Remote Cooler and Economizers Installa-
tion — 

Install the cooler and economizers in a remote

location by following this procedure:
NOTE: Throughout the Remote Cooler and Economizers

Installation steps, the two accessory package part no.

(00EFN900003000A, 00EFN900003100A) have been short-

ened to 3000A and 3100A. When a specific part is referred to

in each accessory’s package, the package no. is mentioned fol-

lowed by the item no. For item no. identification and accessory

package contents, refer to Table 2.

1. After removing the cooler from the base unit, strip back

the insulation on the cooler tube sheets (if required) and

use the two large holes in the top corners for lifting.

2. Transport the cooler and economizer assemblies to the

new location and secure them into position. Keep the

economizer assemblies as close to the cooler as possible.

Also, ensure there is sufficient room to install and remove

cooler tubes from either end of the cooler. See Fig. 4A-

4D for tube removal clearances.

NOTE: The 30XA080 units do not utilize an economizer. In

this case, keep the EXV as close to the cooler as possible.

3. Install the accessory-supplied economizer shutoff valves

(3000A or 3100A: Item 1) and liquid line shutoff valves

(3000A or 3100A: Item 2) on the two economizer lines

and liquid lines at circuits A and B on the 30XA base

unit. See Fig. 7.

4. At the new cooler location, connect the field-supplied

cooler liquid line piping between the factory-installed

manual shutoff valve at the two economizer assemblies

and at the cooler. See Fig. 7.

5. Following good piping practices, install additional field-

supplied liquid and economizer line piping in the required

length to reconnect the two economizer assemblies to the

30XA base unit. See Fig. 8 for double suction riser con-

struction detail.

6. For 30XA080-120: all circuits and 30XA140-160: circuit

B, cut the suction pipe (copper) at the 30XA base unit and

discard (see Fig. 6, cut 4, circuit B). Following good

piping practices, install field-supplied copper suction line

piping from the 30XA base unit to the cooler. Use the

accessory-supplied cooler pipe flange (3000A: Item 8),

cooler flange O-ring (3000A: Item 12), and loose pipe

flange (3000A: Item 11) to connect the field-supplied

copper suction line piping at the cooler. See Fig. 9.

NOTE: The original flanges on the cooler and cut from the

30XA base unit may still be usable. However, Carrier recom-

mends and has provided in the accessory kit, parts necessary to

replace both the cooler pipe flange and the suction flange.

When the extended piping is installed, these flanges should be

replaced.

7. For 30XA140-160: circuit A and 30XA180-350: all

circuits, unbolt (DO NOT CUT) the portion of the steel

suction pipes that connected the flex connector flanges to

the cooler at the 30XA base unit and discard. See Fig. 10.

Refer to Table 6 for parts required (field-supplied or

accessory-supplied) to make new connections at the

cooler and the 30XA base unit with the field-supplied

steel suction line. See Fig 11. Follow good piping

practices to install field-supplied steel suction line piping

between the cooler and the flex connector at the 30XA

base unit.
When field-supplied flanges and gaskets are used, an

extra M16 mounting hole must be drilled and tapped to

connect a mounting bracket at the 30XA base unit. See

Fig. 10 and 11 for mounting bracket placement. See

Fig. 12 for mounting hole locations.
If additional gaskets are needed for installation, they must

be 

1

/

16

 in. non-asbestos fiber with synthetic rubber binder

compressed gasket sheet. An extra mounting hole also

needs to be field modified for any additional gaskets. See

Fig. 12 for mounting hole locations. Field-supplied

mounting nuts and bolts are also needed for field-

supplied gaskets.

8. All of the piping connections are now complete. Leak test

the unit and then pull a deep dehydration vacuum. Con-

nect the vacuum pump to the high-flow access fitting at

the bottom of the cooler, the liquid line service valves,

and the economizer line service valves. For best results, it

is recommended that a vacuum of at least 500 microns

(0.5 mm Hg) be obtained. To perform a standing vacuum

rise test, observe the rate-of-rise of the vacuum in the

system. If the vacuum rises by more than 50 microns in a

30-minute time period, then continue the dehydration

process until the standing vacuum requirement is met.

This will ensure a dry system.
By following this dehydration procedure, the amount of

moisture present in the system will be minimized, and the

factory-supplied filter driers will provide adequate

moisture protection. It is highly recommended that the

filter drier cores be replaced after 24 hours of operation.

This is to ensure that any foreign debris that is captured

during start-up is removed from the system. Additional

moisture removal capacity is also provided.

9. After setup is leak tested and deep dehydration vacuum is

completed, install field-supplied suction and economizer

line insulation between the economizer and the unit. If

necessary, reinstall the insulation on the cooler head.

10. To reconnect the EXV cables, use the accessory-supplied

cable assemblies (3000A or 3100A: Item 4). Two cables

are needed for the 30XA080 unit, and four cables are

needed for 30XA090-350 units. Take one cable assembly,

and label both ends with “EXV-A” for the circuit A main

EXV. Then label another three cable assemblies the same

way with “EXV-B”, “ECEXV-A”, “ECEXV-B” for the

circuit B main EXV, circuit A economizer EXV, and

circuit B economizer EXV, respectively (economizer

EXV does not apply to 30XA080 units).
Plug one side of the electrical connectors of the EXV

labeled cables into their corresponding EXV plugs. Run

the cables to the 30XA base unit, and plug the other side

of the cable connectors into their corresponding EXV

leads. Coil excess cables and wire tie in a convenient

location.

11. To reconnect the flow switch cable, use the accessory-

supplied cable assembly (3000A or 3100A: Item 4). Take

one cable assembly and label both ends with “CWFS.”

Plug one side of the electrical connector of the labeled

cable into the flow switch plug. Run the cable to the base

unit, and plug the other side of the cable connector into

the flow switch lead. Coil excess cables and wire tie in a

convenient location.

Do NOT close both manual shutoff valves in one liquid

line. Pressure can build up in the trapped area. To avoid the

possibility of personal injury or property damage, the new

liquid lines between the manual shutoff valves must each

have field-supplied and installed pressure relief valves.

Summary of Contents for 00EFN900003000A

Page 1: ...owing constraints Operating chilled water temperature is between 40 and 55 F 4 4 and 12 8 C When the remote cooler is applied the cooler heaters will not function so it is critical to maintain the water temperature above the freezing point at all times If the water temperature falls below the freezing point the cooler does not have protection to keep the water from freezing The interior space temp...

Page 2: ... from dropping below the minimum level in the oil separator Add 1 gallon of oil to each circuit Refer to Controls Start up Operation Service and Troubleshooting Guide for recommended oil type Table 3A Refrigeration Piping and Connections Material English Table 3B Refrigeration Piping and Connections Material SI ACCESSORY PACKAGE PART NO ITEM NO DESCRIPTION PART NO QTY 00EFN900003000A 1 Economizer ...

Page 3: ...NDOOR LOCATION 15 FT MAX Fig 1 30XA Unit and Cooler Level Piping Parallel Single Circuit Shown Fig 2 30XA Unit and Cooler Level Piping Elevated Single Circuit Shown Fig 3 30XA Unit with Cooler Located Below Unit Single Circuit Shown a30 4509 a30 4510 a30 4511 LEGEND Liquid Line Economizer Line Suction Line LEGEND Liquid Line Economizer Line Suction Line LEGEND Liquid Line Economizer Line Suction L...

Page 4: ...g 6 NOTE The 30XA080 units do not utilize an economizer In this case only the EXVs are present 7 Unbolt the cooler suction flanges from the cooler Tempo rary supports may be needed to support the suction pipes See Fig 6 8 At each circuit s economizer cut the liquid lines going to the economizer assembly before the manual shutoff valve see Fig 6 cut 1 circuits A and B Cut the cooler liquid lines be...

Page 5: ...3 15 8 15 8 15 8 15 8 11 8 11 8 30XA UNIT SIZE SUCTION LINE DOUBLE SUCTION RISERS COOLER LIQUID LINE CONDENSER LIQUID LINE ECONOMIZER LINE Circuit A Circuit B Circuit A mm Circuit B mm Riser A mm Riser B mm Riser A mm Riser B mm Circuit A mm Circuit B mm Circuit A mm Circuit B mm Circuit A mm Circuit B mm 080 79 79 41 67 41 67 29 29 29 29 090 79 79 41 67 41 67 29 29 29 29 22 22 100 79 79 41 67 41 ...

Page 6: ...ecommended service clearance around the cooler is 36 in 914 mm 3 Recommended cooler tube removal area either end is 109 in 2769 mm NOTES 1 Measurements are shown in inches millimeters 2 Recommended service clearance around the cooler is 36 in 914 mm 3 Recommended cooler tube removal area either end is 109 in 2769 mm 1 2 13 13 16 20 8 9 32 210 117 3 4 2991 52 1 4 1327 21 1 32 534 52 1 4 1327 SIDE V...

Page 7: ...C 30XA180 240 Cooler Dimensions Fig 4D 30XA260 350 Cooler Dimensions NOTES 1 Measurements are shown in inches millimeters 2 Recommended service clearance around the cooler is 36 in 914 mm 3 Recommended cooler tube removal area either end for 30XA180 200 is 1093 8 in 2779 mm 4 Recommended cooler tube removal area either end for 30XA220 240 is 1085 8 in 2758 mm NOTES 1 Measurements are shown in inch...

Page 8: ...3 8 746 8 3 4 222 5 8 17 7 16 12 2 1 4 56 SIDE VIEW END VIEW TOP VIEW Fig 5A 30XA090 160 Economizer Dimensions Fig 5B 30XA180 350 Economizer Dimensions NOTES 1 Measurements are shown in inches millimeters 2 Recommended service clearance around the economizer is 36 in 914 mm NOTES 1 Measurements are shown in inches millimeters 2 Recommended service clearance around the economizer is 36 in 914 mm a3...

Page 9: ...HIDDEN SUCTION PRESSURE TRANSDUCER HIDDEN CUT 2 COOLER LIQUID LINE CUT 1 LIQUID LINE CUT 3 ECONOMIZER LINE CUT 3 ECONOMIZER LINE CUT 1 LIQUID LINE MANUAL SHUTOFF VALVE CUT 2 COOLER LIQUID LINE CIRCUIT B COOLER SUCTION FLANGES CIRCUIT A CONT ENTERING CHILLED WATER LEAVING CHILLED WATER THERMISTORS CHILLED WATER FLOW SWITCH MANUAL SHUTOFF VALVE CIRCUIT A ELECTRONIC EXPANSION VALVES 2 ELECTRONIC EXPA...

Page 10: ... and gaskets are used an extra M16 mounting hole must be drilled and tapped to connect a mounting bracket at the 30XA base unit See Fig 10 and 11 for mounting bracket placement See Fig 12 for mounting hole locations If additional gaskets are needed for installation they must be 1 16 in non asbestos fiber with synthetic rubber binder compressed gasket sheet An extra mounting hole also needs to be f...

Page 11: ...ed junction box 3000A or 3100A Item 5 19 Reinstall the thermistors in the correct cooler wells 20 To reconnect the suction pressure transducers SPT locate the SPT plugs for circuits A and B and cut the leads where they can be conveniently spliced in the installed junction box at the 30XA base unit Label the leads SPTA for the circuit A lead and SPTB for the circuit B lead 21 Take the two pieces of...

Page 12: ...ex Connector Flange O ring 3000A Item 13 Accessory supplied Flex Connector Flange 3000A Item 10 Flex Connector Flange O ring 3000A Item 13 220 Field supplied ASME B16 9 Stub End 4 in 102 mm Accessory supplied Compressor Flange Gasket 3100A Item 9 Loose Pipe Flange 3100A Item 11 Field supplied ASME B16 9 Stub End 4 in 102 mm Accessory supplied Compressor Flange Gasket 3100A Item 9 Loose Pipe Flange...

Page 13: ...em 8 325 Field supplied ASME B16 9 Stub End 4 in 102 mm Accessory supplied Compressor Flange Gasket 3100A Item 9 Loose Pipe Flange 3100A Item 11 Field supplied ASME B16 9 Stub End 4 in 102 mm Accessory supplied Compressor Flange Gasket 3100A Item 9 Loose Pipe Flange 3100A Item 11 Field supplied ASME B16 5 Class 600 Flange 4 in 102 mm Accessory supplied Compressor Flange Gasket 3100 Item 10 Field s...

Page 14: ...NE ECONOMIZER TO COOLER COOLER ECONOMIZER NOTE All shaded piping is field supplied and installed Fig 7 Line Piping and Connections 1 Circuit Shown Fig 8 Double Suction Riser Construction Detail LEGEND RED TEE Reducing Tee STR ELLS Street Elbows a30 4519 a30 4507 LOOSE PIPE FLANGE ACCESSORY SUPPLIED O RING ACCESSORY SUPPLIED COOLER PIPE FLANGE ACCESSORY SUPPLIED a30 4520 Fig 9 Connect Copper Suctio...

Page 15: ...60 Circuit A and 30XA180 350 All Circuits Fig 12 Flange and Gasket Mounting Locations NOTES 1 Measurements are shown in inches millimeters 2 Accessory supplied flanges and gaskets connecting to the flex connector extra hole has been factory drilled and tapped See Table 2 3000A Item 10 14 15 and 3100A Item 9 10 13 3 Field supplied flanges and gaskets connecting to the flex connec tor extra hole mus...

Page 16: ...right 2007 Carrier Corporation MAIN BASE BOARD EWT EWT LWT LWT EWT EWT LWT LWT JUNCTION BOX ACCESSORY SUPPLIED 5 WIRE CABLE ACCESSORY SUPPLIED CONDUIT FIELD SUPPLIED STRAIN RELIEF FIELD SUPPLIED EWT LWT Fig 13 Thermistor Connections Fig 14 Typical Junction Box Connections EWT and LWT Thermistors Shown LEGEND DPT Discharge Pressure Transducer LWT Leaving Water Temperature OAT Outdoor Air Temperatur...

Reviews: