background image

: Service Manual

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

15

extreme high pressure. The relief port has an operating range between

550  to  625  psig  differential  pressure  (Copeland)  and  550  to  650  psig

differential  pressure  (Danfoss)  for  R-410A  refrigerant.  Scrolls  have  a

variety  of  shut  down  solutions,  depending  on  model,  to  prevent

backward rotation and eliminate the need for cycle protection.

Compressor Failures

Compressor  failures  are  classified  in  2  broad  failure  categories;

mechanical and electrical. Both types are discussed below.

Mechanical Failures

A  compressor  is  a  mechanical  pump  driven  by  an  electric  motor

contained in a welded or hermetic shell. In a mechanical failure, motor

or  electrical circuit  appears  normal,  but compressor  does  not function

normally.

Locked Rotor

In this type of failure, compressor motor and all starting components are

normal. When compressor attempts to start, it draws locked rotor current

and cycles off on internal protection. Locked rotor current is measured

by  applying  a  clamp-on  ammeter  around  common  (blk)  lead  of

compressor. Current drawn when it attempts to start is then measured.

Locked rotor amp (LRA) value is stamped on compressor nameplate.
If compressor draws locked rotor amps and all other external sources of

problems have been eliminated, compressor must be replaced. Because

compressor  is  a  sealed  unit,  it  is  impossible  to  determine  exact

mechanical  failure.  However,  complete  system  should  be  checked  for

abnormalities  such  as  incorrect  refrigerant  charge,  restrictions,

insufficient airflow across indoor or outdoor coil, etc., which could be

contributing to the failure. 

Runs, Does Not Pump

In this type of failure, compressor motor runs and turns compressor, but

compressor does not pump refrigerant. A clamp-on ammeter on common

leg  shows  a  very  low  current  draw,  much  lower  than  rated  load  amp

(RLA) value stamped on compressor nameplate. Because no refrigerant

is  being  pumped,  there  is  no  return  gas  to  cool  compressor  motor.  It

eventually overheats and shuts off on its internal protection.

Noisy Compressor

Noise  may  be  caused  by  a  variety  of  internal  and  external  factors.

Careful  attention  to  the  “type”  of  noise  may  help  identify  the  source.

The  following  are  some  examples  of  abnormal  conditions  that  may

create objectionable noise:

1. A gurgling sound may indicate a liquid refrigerant floodback during

operation.    This  could  be  confirmed  if  there  is  no  compressor

superheat.  A compressor superheat of “0” degrees would indicate

liquid  refrigerant  returning  to  the  compressor.    Most  common

reasons for floodback are: loss of evaporator blower, dirty coils, and

improper airflow.

2. A  rattling  noise  may  indicate  loose  hardware.    Inspect  all  unit

hardware including the compressor grommets.

3. An internal “thunking”, “thumping”, “grinding” or “rattling” noise

could indicate compressor internal failures and may be verified by

comparing the compressor amperage to what the compressor should

be drawing according to a manufacturer’s performance data.

4. A  whistling  or  squealing  noise  during  operation  may  indicate  a

partial blockage of the refrigerant charge.

5. A  whistle  on  shut  down  could  indicate  a  partial  leak  path  as

refrigerant  is equalizing from high to  low side.   On  occasion, an

in-line discharge check valve has prevented this sound.

6. If  a  compressor  hums  but  won’t  start  it  could  indicate  either  a

voltage or amperage issue.  Verify adequate voltage and operational

start components if installed.  If it is drawing excessive amperage

and voltage doesn’t appear to be the problem it may be assumed a

locked  condition.    Ensure  refrigerant  has  had  ample  time  to

equalize and boil out of the compressor before condemning.

7. When a heat pump switches into and out of defrost, a ”swooshing”

noise  is  expected  due  to  the  rapid  pressure  change  within  the

system.  Check that the defrost thermostat or thermistor is operating

properly. Insulating the defrost sensing device may also help. 

Electrical Failures

The compressor mechanical pump is driven by an electric motor within

its  hermetic  shell.  In  electrical  failures,  compressor  does  not  run

although  external  electrical  and  mechanical  systems  appear  normal.

Compressor must be checked electrically for abnormalities.
Before  troubleshooting  compressor  motor,  review  this  description  of

compressor motor terminal identification.

Single-Phase Motors

To identify terminals C, S, and R:

1. Turn off all unit power.
2. Discharge run and start capacitors to prevent shock.
3. Remove all wires from motor terminals.
4. Read resistance between all pairs of terminals using an ohmmeter

on 0-10 ohm scale.

5. Determine 2 terminals that provide greatest resistance reading.  

Through elimination, remaining terminal must be common (C). Greatest

resistance between common (C) and another terminal indicates the start

winding  because  it  has  more  turns. This  terminal  is  the  start  (S). The

remaining terminal will be run winding (R). 

NOTE: 

If compressor is hot, allow time to cool and internal line break

to reset. There is an internal line break protector which must be closed.
All compressors are equipped with internal motor protection. If motor

becomes hot for any reason, protector opens. Compressor should always

be allowed to cool and protector to close before troubleshooting. Always

turn off all power to unit and disconnect leads at compressor terminals

before taking readings. 
Most  common  motor  failures  are  due  to either  an  open,  grounded,  or

short circuit. When a compressor fails to start or run, 3 tests can help

determine  the  problem.  First,  all  possible  external  causes  should  be

eliminated, such as overloads, improper voltage, pressure equalization,

defective capacitor(s), relays, wiring, etc. Compressor has internal line

break overload, so be certain it is closed.

WARNING

!

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Do  not  supply  power  to  unit  with  compressor  terminal  box  cover

removed.

WARNING

!

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Exercise  extreme  caution  when  reading  compressor  currents  when

high-voltage power is on. Correct any of the problems described below

before installing and running a replacement compressor.

Summary of Contents for 024-036

Page 1: ...ns Rotating fan blades can cause personal injury Appropriate safety considerations are posted throughout this manual where potentially dangerous techniques are addressed Follow all safety codes Wear safety glasses protective clothing and work gloves Have a fire extinguisher available Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the u...

Page 2: ... low ambient cooling applications Suggested in all commercial applications 2 Evaporator Freeze Thermostat An SPST temperature actuated switch that stops unit operation when evaporator reaches freeze up conditions Usage Guideline Required when low ambient kit has been added 3 Isolation Relay An SPDT relay which switches the low ambient controller out of the outdoor fan motor circuit when the heat p...

Page 3: ...ls must meet the original equipment specifications Insulation must meet NFPA 90A requirements for flame spread and smoke generation Foam gaskets that are in the conditioned air stream must meet the requirements of UL 94 5VA for flammability Instructions for insulation installation 1 Apply adhesive on non foil side of the insulation 2 Align insulation to the panel 3 Care must be taken while applyin...

Page 4: ... reserves the right to change at any time specifications and designs without notice and without obligations 4 A220851 Fig 3 Unit Base Dimensions Small Medium Cabinet with Full Louver 13 4 SEER2 HEAT PUMP 13 4 SEER2 AIR CONDITIONER ...

Page 5: ... the right to change at any time specifications and designs without notice and without obligations 5 A220853 Fig 4 Unit Base Dimensions Heat Pump Air Conditioner Large Cabinet with Full Slots 13 4 SEER2 HEAT PUMP 13 4 SEER2 AIR CONDITIONER ...

Page 6: ...acturer reserves the right to change at any time specifications and designs without notice and without obligations 6 A220854 Fig 5 13 4 SEER2 Air Conditioner Medium and Large Cabinet with Louvers 13 4 SEER2 Air Conditioner ...

Page 7: ... panel to access components above See Fig 7 3 Access or removal of the condenser coil a Removal of the top the control compressor panel the front left side louver panel b Screws from the compressor compartment and either the side of the unit or below the condenser fan depending on the shape of coil will need to be removed to remove condenser coil See Fig 8 4 Access or removal of the evaporator coi...

Page 8: ...ons 8 Labeling The wiring schematic sub cooling charging tables with instructions and warning labels Refer to Fig 10 for label location A10163 Fig 10 Label Location FIELD CONNECTIONS BLOWER PANEL WIRING DIAGRAM ON BACKSIDE OF CONTROL FRONT OF CONTROL COMPRESSOR PANEL WARNING ADVERTISSMENT WARNING ADVERTISSMENT WARNING ADVERTISSMENT ...

Page 9: ...0k scale Using an analog ohmmeter check each terminal to ground use capacitor case Discard any capacitor which measures 1 2 scale deflection or less Place ohmmeter leads across capacitor and place on R X 10k scale Meter should jump to a low resistance value and slowly climb to higher value Failure of meter to do this indicates an open capacitor If resistance stays at 0 or a low value capacitor is ...

Page 10: ...s or heat pumps R 410A pressure switches are identified by a pink stripe down each wire Low Pressure Switch Neither of the air conditioner or heat pump units have a low pressure switch The heat pump models have a loss of charge switch located downstream of the liquid line filter drier See loss of charge for more details High Pressure Switch AC HP The high pressure switch is located in the discharg...

Page 11: ...at or Off the valve is de energized There is no compressor delay built into this control A05332 Fig 14 Defrost Control Heating Sequence of Operation On a call for heating thermostat makes R Y and R G Circuit R Y sends low voltage through the safeties and energizes the contactor which starts the compressor and energizes the T1 terminal on the circuit board The T1 terminal energizes the defrost logi...

Page 12: ...gations 12 A220832 Fig 15 DFT Sensor Location 024 048 SEE DETAIL B DETAIL SEE DETAIL D DETAIL D SEE DETAIL F DETAIL SEE DETAIL H DETAIL H HIURVW WKHUPRVWDW FDQ HLWKHU EH ORFDWHG RQ WKH ERWWRP RI WXEH DV VKRZQ RU RQ WKH WRS DQG PXVW QRW LQWHUIHUH ZLWK DQ RWKHU WXELQJ 030 036 13 4 SEER2 042 13 4 SEER2 048 13 4 SEER2 024 13 4 SEER2 ...

Page 13: ...Whether the unit is in heating or cooling mode it will run a defrost cycle for 10 minutes each time the compressor has been energized for the selected time interval The board will terminate automatically after 10 minutes of defrost time regardless of defrost thermostat position If defrost thermostat is stuck open The unit will not defrost If unit will not defrost 1 Perform the speedup function as ...

Page 14: ...0 F 10ºC to 70 F 21 1ºC Resistance goes from zero to when contacts are open 8 If either opening or closing temperature does not fall within above ranges or thermostat sticks in 1 position replace thermostat to ensure proper defrost operation NOTE With timing cycle set at 90 minutes unit initiates defrost within approximately 21 sec When you hear the reversing valve changing position remove screwdr...

Page 15: ... manufacturer s performance data 4 A whistling or squealing noise during operation may indicate a partial blockage of the refrigerant charge 5 A whistle on shut down could indicate a partial leak path as refrigerant is equalizing from high to low side On occasion an in line discharge check valve has prevented this sound 6 If a compressor hums but won t start it could indicate either a voltage or a...

Page 16: ... sources of problems have been eliminated compressor must be replaced Because compressor is a sealed unit it is impossible to determine exact mechanical failure However complete system should be checked for abnormalities such as incorrect refrigerant charge restrictions insufficient airflow across indoor or outdoor coil etc which could be contributing to the failure Runs Does Not Pump In this type...

Page 17: ...not run although external electrical and mechanical systems appear normal Compressor must be checked electrically for abnormalities Before troubleshooting compressor motor review this description of compressor motor terminal identification Single Phase Motors To identify terminals C S and R 1 Turn off all unit power 2 Short the run and start capacitors to prevent shock 3 Remove all wires from moto...

Page 18: ...mpressor Removal and Replacement Once it is determined that compressor has failed and the reason established compressor must be replaced 1 Shut off all power to unit 2 Remove and recover all refrigerant from system until pressure gages read zero psig Use all service ports 3 Disconnect electrical plug from compressor Disconnect or remove crankcase heater if equipped and remove compressor holddown n...

Page 19: ...ing or first stage heating for heat pumps O Energizes reversing valve on heat pumps C Common side of transformer G Indoor Fan Ground Circuit To determine if a wire has broken or come in direct contact with shell causing a direct short to ground follow these steps 1 Recover all refrigerant charge 2 Using an ohmmeter on R X 10 000 ohm scale or megohmmeter follow manufacturer s instructions 3 Be sure...

Page 20: ...checked such as frost or condensate water on refrigerant tubes The sound made by a reversing valve as it begins or ends defrost is a whooshing sound as the valve reverses and pressures in system equalize An experienced service technician detects this sound and uses it as a valuable troubleshooting tool Using a remote measuring device check inlet and outlet line temperatures DO NOT touch lines If r...

Page 21: ...tor with liquid refrigerant The bleed hole allows a small amount of oil and refrigerant to enter the return line where velocity of refrigerant returns it to compressor If bleed hole plugs oil is trapped in accumulator and compressor will eventually fail from lack of Table 3 Compressor Information 13 4 SEER2 AC Unit Size 24 30 36 42 48 60 Type Emerson Scroll Emerson Scroll Emerson Scroll LG Scroll ...

Page 22: ...tdown TXVs are specifically designed to operate with R 410A refrigerant use only factory authorized TXV s Do not interchange R 410A and R 22 TXVs TXV Operation The TXV is a metering device that is used in air conditioning and heat pump systems to adjust to changing load conditions by maintaining a preset superheat temperature at the outlet of the evaporator coil The volume of refrigerant metered t...

Page 23: ...ston TXV Number Outdoor Heating Piston Number 13 4 SEER2 24 57 30 63 36 67 42 76 48 80 60 TXV Heat Pump Unit Size ton Indoor Cooling Piston TXV Number Outdoor Heating Piston Number 13 4 SEER2 24 57 30 63 55 36 67 57 42 76 59 48 TXV 60 TXV 70 WARNING PERSONAL INJURYAND ENVIRONMENTAL HAZARD Failure to relieve system pressure could result in personal injury and or death 1 Relieve pressure and recover...

Page 24: ...power to unit 2 Recover refrigerant from system through high flow service valves 3 Break vacuum with nitrogen 4 Remove top cover See Access Compressor or other internal cabinet component Fig 6 Fig 8 5 Remove screws in coil panels 6 Use midget tubing cutter to cut liquid and vapor lines at both sides of coil Cut in convenient location for easy reassembly with copper slip couplings 7 Lift coil verti...

Page 25: ...and assure a tight dry system before charging The 2 methods used to evacuate a system are the deep vacuum method and the triple evacuation method Deep Vacuum Method The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gauge capable of accurately measuring this vacuum depth The deep vacuum method is the most positive way of assuring a system is free ...

Page 26: ...ely not controlling properly i e stuck open REPLACE VALVE If superheat is higher than 15 F proceed to Step 3 3 Perform TXV function check With system running place sensing bulb in ice bath for 1 minute superheat should increase If no response Replace Valve If OK proceed to Step 4 4 Check for even temperature distribution at outlet of each circuit of evaporator If greater than 15 F between circuits...

Page 27: ...air return air wet bulb temperature with a sling psychrometer or electronic equivalent 6 Using Superheat Charging Table Table 6 find outdoor temperature and indoor air wet bulb temperature At this intersection note superheat Where a dash appears on table do not attempt to charge unit under these conditions or refrigerant slugging may occur In this situation refrigerant must be evacuated and weighe...

Page 28: ... for Safe Electric Heater Operation Air Conditioner AC Unit Size Minimum Airflow CFM 5 kW 7 5 kW 10 kW 15 kW 20 kW 24 600 750 750 X X 30 600 750 750 X X 36 600 750 750 1050 X 42 600 750 750 1050 X 48 600 750 750 1050 1400 60 600 750 750 1050 1400 Heat Pump HP Unit Size Minimum Airflow CFM 5 kW 7 5 kW 10 kW 15 kW 20 kW 24 750 800 800 X X 30 750 800 800 X X 36 750 800 800 1200 X 42 750 800 800 1200 ...

Page 29: ...12 107 102 97 92 2785 45 42 39 36 33 414 114 109 104 99 94 2854 46 43 40 37 34 424 116 111 106 101 96 2923 47 44 41 38 35 434 118 113 108 103 98 2992 48 45 42 39 36 444 119 114 109 104 99 3061 48 46 43 40 37 454 121 116 111 106 101 3130 49 47 44 41 38 464 123 118 113 108 103 3199 50 48 45 42 39 474 124 119 114 109 104 3268 51 48 46 43 40 484 126 121 116 111 106 3337 52 49 47 44 41 494 127 122 117 ...

Page 30: ...ower off to the unit Disconnect the two plugs going into the motor One plug is the high voltage supply and the other is the low voltage control Cycle power back on and measure the high voltage supply plug to determine if there is voltage at plug If there is no voltage at plug determine if there is power to the unit The easiest place to measure the voltage is on the line side of the contactor If th...

Page 31: ...ntrol panel will expose most of the unit s components Both the air conditioner and heat pump control boxes will be in the upper right corner of the unit There will be a contactor that cycles components off and on The capacitor will assist the outdoor fan and compressor to operate The heat pump models will have a circuit board to control the defrost cycle Always replace these devices with the Facto...

Page 32: ...lectric Heat wiring interconnection electric heater controls removed for clarity Electric Heat Control Box shown uninstalled Electric Heat wiring interconnection electric heater controls removed for clarity Electric Heat Control Box shown uninstalled Air Conditioning Control Box Wiring Heat Pump Control Box Wiring A10030 A10031 HIGH VOLTAGE POWER WIRING ENTRY HOLE LOW VOLTAGE WIRING ENTRY HOLE gro...

Page 33: ...ual Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 33 A210120 Fig 33 Typical Air Conditioning Single Phase Unit Connection Electrical Diagram ...

Page 34: ...anual Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 34 A210121 Fig 34 Typical Air Conditioning Single Phase Unit Ladder Electrical Diagram ...

Page 35: ...ervice Manual Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 35 A210797 Fig 35 Typical Heat Pump Unit Connection Electrical Diagram ...

Page 36: ... Service Manual Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 36 A210799 Fig 36 Typical Heat Pump Unit Ladder Electrical Diagram ...

Page 37: ...d basepan 5 Reinstall side panel 6 Reconnect electrical power and check for proper operation Cleaning Outdoor Fan Motor and Blade 1 Remove grille fan motor and blade Be careful not to bend or dent fan blade 2 Clean motor and blade with soft brush or cloth Be careful not to disturb balance weights on fan blade 3 Check fan blade setscrew for tightness 4 Reinstall fan motor and blade to grille and ch...

Page 38: ...3 53 5 592 147 9 64 4 58 7 3 13 7 160 56 2 13 4 262 86 9 30 5 364 110 0 43 3 466 128 7 53 7 596 148 4 64 7 60 8 6 13 0 162 57 0 13 9 264 87 4 30 8 366 110 4 43 6 468 129 0 53 9 600 149 0 65 0 62 10 0 12 2 164 57 7 14 3 266 87 9 31 1 368 110 8 43 8 470 129 3 54 1 604 149 5 65 3 64 11 3 11 5 166 58 4 14 7 268 88 4 31 3 370 111 2 44 0 472 129 7 53 2 608 150 1 65 6 66 12 6 10 8 168 59 0 15 0 270 88 9 ...

Page 39: ...TIVE RUN CAPACITOR OUTDOOR FAN STOPPED OR CYCLING ON OVERLOAD OUTDOOR AIR RESTRICTED OR RECIRCULATING RESTRICTED DISCHARGE TUBE OVERCHARGE OR NON CONDENSABLES IN SYSTEM LOW REFRIGERANT CHARGE LINE VOLTAGE TOO HIGH OR LOW DEFECTIVE RUN CAPACITOR COMPRESSOR BEARINGS HIGH SUPERHEAT LOOSE LEAD AT FAN MOTOR MOTOR DEFECTIVE LOW SUCTION PRESSURE DIRTY AIR FILTERS DUCT RESTRICTED DAMPERS PARTLY CLOSED COM...

Page 40: ...OAD CONDITION REVERSING VALVE JAMMED IN MIDPOSITION HIGH SUPERHEAT DEFECTIVE FAN MOTOR CAPACITOR LOOSE LEADS AT FAN MOTOR FAN MOTOR BURNED OUT LOW SUCTION LOW HEAD OUTDOOR FAN STOPPED LOOSE LEADS AT OUTDOOR FAN MOTOR INTERNAL FAN MOTOR KLIXON OPEN FAN MOTOR BURNED OUT DEFROST RELAY N C CONTACTS OPEN ON CIRCUIT BOARD REVERSING VALVE DID NOT SHIFT UNIT NOT PROPERLY CHARGED OUTDOOR FAN RUNNING REVERS...

Page 41: ...R OUTDOOR FAN STOPPED OR CYCLING ON OVERLOAD OUTDOOR AIR RESTRICTED OR RECIRCULATING DAMAGED OR STUCK REVERSING VALVE RESTRICTED DISCHARGE TUBE OVERCHARGE OR NON CONDENSABLES IN SYSTEM LOW REFRIGERANT CHARGE LINE VOLTAGE TOO HIGH OR LOW DEFECTIVE RUN CAPACITOR COMPRESSOR BEARINGS HIGH SUPERHEAT LOOSE LEAD AT FAN MOTOR DEFROST RELAY N C CONTACTS OPEN MOTOR DEFECTIVE LOW SUCTION PRESSURE DIRTY AIR F...

Reviews: