Humidifiers | Humidifier Specifications

1.

  Provide self-contained microprocessor controlled steam generat-

ing humidifiers of the size(s) shown on plans as manufactured by 

Carnes Company, Verona, WI.

2.

  Carnes Humidifiers shall have the capacity to operate at 

115, 208, 230, 277, 380, 415, 460 and 575 volt (or nominal value), 

60 or 50 hz (cycle), single or 3 phase power. Specific combina-

tion of maximum output, voltage and phase for order application 

determined by electrical data chart.

3.

  The humidifier(s) shall be UL and cUL listed.

4.

  The humidifier(s) shall have a total Color “True Touchscreen” 

user interface. Features:

 

a.  True Touchscreen navigation for all aspects of operation and 

  

information  access.

 

b.  Cylinder life-counter (hours of operation. Found by accessing 

  

Settings  button.

 

c.  With Fan Distribution Unit, there is a fan speed Slide Bar 

   control with CFM indication. Found by accessing Settings 

  

button.

 

d.  “Help” screen button.

 

e. “Service Required” button and indicator and corresponding 

   screen explaining service issues and possible troubleshooting 

  

tips.

 

f.  “Dim LCD” feature button.

 

g. “Humidistat Demand” indication button. Shows control 

   humidistat and high-limit humidistat.

 

h.  “Settings button - where all operational values can be set.

 

i.  “Setpoints” button - target steam output of the humidifier.

5.

  Steam shall be generated from tap water or softened water (see 

factory representative) in a factory sealed cylinder containing 

electrodes. Cylinders shall not require setting of electrode spac-

ing, cleaning or maintenance and shall be of the disposable type.

6.

  The humidifier(s) shall include an automatic drain cycle controlled 

electronically to maximize energy efficiency. Drain cycle shall 

adapt to variations in water conditions (high/low conductivity and 

high/low hardness) and not require manual setting. There is also 

a default setting for a pulsing drain action to assist in keeping 

drain lines open.

7.

  In the event of over-current, the humidifier shall signal that a 

fault condition exists by message on touchscreen. Over-current 

protection shall be resettable. Replacement type fuses are not 

acceptable.

 

Option:

  Humidifier(s) shall also include secondary magnetic 

overload switches (circuit breakers) that shall be manually 

resettable and shall be of the type that positively disconnects 

power to the steam cylinder.

8.

  Humidifier(s) shall include a door interlock safety switch to discon-

nect power to steam cylinder(s) when cabinet door is opened.

9.

  The system shall include one steam distributor pipe for each 

steam generating cylinder mounting in the duct as shown on the 

plans. Steam distributing pipe(s) shall be of corrosion resistant 

design (copper or stainless steel) and be designed to provide 

uniform distribution over the entire length of the pipe.

 

Option:

  Supply and install remote (or humidifier mounted) fan 

distribution units to discharge steam directly into the conditioned 

space. 

 

Provide the following components:

 

a.  Three 12VDC fans operated by circuit board.

 

b.  Integral steam manifold trap.

 

b.  Remote mounted on/off, proportional control humidistat.

 

Option:

 When plans call for a specific short absorption 

distance from dispersion system, a multi-tube Short Absorption 

Manifold is available sized specifically to duct dimensions, with 

horizontal stainless steel cross tubes and vertical headers.

10.

  The system shall include flexible hose to connect the steam 

cylinder(s) to the steam distributor pipe(s). A separate conden-

sate return line shall return condensate to the humidifier for 

reuse to minimize consumption. If due to specific routing issues 

or application of unit, condensate line can not run back to unit, 

the line can go directly to the common drain, and the addition of 

a “circle” or “U” trap will be required (see IOM). Long distances 

from unit to common drain can be accommodated with accessory 

option Water Pump (HXWA). Hard tubing can be used for Steam 

Hose and Condensate Return to prevent sags, restrictions or 

obstructions (see IOM), but it is recommended a minimum of 12 

inches of flexible hose be used from unit and before distributor 

pipe. We recommend a maximum distance of 30 feet from unit 

to distributor pipe(s) or short absorption manifold and proper 

routing and inclination of hoses and hard tubing be adhered to for 

proper, overall consistent and dependable operation.

11.

  The humidifier(s) shall incorporate a 1” air gap on the fill water line 

to prevent backflow. It is recommended that a drain air gap fitting 

be installed by a non-Carnes contractor to prevent backflow of 

water. Carnes offers an air gap fitting as a purchased option.

12.

 The humidifier cabinet(s) shall be constructed of 20 gauge 

steel with a stainless steel bottom pan, protected by a dipped 

electrostatic baked enamel undercoat with multi spec textured top 

coat with black accent architectural grade. The cabinet door shall 

be hinged and provided with a lock and key. The main door is 

also provided with a quick release pin for removal to provide easy 

access to internals. The True Touchscreen Home Page will show 

a digital LCD steam output meter calibrated in pounds of steam 

per hour (kg of steam per hour selection is included as a built in 

option), fill cycle, drain cycle and high water indicator lights will be 

visible with the cabinet door closed.

13.

 The humidifier(s) shall be controlled by a humidistat which 

operates through the solid-state circuit board. Humidifier(s) shall 

incorporate terminals for connection of humidistat, air flow switch 

and high limit control humidistat.

 

Option:

  Provide the following accessory controls:

 

a.  Wall mounted humidistat, on/off control.

 

b.  Wall mounted humidistat, w/ LCD combo (NEW).

 

c.  Duct mounted humidistat, on/off control.

 

d.  Duct mounted humidistat, proportional control.

 

 e.  Duct mounted humidistat w/digital humidity and temperature, 

  

combo  (NEW).

 

f.  High limit duct mounted humidistat, on/off control.

 

g.  High limit duct mounted humidistat, proportional control.

 

h.  Pressure differential type air flow switch.

 

i.  Paddle type air flow switch.

 

j.  Wall or duct mounted temperature compensated, on/off 

   or proportional control, digital display humidistat.

14.

  External Control Signals - All Carnes humidifiers will accept 

external DDC control signals of 0-10 volt DC. Signal to modulate 

the output of humidifier. Polarity must be observed and input 

impedance is 20K ohms. If 4-20 mA signal is provided a 470 ohm, 

1/4 watt resistor must be installed. Humidifiers will also accept 

internal (BMS) building management system or (BAS) building 

automation system signal.

15.

  The fill water line shall include a strainer to remove sediment 

from incoming water and a flow regulating control to automatically 

compensate for water pressures from 20-120 psi.

16.

 Humidifier(s) shall include a “Service Required” button with 

indication light on the total “True Touchscreen” home page which 

shall explain serivce issues and possible troubleshooting tips. The 

light shall be visible with the cabinet door closed and terminals 

shall be provided for remote signal. Terminals are also provided 

to indicate normal operation to a remote location.

17.

  Dedicated buttons with indicator lights on the home page of 

the total “True Touchscreen” shall indicate status of the control 

humidistat, high limit humidistat, air flow switch and door interlock 

switch. Operation of fill solenoid, drain solenoid, power contac-

tor and high water sensor shall be shown after accessing the 

“Component Activity” button on the home page of the total “True 

Touchscreen”.

18.

  The humidifier(s) electronic circuit board shall include automatic 

controls to compensate for varying water conditions without 

changing cylinders or electrode spacing. The control shall acti-

vate the fill and drain solenoid valves to automatically maximize 

efficiency. Unit will perform system self-correction procedures to 

assist in preventing unit shutdown due to any fault in operational 

sequence. A drain pulsing feature is included to assist in expelling 

any blockage that may occur during a self-correcting drain cycle. 

If self-correction procedures are unable to correct problems after 

specific cycles, unit will automatically shutdown.

19.

  The humidifier(s) shall include a non water contact capacitance 

proximity high water sensor to prevent overfilling and loss of 

water.

20.

  The fill solenoid valve shall open whenever the drain solenoid is 

activated, whether in automatic or manual operation, to prevent 

discharge of boiling water into drainage system. Drain light shall 

indicate the switch is in drain position.

21.

  Humidifiers, dependent upon capacity, will have one (1) or two (2) 

cylinders for operation. If a capacity is desired of 125, 150, 175 

or 200 lbs./hr., the units will be equipped with two (2) cylinders, 

each independently and separately controlled by their own control 

signal.

22.

  Automatic Drain of cylinder water will take place when there is a 

demand signal loss for 72 hours. Unit will remain in stand-by in 

the event that a quick start-up is required.

Summary of Contents for HBAH

Page 1: ...Humidifiers www carnes com G 1 Humidifiers Steam Humidifiers COMMERCIAL INDUSTRIAL AND INSTITUTIONAL STEAM HUMIDIFIERS HCHH Shown...

Page 2: ...oportional Humidistat or External Signal from DDC Controls Optional internal circuit breaker available Please note certain units require circuit breakers per NEC 48 amp guidelines True Touchscreen con...

Page 3: ...omponent Activity menu HIGH WATER LED The HIGH WATER LED is an orange light illuminated when the High Water Sensor is activated An activated High Water Sensor indicates that the water has risen to the...

Page 4: ...midifier if any Indicator light to the left of the button turns red when service is needed and will otherwise remain green Refer to the separate Service 5 Maize Help buttons are used exclusively in th...

Page 5: ...her filling or draining the cylinder The Drain Valve is on when the humidifier is draining the cylinder The Contactor is on when the humidifier is producing steam The High Water Sensor is on when the...

Page 6: ...user can monitor the life in hours of the cylinder When changing a cylinder press the Reset button on this page to reset the timer The Cylinder Life Counter only counts the amount of actual runtime of...

Page 7: ...ater situa tion the humidifier will continue to run If the humidifier cannot work it s way back up the normal max controlled setpoint the humidifier will shut down after the High Water Timeout value e...

Page 8: ...humidifier is programmed into the unit This page is password protected and number should not be modified by the end user Contact the factory if further information is needed Corrective Drain Length Th...

Page 9: ...cted to the steam distributor pipe The circuit board reacts to current flow between the electrodes and automatically opens the fill solenoid valve when more water is required to maintain the desired o...

Page 10: ...n in Figure B The distance between the humidifier cabinet and the steam distributor should be the minimum distance possible Refer to Table 5 for maximum length that may be installed based on static pr...

Page 11: ...tube is used a minimum of one inch of insulation must be applied to prevent excessive condensation A short length of steam hose must be used to connect the cylinder in the humidifier to the copper tu...

Page 12: ...If the steam distributor pipe is located in a duct where there is no air flow and the control humidistat is calling for humidity steam would be discharged into the duct where it would immediately cond...

Page 13: ...ing recommended No 20 AWG wire Avoid running control wiring near high voltage primary wires Connections shown in Figure H are for typical on off controls For Carnes proportional controls see Figure J...

Page 14: ...18 1 H_DHQU 20 415 1 6 9 16 6 25 1 25 Amp B600 16 6 H_DHMU 20 460 1 6 9 15 0 25 1 25 Amp B700 15 H_DHNU 20 575 1 6 9 12 0 20 1 15 Amp B700 12 H_DHCU 20 208 3 6 9 19 1 30 1 25 Amp B500 19 1 H_DHEU 20...

Page 15: ..._GHWU 100 415 3 34 4 47 9 80 2 40 Amp C12 24 H_GHGU 100 460 3 34 4 43 3 70 1 60 Amp C12 21 7 H_GHHU 100 575 3 34 4 34 6 60 1 50 Amp C12 17 3 HBHH HCHH HSHH HTHH H_HHCU 125 208 3 43 119 5 200 4 40 Amp...

Page 16: ...stallation anywhere between 100 and 25 of maximum capacity Voltage and Phase designate available phase and nominal voltages Single phase units may be operated from two legs of a three phase supply but...

Page 17: ...ble in the unit to reduce the risk of costly damage in the event of internal failure It is not meant to be the primary protection as may be required by local and national electrical codes All units in...

Page 18: ...HXPBB024S 23 13 16 605mm 7 8 HXPBB030S 29 13 16 757mm 7 8 HXPBB036S 35 13 16 910mm 7 8 Minimum Maximum PIPE N N T HXPBB040S 35 889mm 38 965mm 7 8 HXPBB044S 39 991mm 42 1067mm 7 8 HXPBB048S 43 1092mm 4...

Page 19: ...above any items that would be damaged if a water leak were to develop STANDARD MOUNTING Factory attached to humidifier OPTION Mounted remote from humidifier FAN VOLTAGE 3 fans attached 12 volt from hu...

Page 20: ...trol takes the temperature into consideration when calculating the humidity to provide an extra degree of precision 0 to 100 set point range WALL HUMIDISTAT ON OFF CONTROL WALL HUMIDISTAT PROPORTIONAL...

Page 21: ...ge is from 0 to 100 R H Ambient operating conditions are from 0 to 85 C The humidistat may be mounted in a return duct to provide a mean of sensing and controlling relative humidity The humidistat may...

Page 22: ...low 10 there is no adjustment AIR FLOW SWITCH VELOCITY TYPE AIR FLOW SWITCH PRESSURE DIFFERENTIAL TYPE Model HXAAE Air flow in the duct may be sensed by using this differen tial pressure switch The di...

Page 23: ...cations it may be desirable to have the steam generator cylinder feed two steam distributor pipes T fittings can be installed in the steam hose and condensate return line Two models of condensate retu...

Page 24: ...ter The pump is capable of operation with a vertical lift up to 12 feet or horizontal run of 40 feet The complete package includes drain pump with six feet of cord and plug for 115 volt operation 3 Pr...

Page 25: ...t Steam Output Mounting Flange Drain Pipe 3 8 FPT Water Inlet 1 1 2 PVC Air Gap Connection 7 8 Dia Hole For Control Wiring 1 3 8 Dia Hole For Power Wiring 9 000 229 1 500 38 24 947 634 19 813 503 19 9...

Page 26: ...set up non Carnes installation See picture 31 3 4 806 19 5 8 498 6 152 38 965 26 660 14 3 4 375 25 3 4 654 Drain Pipe Condensate Return Inlet Condensate Return Inlet Steam Outlets TOP 9 1 2 241 2 1 4...

Page 27: ...ap on the fill water line to prevent backflow It is recommended that a drain air gap fitting be installed by a non Carnes contractor to prevent backflow of water Carnes offers an air gap fitting as a...

Reviews: