INSTALLATION

1. Inspect package contents for missing or damaged parts.

File a claim with the shipping agency if parts are

damaged and notify your local Carrier representative if

any item is missing.

2. Determine the new location for the cooler. Ensure that the

new location supports the cooler and economizers

weights and that there is enough room for service access

and tube removal. See Tables 4A and 4B to determine

refrigeration line sizes. See Table 5 for cooler and

economizers weights. See Fig. 4A-5B for cooler and

economizers dimensions, tube removal clearances, and

service areas.

3. Open and tag all electrical disconnects.

Cooler and Economizer Removal — 

The cooler and

economizers are accessible from the cooler side of the unit. To

remove the cooler and economizers from the unit, complete the

following steps:

1. Remove refrigerant from all circuits using standard

refrigeration practices. Refer to unit nameplate or installa-

tion instructions for refrigerant quantities.

2. Disconnect the cooler heater wiring, and conduit if

equipped.

3. Remove entering and leaving chilled water temperature

thermistors. Make sure to label thermistors as they are

removed. See Fig. 6.

4. Disconnect and label the chilled water flow switch cable

from the chilled water flow switch located on the leaving

water nozzle. See Fig. 6.

5. Disconnect the suction pressure transducer cables from

the transducers. Make sure to label cables as they are

removed. See Fig. 6.

NOTE: The suction pressure transducers (SPT) do not neces-

sarily need to be removed. However, use care in protecting the

SPTs throughout the removal and remote installation processes,

as the SPTs are an important part of the remote installation.

6. Disconnect the electronic expansion valve (EXV) cables

from the EXVs at each economizer. Make sure to label

cables as they are removed. See Fig. 6.
NOTE: The 30XA080 units do not utilize an economizer.

In this case, only the EXVs are present.

7. Unbolt the cooler suction flanges from the cooler. Tempo-

rary supports may be needed to support the suction pipes.

See Fig 6.

8. At each circuit’s economizer, cut the liquid lines going to

the economizer assembly before the manual shutoff valve

(see Fig. 6, cut 1, circuits A and B). Cut the cooler liquid

lines between the manual shutoff valve and the cooler

(see Fig. 6, cut 2, circuits A and B). Cut the economizer

lines between the manual shutoff valve and the sensors

(see Fig. 6, cut 3, circuits A and B).

9. Remove the screws from the feet of each economizer.

Save all of the screws. Remove the economizers by care-

fully sliding them out the cooler side of the unit.

10. Remove the screws from the cooler feet. Save all of the

screws. Slide the cooler slightly to the left to clear the

refrigerant tubing.

11. Remove the cooler by carefully sliding the cooler out the

cooler side of the unit. 

Shut off all power to this equipment prior to installation.

There may be more than one disconnect switch. Tag all

disconnect locations to alert others not to restore power

until work is completed. Failure to disconnect power from

equipment prior to installation could result in serious

personal injury or death.

Because 30XA systems use polyolester oil, which can ab-

sorb moisture, it is important to minimize the amount of

time that the refrigeration system is left exposed to the at-

mosphere. Minimizing the exposure time will reduce the

amount of moisture that could possibly damage the unit.

The removal instructions minimize the exposure time to

prevent this type of damage. The remote installation in-

structions outline a dehydration process to counteract any

exposure that might have occurred.

Before installation of the field-supplied piping, the piping

must be thoroughly cleaned and free of dirt, debris, oil, and

welding residue. Presence of these objects will cause severe

damage to the compressors or other components of the re-

frigeration system.

Summary of Contents for 00EFN900003000A

Page 1: ...owing constraints Operating chilled water temperature is between 40 and 55 F 4 4 and 12 8 C When the remote cooler is applied the cooler heaters will not function so it is critical to maintain the water temperature above the freezing point at all times If the water temperature falls below the freezing point the cooler does not have protection to keep the water from freezing The interior space temp...

Page 2: ... from dropping below the minimum level in the oil separator Add 1 gallon of oil to each circuit Refer to Controls Start up Operation Service and Troubleshooting Guide for recommended oil type Table 3A Refrigeration Piping and Connections Material English Table 3B Refrigeration Piping and Connections Material SI ACCESSORY PACKAGE PART NO ITEM NO DESCRIPTION PART NO QTY 00EFN900003000A 1 Economizer ...

Page 3: ...NDOOR LOCATION 15 FT MAX Fig 1 30XA Unit and Cooler Level Piping Parallel Single Circuit Shown Fig 2 30XA Unit and Cooler Level Piping Elevated Single Circuit Shown Fig 3 30XA Unit with Cooler Located Below Unit Single Circuit Shown a30 4509 a30 4510 a30 4511 LEGEND Liquid Line Economizer Line Suction Line LEGEND Liquid Line Economizer Line Suction Line LEGEND Liquid Line Economizer Line Suction L...

Page 4: ...g 6 NOTE The 30XA080 units do not utilize an economizer In this case only the EXVs are present 7 Unbolt the cooler suction flanges from the cooler Tempo rary supports may be needed to support the suction pipes See Fig 6 8 At each circuit s economizer cut the liquid lines going to the economizer assembly before the manual shutoff valve see Fig 6 cut 1 circuits A and B Cut the cooler liquid lines be...

Page 5: ...3 15 8 15 8 15 8 15 8 11 8 11 8 30XA UNIT SIZE SUCTION LINE DOUBLE SUCTION RISERS COOLER LIQUID LINE CONDENSER LIQUID LINE ECONOMIZER LINE Circuit A Circuit B Circuit A mm Circuit B mm Riser A mm Riser B mm Riser A mm Riser B mm Circuit A mm Circuit B mm Circuit A mm Circuit B mm Circuit A mm Circuit B mm 080 79 79 41 67 41 67 29 29 29 29 090 79 79 41 67 41 67 29 29 29 29 22 22 100 79 79 41 67 41 ...

Page 6: ...ecommended service clearance around the cooler is 36 in 914 mm 3 Recommended cooler tube removal area either end is 109 in 2769 mm NOTES 1 Measurements are shown in inches millimeters 2 Recommended service clearance around the cooler is 36 in 914 mm 3 Recommended cooler tube removal area either end is 109 in 2769 mm 1 2 13 13 16 20 8 9 32 210 117 3 4 2991 52 1 4 1327 21 1 32 534 52 1 4 1327 SIDE V...

Page 7: ...C 30XA180 240 Cooler Dimensions Fig 4D 30XA260 350 Cooler Dimensions NOTES 1 Measurements are shown in inches millimeters 2 Recommended service clearance around the cooler is 36 in 914 mm 3 Recommended cooler tube removal area either end for 30XA180 200 is 1093 8 in 2779 mm 4 Recommended cooler tube removal area either end for 30XA220 240 is 1085 8 in 2758 mm NOTES 1 Measurements are shown in inch...

Page 8: ...3 8 746 8 3 4 222 5 8 17 7 16 12 2 1 4 56 SIDE VIEW END VIEW TOP VIEW Fig 5A 30XA090 160 Economizer Dimensions Fig 5B 30XA180 350 Economizer Dimensions NOTES 1 Measurements are shown in inches millimeters 2 Recommended service clearance around the economizer is 36 in 914 mm NOTES 1 Measurements are shown in inches millimeters 2 Recommended service clearance around the economizer is 36 in 914 mm a3...

Page 9: ...HIDDEN SUCTION PRESSURE TRANSDUCER HIDDEN CUT 2 COOLER LIQUID LINE CUT 1 LIQUID LINE CUT 3 ECONOMIZER LINE CUT 3 ECONOMIZER LINE CUT 1 LIQUID LINE MANUAL SHUTOFF VALVE CUT 2 COOLER LIQUID LINE CIRCUIT B COOLER SUCTION FLANGES CIRCUIT A CONT ENTERING CHILLED WATER LEAVING CHILLED WATER THERMISTORS CHILLED WATER FLOW SWITCH MANUAL SHUTOFF VALVE CIRCUIT A ELECTRONIC EXPANSION VALVES 2 ELECTRONIC EXPA...

Page 10: ... and gaskets are used an extra M16 mounting hole must be drilled and tapped to connect a mounting bracket at the 30XA base unit See Fig 10 and 11 for mounting bracket placement See Fig 12 for mounting hole locations If additional gaskets are needed for installation they must be 1 16 in non asbestos fiber with synthetic rubber binder compressed gasket sheet An extra mounting hole also needs to be f...

Page 11: ...ed junction box 3000A or 3100A Item 5 19 Reinstall the thermistors in the correct cooler wells 20 To reconnect the suction pressure transducers SPT locate the SPT plugs for circuits A and B and cut the leads where they can be conveniently spliced in the installed junction box at the 30XA base unit Label the leads SPTA for the circuit A lead and SPTB for the circuit B lead 21 Take the two pieces of...

Page 12: ...ex Connector Flange O ring 3000A Item 13 Accessory supplied Flex Connector Flange 3000A Item 10 Flex Connector Flange O ring 3000A Item 13 220 Field supplied ASME B16 9 Stub End 4 in 102 mm Accessory supplied Compressor Flange Gasket 3100A Item 9 Loose Pipe Flange 3100A Item 11 Field supplied ASME B16 9 Stub End 4 in 102 mm Accessory supplied Compressor Flange Gasket 3100A Item 9 Loose Pipe Flange...

Page 13: ...em 8 325 Field supplied ASME B16 9 Stub End 4 in 102 mm Accessory supplied Compressor Flange Gasket 3100A Item 9 Loose Pipe Flange 3100A Item 11 Field supplied ASME B16 9 Stub End 4 in 102 mm Accessory supplied Compressor Flange Gasket 3100A Item 9 Loose Pipe Flange 3100A Item 11 Field supplied ASME B16 5 Class 600 Flange 4 in 102 mm Accessory supplied Compressor Flange Gasket 3100 Item 10 Field s...

Page 14: ...NE ECONOMIZER TO COOLER COOLER ECONOMIZER NOTE All shaded piping is field supplied and installed Fig 7 Line Piping and Connections 1 Circuit Shown Fig 8 Double Suction Riser Construction Detail LEGEND RED TEE Reducing Tee STR ELLS Street Elbows a30 4519 a30 4507 LOOSE PIPE FLANGE ACCESSORY SUPPLIED O RING ACCESSORY SUPPLIED COOLER PIPE FLANGE ACCESSORY SUPPLIED a30 4520 Fig 9 Connect Copper Suctio...

Page 15: ...60 Circuit A and 30XA180 350 All Circuits Fig 12 Flange and Gasket Mounting Locations NOTES 1 Measurements are shown in inches millimeters 2 Accessory supplied flanges and gaskets connecting to the flex connector extra hole has been factory drilled and tapped See Table 2 3000A Item 10 14 15 and 3100A Item 9 10 13 3 Field supplied flanges and gaskets connecting to the flex connec tor extra hole mus...

Page 16: ...right 2007 Carrier Corporation MAIN BASE BOARD EWT EWT LWT LWT EWT EWT LWT LWT JUNCTION BOX ACCESSORY SUPPLIED 5 WIRE CABLE ACCESSORY SUPPLIED CONDUIT FIELD SUPPLIED STRAIN RELIEF FIELD SUPPLIED EWT LWT Fig 13 Thermistor Connections Fig 14 Typical Junction Box Connections EWT and LWT Thermistors Shown LEGEND DPT Discharge Pressure Transducer LWT Leaving Water Temperature OAT Outdoor Air Temperatur...

Reviews: