3
1.2 Other Required System Safeties
The new (or old)
module does not eliminate the need for the Low and/or High
Pressure safety switch(es)
. These functions are not included in the module.
A voltage sensing relay with normally open contacts should be wired to the load side of
the compressor circuit breaker, with the contacts in series with the mechanical safeties
as supplied to the Slimits input on the module. This is to deactivate the module (i.e. shut
off oil feed) in case of a breaker trip.
2.0 Bill of Materials
To simplify installation, all of the required parts are included in a single package.
Separate packages were developed for modules with and without the LonWorks
®
communication option. The following table lists all the components supplied in each
package.
Table 1. Bill of Materials
Item
0TA1063
Package
with
LonWorks
(Quantity)
0TA1064
Package
without
LonWorks
(Quantity)
Carlyle P/N
Description
1
1
3TA1061
LonCEM (
with LonWorks
Transciever)
1
1
3TA1062
LonCEM (
without LonWorks
Transciever)
2
1
1
HK05YZ003
Low Pressure Transducer (suction)
3
2
2
HK05YZ002
High Pressure Transducer (disch and oil)
4
3
3
06TA680007S**
Harness for Transducers (15 ft lead wire)
5
1
1
HH79NZ065
Discharge Temperature Thermistor
(5 Kohm)
6
1
1
DD08SA051
SAE Discharge Adapter Fitting
(1.3”L, 7/16”-20 SAE to ¼” NPT)
7
1
1
DD08SA052
SAE Suction Adapter Fitting
(3.7”L, 7/16”-20 SAE to ¼” NPT)
8
2
2
DD17GA051
∗
Cross Fitting (suction and discharge)
* Parker Part Number: AVC1-4
** Updated package includes shielded cable for the pressure transducer wiring harness, see
Appendix C for proper shielded cable grounding techniques.