SERVICE

Protection Devices

HIGH-PRESSURE 

SWITCH — Check by throttling con-

denser water or blocking airflow on air-cooled units, allowing
head pressure to rise gradually. Check discharge pressure
constantly throughout procedure. Compressor should shut off
within 10 psi of values shown in Table 4.
LOW-PRESSURE SWITCH — Check  by  slowly  closing
suction shutoff valve or by completely closing liquid line
shutoff valve. A decrease of suction pressure will follow.
Compressor should shut off within 4 psi of values shown in
Table 4.
OIL PRESSURE SWITCH (OPS) — The oil pressure switch
protects against damage from loss of oil or loss of oil pressure
during unit start-up. If the oil pressure differential sensed by the
OPS is 6 psig or less on unit start-up, the switch remains closed
and the OPS heater is energized.

The switch time delay is approximately 45 seconds. If after

45 seconds the oil pressure differential sensed by the OPS is
less than 11 psig, the heater remains energized. The OPS
temperature actuated switch then opens and the compressor is
deenergized. If the differential reaches 11 psig, the OPS opens
and deenergizes the heater and the system operates normally.
See Table 4.

To restart the unit, push the OPS reset button and then push

the control circuit switch on the unit control box to OFF and
then to ON.

Table 4 — Factory Switch Settings

NOTES:
1. Values for the high- and low-pressure switches based on R-22.

For other refrigerants, reset to pressure corresponding to satura-
tion temperatures indicated by the listed pressures.

2. Values for oil pressure are above operating suction pressure

(pressure differential between suction and discharge pressures
of oil pump).

TIME GUARD® CONTROL — The  Time  Guard  control
protects against short cycling. See Start Compressor.
CRANKCASE HEATER — The  crankcase  heater  prevents
absorption of liquid refrigerant by oil in crankcase during brief
or extended shutdown periods. Source of 115-volt power is the
auxiliary control power, independent of the main unit power.
This assures compressor protection even when main unit
power disconnect switch is off.

Compressor Thermal Protection — 

A discharge

temperature sensor, installed in one cylinder head, detects an
overtemperature condition. If the discharge temperature

exceeds 295 ± 5 F, the sensor contacts open and the compressor
shuts down. The sensor reset temperature is 235 F minimum.
See Fig. 8 for control circuit connections.

Capacity Control System

CAPACITY CONTROL VALVE (Fig. 9) — Valve  is  con-
trolled by suction pressure and actuated by discharge pressure.
Each valve controls 2 cylinders. On start-up, controlled
cylinders do not load up until differential between suction and
discharge pressures is approximately 25 psi. See Table 5.

CAPACITY CONTROL VALVE ADJUSTMENTS
Control Set Point (Cylinder Load Point) — Adjustable from
0 to 86 psig. Pressure differential between cylinder load-up
point and cylinder unload point is adjustable from 6 psi
to 16 psi.

IMPORTANT: If the oil pressure switch causes unit lock-
out, determine and correct the cause of the lockout (such as
loss of compressor oil or flooded compressor) before
restarting the unit. Failure to correct the cause of OPS
lockout may constitute abuse. Equipment failure due to
abuse is not covered by warranty.

SWITCH TYPE

PRESSURE CHANGE AFFECTING

SWITCH POSITION (psig)

Closed

Open

High Pressure

210 (±10)

290 (±10)

Low Pressure

70 (±4)

60 (±4)

Oil Pressure

6

11

IMPORTANT: Never open any switch or disconnect that
will deenergize the crankcase heater unless unit is being
serviced or is to be shut down for a prolonged period. After
a prolonged shutdown or a service job, energize the crank-
case heater for 24 hours before starting the compressor.

IMPORTANT: Do not use automatic pumpdown control
on 06E,07E units equipped with unloader valves. Use
single pumpout or solenoid drop (minimum protection)
control.

CONTROL
SET POINT
ADJUSTMENT
NUT

VALVE BODY

SEALING CAP

(COVERS PRESSURE DIFFERENTIAL

ADJUSTMENT SCREW)

Fig. 9 — Capacity Control Valve

TIMER
CONTACTS

BLU

ORN

B2

B1

CR

4

6

RED

C1

C2

C2

DTS

BLU

YEL

TB2

6

C2

C1

B

LEGEND

Fig. 8 — Discharge Temperature Sensor (DTS)

C

Compressor Contactor

CR

Control Relay

DTS

Discharge Temperature Sensor

TB

Terminal Block

Splice (in compressor junction box)

Summary of Contents for 06E

Page 1: ... Wear safety glasses and work gloves Use care when handling rigging and setting bulky equipment INSTALLATION Receive and Inspect Unit Inspect shipment for damage File claim with the shipping company if shipment is damaged or parts are missing Local water conditions can cause excessive fouling or pitting of condenser tubes If such conditions are anticipated a water treatment analysis is recommended...

Page 2: ...ly voltage is greater than 2 Use the following formula to determine the voltage imbalance Voltage Imbalance Example Supply voltage is 240 3 60 AB 243 volts BC 236 volts AC 238 volts Determine maximum deviation from average voltage AB 243 239 4 volts BC 239 236 3 volts AC 239 238 1 volt Maximum deviation is 4 volts Determine voltage imbalance This amount of phase imbalance is satisfactory as it is ...

Page 3: ...5 9 16 9 5 16 460 575 78 43 3 4 2 3 4 34 26 1 21 5 9 16 9 5 16 D044 208 230 69 1 2 49 3 4 2 3 4 34 27 1 2 1 21 4 1 8 8 5 8 460 575 69 1 2 49 3 4 2 3 4 34 27 1 2 1 21 4 1 8 8 5 8 NOTES 1 For standard service practices such as trouble shooting and refrigerant charging allow a minimum 2 6 clearance around the unit 2 Recommended service space for condenser tube removal is one condenser length at eithe...

Page 4: ...2 460 575 501 4 29 367 8 11 2 26 1 191 2 W044 208 230 501 4 35 367 8 11 2 271 2 1 191 2 460 575 501 4 35 367 8 11 2 271 2 1 191 2 Fig 3 06E Hermetic Compressor Units Fig 4 06E Compressors NOTES 1 For standard service practices such as troubleshooting and refrigerant charging allow a minimum 2 6 clearance around the unit 2 For compressor removal allow a minimum 3 wide access aisle to and from the u...

Page 5: ...ive COMPRESSOR MOTOR DATA CIRCUIT BREAKER Compressor Part Number 06E Voltage 3 Ph 60 Hz Hp Maximum Must Trip Amps Maximum RLA LRA XL LRA PW first winding Motor Winding Resistance Ohms Recommended Circuit Breaker Part No MHA MTA LRA Recommended RLA A 250 208 230 20 108 87 345 207 0 32 HH83XB336 91 104 350 74 3 575 45 36 120 72 2 2 XA461 33 38 124 27 1 460 54 44 173 104 1 3 XA424 42 49 175 35 0 265 ...

Page 6: ...ntact rating must be 25 va 5 60 Hz units have 120 volt control circuit 50 Hz units have 230 volt control circuit A separate source of supply at the correct voltage must be field supplied through a fused disconnect device with a maximum rating of 15 A to TB2 connections Hot Side and Neutral 6 Open control circuit disconnect switch for servicing only Discon nect must remain closed for crankcase heat...

Page 7: ...oil fill plug above bull s eye add oil through plug hole and replace plug Run compressor for about 20 min utes and check the oil level TO REMOVE OIL Pump down compressor to 2 psig Loosen the 1 4 in pipe plug in compressor base and allow the oil to seep out past the threads of the plug The crankcase will be under slight pressure Be careful not to remove the plug the entire oil charge may be lost Ta...

Page 8: ...er Functions See Fig 7 Timer Cycle 1 Switch A contacts A A1 and A A2 provides Time Guard function Start of compressor is delayed approxi mately 5 5 minutes after shutoff The minimum time between starts of compressor is 8 minutes 2 Switch B contacts B B1 and B B2 starts compressor and deenergizes the crankcase heater These contacts also provide one second time delay for part winding start 3 Switch ...

Page 9: ...his assures compressor protection even when main unit power disconnect switch is off Compressor Thermal Protection A discharge temperature sensor installed in one cylinder head detects an overtemperature condition If the discharge temperature exceeds 295 5 F the sensor contacts open and the compressor shuts down The sensor reset temperature is 235 F minimum See Fig 8 for control circuit connection...

Page 10: ...alves One side bank cylinder head is a bypass unloading type plugged with a spring loaded piston plug assembly As received the compres sor will run fully loaded Replacing Suction Cutoff Unloading Heads When the original compressor is equipped with suction cutoff unloading head s the complete cylinder head and control valve assem blies must be transferred to the service replacement compres sor See ...

Page 11: ...11 NOTE Pressure operated control valve shown A solenoid operated control valve can also be used Fig 10 Suction Cutoff Unloader Operation ...

Page 12: ... Oil Sight Glass Lock Washer 19 Pipe Plug Hex Head 20 Crankshaft 21 Ring Spacer when required 22 Bearing Washer 23 Connecting Rod and Piston Assembly 24 Connecting Rod and Cap Assembly 25 Piston Piston Pin and Retaining Ring Package 26 Piston Rings Oil and Compression 27 Terminal Plate Assembly 28 Terminal Bolt Assembly 29 Terminal Box 30 Terminal Box Mounting Screw 4 31 Suction Valve 32 Valve Pla...

Page 13: ...65 lb ft torque Bolt drive segment to crankshaft 4 Insert the oil feed guide vane with large diameter inward Place oil feed guide vane spring over small diameter of guide vane 5 Install pump cover plate SIZE DIAM in THREADS PER IN TORQUE RANGE lb ft USAGE 1 16 27 pipe 8 12 Pipe Plug Crankshaft 1 4 18 pipe 20 25 Pipe Plug Crankcase 1 4 20 8 10 Conn Rod Cap Screw 8 12 Junction Box 1 4 28 3 5 Sight G...

Page 14: ...k ets and suction valves on dowel pins backer is under the valve see Fig 15 Place valve plate on cylinder deck and reinstall discharge valve assembly Retorque discharge valve stop cap screws to 16 lb ft Replace cylinder head Be sure tab on cylinder head gasket is lined up with tabs on cylinder head and valve plate Terminal Plate Assembly If there is a refrigerant leak between the terminal plate an...

Page 15: ...1 Check ring gap by inserting each ring separately in cylin der approximately 3 8 in from top Ring gap should be between 0 002 in and 0 007 inch 2 Install compression ring in top piston groove with either side up no difference Install oil ring below compression ring with notched end on bottom Stagger ring gaps 180 degrees 3 Measure side clearance between ring and piston Table 6 Check rings for fre...

Page 16: ...above stator temperature Check stator for damage to windings and lead wires Use a megohmmeter to check for grounds or shorts between windings Motor Replacement STATOR AND ROTOR Install stator halfway into hous ing Insert the terminal leads first guiding them to terminal plate opening as stator is being inserted Replace ring spacer Fig 11 item 21 on crankshaft Ease rotor onto shaft until it begins ...

Page 17: ... strainer If filter drier or suction strainer is dirty or discolored repeat this step until system is clean Condenser Maintenance 07E Units To inspect and clean condenser drain water and remove condenser heads To drain condenser shut off water supply and disconnect inlet and outlet piping Remove drain plugs and vent plug With condenser heads removed inspect tubes for refrigerant leaks Refer to Car...

Page 18: ...CTION CONDENSER 3 TO 4 VENT PIPE 5 APPROX 1 PIPE Fig 24 Gravity Circulation SUCTION PUMP SUPPORT TANK FINE MESH SCREEN RETURN GAS VENT PUMP PRIMING CONN GLOBE VALVES 1 PIPE CONDENSER REMOVE WATER REGULATING VALVE CENTRIFUGAL PUMP 1 2 HP 30 GPM AT 35 HEAD CLOSE VENT PIPE VALVE WHEN PUMP IS RUNNING Fig 25 Forced Circulation ...

Page 19: ......

Page 20: ...r change at any time specifications or designs without notice and without incurring obligations PC 802 Catalog No 530 607 Printed in U S A Form 06 07E 2SI Pg 20 7 02 Replaces 06 07E 1SI Book 2 2 4 4 Tab 1b 2a 2b 3a Copyright 2002 Carrier Corporation ...

Reviews: