7
ENGLISH
6
ENGLISH
PROTECTION DEGREE / WEIGHT
IP 65 (standard), 470 g. approximately (included analogue output and
packing)
AC
Input
RL1 Output
RL2 Output
Analogue
DC Power
Serial
Power Supply
Output
Supply
Output
AC Power
Supply
–––
4kV
4kV
4kV
4kV
–––
4kV
Input
4kV
–––
2kV
2kV
500V
2kV
500V
RL1 Output
4kV
2kV
–––
2kV
2kV
2kV
2kV
RL2 Output
4kV
2kV
2kV
–––
2kV
2kV
2kV
Anal. Output
4kV
500V
2kV
2kV
–––
2kV
500V
DC Power S.
–––
2kV
2kV
2kV
2kV
–––
2kV
Serial Output
4kV
500V
2kV
2kV
500V
2kV
–––
Tab.1: insulation table
INSTALLATION
Overall dimensions and panel cut-out
A
A
A
A
A
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
AAAAAAAA
92 mm
45 mm
124 mm
F
S
al1
al2
96 mm
48 mm
A
A
A
A
A
A
A
A
91 mm
112 mm
max. 10
mm
EXCITATION OUTPUT (ON REQUEST)
15VDC / 40mA (12VDC / 60mA) (non-stabilized)
POWER SUPPLY INPUT
230VAC -15% +10% 50/60Hz (standard) (200mAT protection fuse*);
115 VAC -15% +10% 50/60Hz (on request) (200mAT protection fuse*);
48 VAC -15% +10% 50/60 Hz (on request) (630mAT protection fuse*);
24 VAC -15% +10% 50/60 Hz (on request) (630mAT protection fuse*);
120VAC-15% +10% 50/60 Hz (on request) (200mAT protection fuse*);
240VAC-15% +10% 50/60 Hz (on request) (200mAT protection fuse*);
9 to 32VDC galvanic insulation (1AT protection fuse*);
40 to 155VDC galvanic insulation (315mAT protection fuse*).
*note: the mains has to be protected by means of a proper fuse type
SELF CONSUMPTION
8VA
OPERATING TEMPERATURE
From 0 to +50
°
C (R.H. <90% non-condensing).
STORAGE TEMPERATURE
From -10 to +60
°
C (R.H. <90% non-condensing).
INSULATION REFERENCE VOLTAGE
300VRMS
INSTALLATION CATEGORY CAT III - 300V (EN61010-1).
DIELECTRIC STRENGTH 4000 VRMS for 1 minute.
EMC IEC 801-2, IEC 801-3, IEC 801-4 (level 3).
SAFETY STANDARDS EN 61010-1, IEC 1010-1, VDE 0411.
CONNECTIONS screw-type, detachable.
HOUSING SIZE / DIMENSIONS / MATERIAL
1/8 DIN / 48 x 96 x 124 mm / ABS, self-extinguishing: UL 94 V-0.