PLUMBERS INSTALLATION INSTRUCTIONS - CONTROL BOX
IS1812(2)(02/19)
Sheet 2 of 2
To
Sensor
Cable
To tap outlet
From water supply
Control Box Components
Fig. 5
ELECTRONIC WALL MOUNTED OUTLET(REMOTE)
8 0
86
Fixing Holes
Control box
isolation valve
Step 2: Mounting Holes
Control
Module
Fig. 4
Inlet
Outlet
Step 1: Remove Cover
& Install Solenoid
Cover
retaining
screw
Fig. 3
Control Box Mounting Instructions:
1)
2)
Remove control box cover: Using a phillips head screwdriver, remove
cover retaining screw. Apply a light force to the small button underneath
and gently lift off cover (Fig.3). With the cover removed you can see a
hexagonal brass nut. Remove this nut and replace it with enclosed solenoid.
Determine location & fasten control box to wall: Control box should be
located within 300mm from the wall outlet. Attach control box to wall using
4 supplied wall plugs & screws (Fig.4).
3)
Connect cables to controller: Remove split strain relief from box &
connect Power Supply cable to Control Module as shown in Fig. 2.
Then connect Control Module to Tap Sensor Cable and Tap Sensor
Cable to Solenoid.
Open the relief and pass Power Supply cable and Tap Sensor Cable
through. Wind up any excess Power Supply cable and store inside
the control box.
Re-insert the strain relief and ensure that power, sensor, solenoid and
module cables are connected and secured (Fig.2).
4)
Connect power supply to a 240VAC, 10A GPO.
Ensure that supply of power has been isolated.
The power outlet should be located no more than 300mm from
the control box when using the standard cable.
If a longer seperation is required, please use optional extension cable
(98454) to extend the distance up to a maximum of 2.2 meters.
Commissioning Procedure:
a) Turn on mains water supply & check for leaks
at both ends of the mains supply hose.
b) Open the control box isolation valve and
check for leaks at the remaining connections.
c) Re-attach cover and fasten with retaining screw.
d) Power on the device at the GPO and allow the unit to
complete the calibration sequence as follows:
1) The indicator LED starts blinking.
2) The indicator LED will turn off for 2 to 3 seconds performing
calibration then a small amount of water will discharge.
3) The unit is now ready to operate.
e) Test operation by placing hands under the sensor (within 100mm from
outlet of spout). Water should flow within 0.5 seconds.
Remove hand and the water supply should stop within 2 seconds.
IMPORTANT: Please refer to AWARE Operation Manual (IS 1683) to configure
wireless communication and change the device default settings.
6)
Flush the inlet and outlet lines before connecting to the Control Box.
Then connect inlet and outlet lines.
5)
Fig. 2
To Power Supply
To Sensor Cable
Solenoid (Red + Black)
To Solenoid (Green + Yellow)
To Module (Brown + White)
To Tap Sensor Cable
Split strain relief
Power Supply
WATER EFFICIENT - CONNECTED TAPWARE ENABLED BY AWARE
TM
Refer to side 1 of this instruction for wall outlet installation.
Static Inlet pressure range : 150 - 700 kPa.
New Regulation : 500 kPa maximum static pressure at
any outlet within a building. (Ref. AS/NZS 3500.1)
IMPORTANT