33
Technical features
General features
31
Dual phase system
32
37
38
■
Maximum and minimum indication
Max. 19999999 (99999999); Min. 0.
■
Measurements
Power, energy, TRMS measurement of distorted waveforms.
Coupling:
direct.
■
Crest factor
Ib 5A:
≤
3 (15A peak max.).
Ib 20A:
≤
6 (127A peak max.).
■
Current overload
5(10) A, for 10ms:
300A max, at 50Hz.
5(10) A, for 500ms:
200A max, at 50Hz.
5(10) A, permanent:
10A, at 50Hz.
20(90) A, for 10ms:
2700A max, at 50Hz.
20(90) A, permanent:
90A, at 50Hz.
■
Voltage overload
Permanent:
1.2 Un;
For 1s:
2 Un.
■
Rated input voltages (Un)/range
AV0:
208VL-L/20(90)AAC, Un: -20+15%
AV1:
400VL-L/20(90)AAC, Un: -20+15%
AV3:
660VL-L/20(90)AAC, Un: -30+15%
AV4:
208VL-L/5(10)AAC, Un: -20+15%
AV5:
400VL-L/5(10)AAC, Un: -20+15%
AV6:
100VL-L/5(10)AAC, Un: -20+20%
AV7:
660VL-L/5(10)AAC, Un: -30+15%
AV8:
208VL-L/20(90)AAC Un: -20+15%
AV9:
400VL-L/20(90)AAC Un: -20+15%
■
Input impedance
AV1-AV5-AV9: 400V
L-L
> 720K
Ω
AV0-AV4-AV8: 208V
L-L
> 720K
Ω
AV3-AV7: 660V
L-L
> 1.97K
Ω
AV6: 100V
L-L
> 400K
Ω