skid PLACING UNIT The 09AZ units are designed for outdoor applications If the unit is mounted indoors provisi...

Page 3: ...th Contactors D Fan Cycling TEAO Circuiting Option A Single Circuit Subcooling E Dual Circuit Subcooling Factory Options A Aluminum Cabinet B Fused Disconnect D Aluminum Cabinet Fused Disconnect F Fused Disconnect 115 Volt Transformer Packaging 1 Standard Design Series 0 First Design V Ph Hz 1 575 3 60 3 208 230 1 60 5 208 230 3 60 6 460 3 60 Coil Construction Option Aluminum Fin Copper Tube C Cop...

Page 4: ... 3164 2590 4032 3110 3081 3730 3820 Shipping Weight 2705 3374 2800 4242 3370 3450 4040 4130 REFRIGERANT Type 134a FAN Type Direct Drive Vertical Discharge Quantity 8 10 8 10 10 12 12 12 Diameter in 26 26 26 26 26 26 26 26 No of Blades 4 4 4 4 4 4 4 4 Max Rpm 1140 1140 1140 1140 1140 1140 1140 1140 Total Airflow Cfm 124 000 155 000 124 000 155 000 155 000 186 000 186 000 186 000 Motor Hp 11 2 11 2 ...

Page 5: ...YP 194 1 4 96 TYP 1 1 8 TYP 15 6 6 242 1 4 48 96 TYP 1 1 8 TYP 15 CONTROL PANEL RETURN BEND COVER LIFTING HOLE 1 1 2 DIA TYP 6 290 1 4 96 TYP 1 1 8 TYP 15 6 IN DISCHARGE GAS 3 1 8 DIA LIQUID 2 5 8 DIA AIRFLOW 47 000 60 20 20 20 09AZV 1 A Single Circuit NOTES 1 Service clearances must be at least 48 in on all sides 2 Field assembly of discharge liquid headers required 09AZV091 101 09AZV151 09AZV171...

Page 6: ... 1 1 2 DIA TYP 194 1 4 96 TYP 1 1 8 TYP 6 6 242 1 4 48 96 TYP 1 1 8 TYP CONTROL PANEL RETURN BEND COVER LIFTING HOLE 1 1 2 DIA TYP 6 290 1 4 96 TYP 1 1 8 TYP 6 6 IN 46 DISCHARGE GAS 2 5 8 DIA DISCHARGE GAS 2 5 8 DIA 94 LIQUID 2 1 8 DIA LIQUID 2 1 8 DIA AIRFLOW 6 5 5 6 6 5 5 09AZV 2 E Dual Circuit NOTE Service clearances must be at least 48 in on all sides 09AZV102 122 09AZV112 132 142 09AZV162 172...

Page 7: ...02 605 467 462 560 573 H 308 373 377 316 403 311 308 373 382 1 2 LEG BOLTS Fig 4 Unit Rigging A ROTATE UNIT FLAT 1 Gently pull top of unit over maintaining cable tension as unit is rotated from vertical to horizontal position B LOWERING LEGS INTO POSITION 1 Reattach lifting hooks into lifting eyes in the perma nently attached leg channels One set of hooks at each leg position 2 Remove the four 1 2...

Page 8: ...nual Part 3 or the Carrier E20 II Software Refrigerant Piping program for proper piping sizes and design 4 Hot gas lines should rise above refrigerant level in condenser circuit 5 Trap should be installed on hot gas lines to prevent condenser oil and refrigerant vapor migration from accumulating on com pressor heads during off cycle 6 For piping lengths greater than 50 ft 15 2 m provide support to...

Page 9: ...ing speed control head pressure control winter start control fan cycling and electrical interlock may affect wiring connec tions Refer to Fig 7 9 for typical unit wiring 1 Power entry is at one end only 2 Fan motors are thermally protected All 3 phase motors are protected against primary single phasing conditions 3 Replacement of factory wires must be with appliance wiring material rated 105 C or ...

Page 10: ...5 1 60 09AZV SIZE 208 230 3 60 460 3 60 575 3 60 CONTROL CIRCUIT V Ph Hz FLA MCA MOCP Min Max Volts FLA MCA MOCP Min Max Volts FLA MCA MOCP Min Max Volts 102 6 5 53 6 60 0 187 253 3 3 27 2 30 0 414 506 2 4 19 8 20 0 518 632 115 1 60 112 6 5 66 0 70 0 187 253 3 3 33 8 35 0 414 506 2 4 24 6 25 0 518 632 115 1 60 122 6 5 56 3 60 0 187 253 3 3 27 2 30 0 414 506 2 4 19 8 20 0 518 632 115 1 60 132 6 5 6...

Page 11: ...60 C copper conductors only 2 See nameplate for branch circuit fuse size use time delay fuse only 3 Motors 1 and 2 are located at header end of unit 4 All wire is 14 ga except as noted C Contactor FB Fuse Block MTR Motor Downloaded from ManualsNet com search engine ...

Page 12: ...tor FB Fuse Block NOTES 1 Use 60 C copper conductors only 2 See nameplate for branch circuit fuse size use time delay fuse only 3 Motors 1 and 2 are located at header end of unit 4 All wire is 14 ga except as noted Downloaded from ManualsNet com search engine ...

Page 13: ...the key 6 Replace the permagum sealing material and the rubber cap over the end of the motor shaft to prevent moisture from causing fan to rust on the shaft 7 Replace the fan guard Fan Motor Removal 1 Make certain condenser power is off 2 Remove fan guard and fan 3 Loosen nut on the motor holding clamp that secures mo tor to motor support 4 Lift motor upward Remove the fan wheel through the fan di...

Page 14: ...not operating correctly 1 Check head pressure control and be sure it is operating properly Install if not provided 2 Check wind baffles apply if required 3 Check operation of fan cycling control on two fan units Unit trips on low pressure at start up with low outdoor temperatures 1 Winterstart kit not installed or not working correctly 2 Fan cycling control for two fan units is not installed or no...

Page 15: ... TO CONFIRM PROPER DAINAGE Y N ________ ARE PROPER AIR FILTERS IN PLACE Y N ________ CONTROLS HAVE THERMOSTAT INDOOR FAN CONTROL AND CONDENSER FAN CONTROL RELAY WIRING CONNECTIONS BEEN MADE AND CHECKED Y N ________ ARE ALL WIRING TERMINALS including main power supply TIGHT Y N ________ HAS CRANKCASE HEATER IF EQUIPPED ON UNIT BEEN ENERGIZED FOR 24 HOURS Y N ________ 09AZ UNIT CHECK POWER SUPPLY DO...

Page 16: ...FTER AT LEAST 15 MINUTES RUNNING TIME RECORD THE FOLLOWING MEASUREMENTS OIL PRESSURE Where Appropriate ________ ________ SUCTION PRESSURE ________ ________ SUCTION LINE TEMP ________ ________ DISCHARGE PRESSURE ________ ________ DISCHARGE LINE TEMP ________ ________ ENTERING CONDENSER AIR TEMP ________ ________ LEAVING CONDENSER AIR TEMP ________ ________ EVAP ENTERING AIR DB dry bulb TEMP _______...

Reviews: