CARNES Comfort Control User Manual Download Page 6

Option 1: Cleaning the Touch Screen

This option disables the touchscreen for 30 seconds to enable 
you to clean the touchscreen

Press and hold the MENU key to display 
Option 01. 

Option

Menu

Enter

Option

Menu

Enter

o

F

Option 3: Setting discharge air 
temperature for detecting heating call

Factory Default         95

Option 2: Changing the LCD Contrast

Press and hold the MENU key to display 
Option 02. 

Option

Menu

Enter

Factory Default        1

Option 1
Option 2
Option 3
Option 4
Option 5
Option 6
Option 7

Option 8

Cleaning the touch screen
Changing the LCD contrast
Setting discharge air temp to detect heating
Setting discharge air temp to detect cooling
Setting the night time or off airflow
Set the change in damper position per degree
Turning on temperature in the display in 
Remote Control Mode
Set the minimum airflow allowed

Options and Factory Defaults

Default = Off
Default = 10
Default = 95
Default = 65
Default = 50%
Default = 10%
Default = Off

Default = 0%

Options = Off or On
Options = 1 - 10
Options = 85  - 120
Options = 60  - 75
Options = 20% - 100%
Options = 5% - 25%
Options = Off or On

Options = 0% - 50%

Options are set using the Menu key. The MENU key is also used to set the schedule. 

Scroll through the options by pressing and holding the MENU. Schedule options are displayed first, then Options. Continue to 
press and hold until Option 01 is displayed. Continue to press and hold MENU to see all options. Press ENTER to return to 
normal operation.

The following options are available. Some options should be set by the installer and have been indicated as Installer.

Option

o

F

Option 4: Setting discharge air 
temperature for detecting cooling call

Factory Default          65

Menu

Enter

User
User
Installer
Installer
User
Installer
User

Installer

If the discharge air temperature is below the default of 95 degrees, a 
heating call will not be detected and the thermostat will not control 
airflow properly. Use this option to lower the temperature setting 
for discharge air so a heating call will be detected.

If the discharge air temperature is above the default of 65 degrees, a 
cooling call will not be detected and the thermostat will not control 
airflow properly. Use this option to raise the temperature setting for 
discharge air so a cooling call will be detected.

6

1.

During the 30 second countdown, use a 
damp, soft cloth to clean the touchscreen. 
After 30 seconds, the remote thermostat 
returns to normal operation.

2.

3.

Press the UP key to select On.

Press the ENTER key to start a 30 second 
count down.

1.

Or press and hold MENU to save the 
changes and display the next option. 

2.

3.

4.

Use the UP / DOWN keys to change the 
LCD contrast. 

Press ENTER to save the changes and 
return to normal operation.

Press and hold the MENU key to display 
Option 03. 

1.

Or press and hold MENU to save the 
changes and display the next option. 

2.

3.

4.

Use the UP / DOWN keys to change the 
heating detect setpoint temperature.

Press ENTER to save the changes and 
return to normal operation.

Press and hold the MENU key to display 
Option 04. 

1.

Or press and hold MENU to save the 
changes and display the next option. 

2.

3.

4.

Use the UP / DOWN keys to change the 
cooling detect setpoint temperature.

Press ENTER to save the changes and 
return to normal operation.

Summary of Contents for Comfort Control

Page 1: ...d room temperature and whether the system is in heating or cooling A schedulecanbeprogrammedintothethermostattocontrolairflowfordaytimeandnighttime orfordaysoff Thermostat Mode Indoors Thermostat oF S...

Page 2: ...shown in grey and displays airflow instead of temperature shown in grey Remote Remote Control Mode Remote Control Airflow Displayed Linked Remote AM Tu Menu Press the UP DOWN keys to change the damper...

Page 3: ...the airflow to reach the setpoint temperature Indoors Thermostat oF Set To Hold AM ed Link Tu Menu In the Night Mode the thermostat sets the damper to the Nighttime position set in Option 5 The factor...

Page 4: ...re displayed The Remote Thermostat is shown in Thermostat Mode Schedule 1 Press the NEXT key to display the Day and Night schedule for each day 2 Or press ENTER if you have no more changes 1 2 3 4 5 D...

Page 5: ...removing and installing the Remote Thermostat on the sub base Table Top and Wall Mounts Table Foot Or install the sub base on an interior wall about 5 feet above the floor and out of sunlight using tw...

Page 6: ...d have been indicated as Installer Option oF Option 4 Setting discharge air temperature for detecting cooling call Factory Default 65 Menu Enter User User Installer Installer User Installer User Insta...

Page 7: ...in remote control mode The UP DOWN keys are used to adjust airflow This option sets the minimum airflow allowed and can be used to minimize damper noise Press and hold the MENU key to display Option 0...

Page 8: ...ting or cooling Remote Thermostat Actuator Doesn t Seem To Be Responding Ensure the actuator has power You may be able to observe the LED light on the actuator through the diffuser The LED light will...