52
Code
AC
AD
Format
LSB16
MSB16
Bits
240 241 242 243 244 245 246 247 248 249 250
251 252 253 254 255
Code
Variable
Conversion Statement
Comments
AC
Estimated
Motor
Temperature
- Convert LSB16 to decimal and store the
result in variable
𝑥
- Conversion result =
𝑥
Scaling Factor: -40
Code
Variable
Conversion Statement
Comments
AD
Soft starter
Status after
stopping
- Convert MSB16 to decimal and store
the result in variable
𝑥
- Conversion result =
𝑥
Value
State
0
Internal fault
1
Spare
2
Spare
3
Short circuit during idle
4
Short circuit during ramp
5
Spare
6
Negative phase sequence
7
Spare
8
Spare
9
Synchronisation loss
10
System voltage not detected
11
Line voltage out of range
12
Current unbalance
13
Spare
14
Spare
15
Locked rotor
16
Spare
17
Spare
18
Excess ramp-up time
19
Spare
20
Spare
21
Internal over temperature
22
Spare
23
Spare
24
Motor overload
25
Maximum current in bypass
Value
State
26
PTC alarm
27
Supply voltage unbalance
28
Spare
29
Spare
30
Low internal voltage
31
No reset
32
Idle
30
b
yt
es
31
b
yt
es
32
b
yt
es