background image

Humidifiers | Unit Availability

Humidifiers

G-14

 

www.carnes.com

MODELS AVAILABLE AND ELECTRICAL DATA - 

Table 8

Model

Max 

Lb/Hr

Voltage

Phase

kW

Line 

Amp

Disc. 

Size

Optional 

Cir. 

Breaker*

Steam 

Cylinder

Cyl Wire 

Current

HBAH 
HCAH
HSAH
HTAH

H_AHAU

5

120

1

1.725

14.4

25

1-20 Amp

AX220

14.4

H_AHBU

5

208

1

1.725

8.3

15

1-15 Amp

AX380

8.3

H_AHDU

5

230

1

1.725

7.5

15

1-20 Amp

AX380

7.5

H_AHFU

5

277

1

1.725

6.2

15

1-15 Amp

AX380

6.2

H_AHLU

5

380

1

1.725

4.5

15

1-15 Amp

AX600

4.5

H_AHQU

5

415

1

1.725

4.2

15

1-15 Amp

AX600

4.2

H_AHMU

5

460

1

1.725

3.7

15

1-15 Amp

AX700

3.7

H_AHNU

5

575

1

1.725

3.0

15

1-15 Amp

AX700

3

H_AHAU

10

120

1

3.45

28.7

45

1-40 Amp

AX220

28.7

H_AHBU

10

208

1

3.45

16.6

25

1-25 Amp

AX380

16.6

H_AHDU

10

230

1

3.45

15.0

25

1-25 Amp

AX380

15

H_AHFU

10

277

1

3.45

12.4

20

1-20 Amp

AX380

12.4

H_AHLU

10

380

1

3.45

9.1

15

1-15 Amp

AX600

9.1

H_AHQU

10

415

1

3.45

8.3

15

1-15 Amp

AX600

8.3

H_AHMU

10

460

1

3.45

7.5

15

1-15 Amp

AX700

7.5

H_AHNU

10

575

1

3.45

6.0

15

1-15 Amp

AX700

6

HBDH 
HCDH
HSDH
HTDH

H_DHBU

20

208

1

6.9

33.1

50

1-45 Amp

B380

33.1

H_DHDU

20

230

1

6.9

29.9

45

1-40 Amp

B380

30

H_DHFU

20

277

1

6.9

24.9

40

1-35 Amp

B380

24.9

H_DHLU

20

380

1

6.9

18.1

30

1-30 Amp

B600

18.1

H_DHQU

20

415

1

6.9

16.6

25

1-25 Amp

B600

16.6

H_DHMU

20

460

1

6.9

15.0

25

1-25 Amp

B700

15

H_DHNU

20

575

1

6.9

12.0

20

1-15 Amp

B700

12

H_DHCU

20

208

3

6.9

19.1

30

1-25 Amp

B500

19.1

H_DHEU

20

230

3

6.9

17.3

30

1-25 Amp

B500

17.3

H_DHTU

20

380

3

6.9

10.4

20

1-20 Amp

B600

10.4

H_DHWU

20

415

3

6.9

9.6

20

1-20 Amp

B600

9.6

H_DHGU

20

460

3

6.9

8.6

15

1-15 Amp

B700

8.6

H_DHHU

20

575

3

6.9

6.9

15

1-15 Amp

B700

6.9

H_DHCU

30

208

3

10.3

28.7

45

1-40 Amp

B500

28.7

H_DHEU

30

230

3

10.3

25.9

40

1-35 Amp

B500

25.9

H_DHTU

30

380

3

10.3

15.6

25

1-25 Amp

B600

15.6

H_DHWU

30

415

3

10.3

14.4

25

1-25 Amp

B600

14.4

H_DHGU

30

460

3

10.3

13.0

20

1-20 Amp

B700

13

H_DHHU

30

575

3

10.3

10.4

20

1-15 Amp

B700

10.4

HBGH 
HCGH
HSGH
HTGH

 H_GHBU

*

30

208

1

10.3

49.7

*

80

2-35 Amp

*

C62

24.8

H_GHDU

30

230

1

10.3

44.9

70

1-60 Amp

C62

22.4

H_GHFU

30

277

1

10.3

37.3

60

1-50 Amp

C62

18.6

H_GHLU

30

380

1

10.3

27.2

45

1-40 Amp

C62

13.6

H_GHQU

30

415

1

10.3

24.9

40

1-40 Amp

C62

12.5

H_GHMU

30

460

1

10.3

22.5

35

1-30 Amp

C62

11.3

H_GHNU

30

575

1

10.3

17.9

30

1-25 Amp

C62

9.0

H_GHCU

40

208

3

13.8

38.3

60

1-60 Amp

C62

19.1

H_GHEU

40

230

3

13.8

34.6

60

1-50 Amp

C62

17.2

H_GHTU

40

380

3

13.8

20.9

35

1-35 Amp

C65

20.9

H_GHWU

40

415

3

13.8

19.2

30

1-30 Amp

C65

19.2

H_GHGU

40

460

3

13.8

17.3

30

1-25 Amp

C65

17.3

H_GHHU

40

575

3

13.8

13.8

25

1-20 Amp

C65

13.8

* = Circuit Breaker is REQUIRED per NEC 48 amp guidelines.

Summary of Contents for HBAH

Page 1: ...Humidifiers www carnes com G 1 Humidifiers Steam Humidifiers COMMERCIAL INDUSTRIAL AND INSTITUTIONAL STEAM HUMIDIFIERS HCHH Shown...

Page 2: ...oportional Humidistat or External Signal from DDC Controls Optional internal circuit breaker available Please note certain units require circuit breakers per NEC 48 amp guidelines True Touchscreen con...

Page 3: ...omponent Activity menu HIGH WATER LED The HIGH WATER LED is an orange light illuminated when the High Water Sensor is activated An activated High Water Sensor indicates that the water has risen to the...

Page 4: ...midifier if any Indicator light to the left of the button turns red when service is needed and will otherwise remain green Refer to the separate Service 5 Maize Help buttons are used exclusively in th...

Page 5: ...her filling or draining the cylinder The Drain Valve is on when the humidifier is draining the cylinder The Contactor is on when the humidifier is producing steam The High Water Sensor is on when the...

Page 6: ...user can monitor the life in hours of the cylinder When changing a cylinder press the Reset button on this page to reset the timer The Cylinder Life Counter only counts the amount of actual runtime of...

Page 7: ...ater situa tion the humidifier will continue to run If the humidifier cannot work it s way back up the normal max controlled setpoint the humidifier will shut down after the High Water Timeout value e...

Page 8: ...humidifier is programmed into the unit This page is password protected and number should not be modified by the end user Contact the factory if further information is needed Corrective Drain Length Th...

Page 9: ...cted to the steam distributor pipe The circuit board reacts to current flow between the electrodes and automatically opens the fill solenoid valve when more water is required to maintain the desired o...

Page 10: ...n in Figure B The distance between the humidifier cabinet and the steam distributor should be the minimum distance possible Refer to Table 5 for maximum length that may be installed based on static pr...

Page 11: ...tube is used a minimum of one inch of insulation must be applied to prevent excessive condensation A short length of steam hose must be used to connect the cylinder in the humidifier to the copper tu...

Page 12: ...If the steam distributor pipe is located in a duct where there is no air flow and the control humidistat is calling for humidity steam would be discharged into the duct where it would immediately cond...

Page 13: ...ing recommended No 20 AWG wire Avoid running control wiring near high voltage primary wires Connections shown in Figure H are for typical on off controls For Carnes proportional controls see Figure J...

Page 14: ...18 1 H_DHQU 20 415 1 6 9 16 6 25 1 25 Amp B600 16 6 H_DHMU 20 460 1 6 9 15 0 25 1 25 Amp B700 15 H_DHNU 20 575 1 6 9 12 0 20 1 15 Amp B700 12 H_DHCU 20 208 3 6 9 19 1 30 1 25 Amp B500 19 1 H_DHEU 20...

Page 15: ..._GHWU 100 415 3 34 4 47 9 80 2 40 Amp C12 24 H_GHGU 100 460 3 34 4 43 3 70 1 60 Amp C12 21 7 H_GHHU 100 575 3 34 4 34 6 60 1 50 Amp C12 17 3 HBHH HCHH HSHH HTHH H_HHCU 125 208 3 43 119 5 200 4 40 Amp...

Page 16: ...stallation anywhere between 100 and 25 of maximum capacity Voltage and Phase designate available phase and nominal voltages Single phase units may be operated from two legs of a three phase supply but...

Page 17: ...ble in the unit to reduce the risk of costly damage in the event of internal failure It is not meant to be the primary protection as may be required by local and national electrical codes All units in...

Page 18: ...HXPBB024S 23 13 16 605mm 7 8 HXPBB030S 29 13 16 757mm 7 8 HXPBB036S 35 13 16 910mm 7 8 Minimum Maximum PIPE N N T HXPBB040S 35 889mm 38 965mm 7 8 HXPBB044S 39 991mm 42 1067mm 7 8 HXPBB048S 43 1092mm 4...

Page 19: ...above any items that would be damaged if a water leak were to develop STANDARD MOUNTING Factory attached to humidifier OPTION Mounted remote from humidifier FAN VOLTAGE 3 fans attached 12 volt from hu...

Page 20: ...trol takes the temperature into consideration when calculating the humidity to provide an extra degree of precision 0 to 100 set point range WALL HUMIDISTAT ON OFF CONTROL WALL HUMIDISTAT PROPORTIONAL...

Page 21: ...ge is from 0 to 100 R H Ambient operating conditions are from 0 to 85 C The humidistat may be mounted in a return duct to provide a mean of sensing and controlling relative humidity The humidistat may...

Page 22: ...low 10 there is no adjustment AIR FLOW SWITCH VELOCITY TYPE AIR FLOW SWITCH PRESSURE DIFFERENTIAL TYPE Model HXAAE Air flow in the duct may be sensed by using this differen tial pressure switch The di...

Page 23: ...cations it may be desirable to have the steam generator cylinder feed two steam distributor pipes T fittings can be installed in the steam hose and condensate return line Two models of condensate retu...

Page 24: ...ter The pump is capable of operation with a vertical lift up to 12 feet or horizontal run of 40 feet The complete package includes drain pump with six feet of cord and plug for 115 volt operation 3 Pr...

Page 25: ...t Steam Output Mounting Flange Drain Pipe 3 8 FPT Water Inlet 1 1 2 PVC Air Gap Connection 7 8 Dia Hole For Control Wiring 1 3 8 Dia Hole For Power Wiring 9 000 229 1 500 38 24 947 634 19 813 503 19 9...

Page 26: ...set up non Carnes installation See picture 31 3 4 806 19 5 8 498 6 152 38 965 26 660 14 3 4 375 25 3 4 654 Drain Pipe Condensate Return Inlet Condensate Return Inlet Steam Outlets TOP 9 1 2 241 2 1 4...

Page 27: ...ap on the fill water line to prevent backflow It is recommended that a drain air gap fitting be installed by a non Carnes contractor to prevent backflow of water Carnes offers an air gap fitting as a...