13
Configure the system
EM24 IS - Instruction manual | CARLO GAVAZZI Controls SpA
EM24 IS - Instruction manual | CARLO GAVAZZI Controls SpA
diG out 2
diG out 2
Function
kWh pulse, kvarh pulse and alarm variables
kWh pulse
PULSE ou.2
Pulse weight
From 0.001 to 10.00
0.001
ton out.2
Pulse duration
30 ms or 100 ms
30 ms
test Pu.2
Pulse test activation
no/yes
no
P test 2
Simulated power for pulse test
From 0 to 9999
1000
on AL 2
activation set point
From 0 to 70 000 000
0
off AL 2
deactivation set point
From 0 to 70 000 000
0
t del 2
activation delay
From 0 to 255 s
0
out 2
normal status
nE (normally energized)
nd (normally denergized)
nd
Ene t.rES
Reset of all the total counters
YES/no
no
End
-
Exit and save
-
-
General settings - SFA models
The available settings depend on the model and application set.
Page title
Sub-menu Description
Values
Default value
Cng PASS
-
Change password
From 0 to 9999
0
FiLtEr.S
-
Interval of filter intervention with respect
to full scale (%)
From 0 to 100
2
FiLtEr.Co
-
Filter coefficient
From 1 to 32
2
AddrESS
AddrESS Serial address
From 1 to 247
1
bAudrAtE Baud rate
4.800 or 9.600
9600
diG out 1
diG out 1
Function
kWh pulse and alarm variables
kWh pulse
PULSE ou.1
Pulse weight
From 0.001 to 10.00
0.001
ton out.1
Pulse duration
30 ms or 100 ms
30 ms
test Pu.1
Pulse test activation
no/yes
no
P test 1
Simulated power for pulse test
From 0 to 9999
1000
on AL 1
activation set point
From 0 to 70 000 000
0
off AL 1
deactivation set point
From 0 to 70 000 000
0
t del 1
activation delay
From 0 to 255 s
0
out 1
normal status
nE (normally energized)
nd (normally denergized)
nd
diG out 2
diG out 2
Function
kWh pulse and alarm variables
kWh pulse
PULSE ou.2
Pulse weight
From 0.001 to 10.00
0.001
ton out.2
Pulse duration
30 ms or 100 ms
30 ms
test Pu.2
Pulse test activation
no/yes
no
P test 2
Simulated power for pulse test
From 0 to 9999
1000
on AL 2
activation set point
From 0 to 70 000 000
0
off AL 2
deactivation set point
From 0 to 70 000 000
0
t del 2
activation delay
From 0 to 255 s
0
out 2
normal status
nE (normally energized)
nd (normally denergized)
nd
End
-
Exit and save
-
-
Summary of Contents for EM24 IS-R2-O2 Series
Page 2: ...EM24 IS R2 O2 XX Three phase energy analyzer USER MANUAL...
Page 21: ...EM24 IS R2 O2 XX Analizzatore di energia per sistemi trifase MANUALE UTENTE...
Page 40: ...EM24 IS R2 O2 XX Dreiphasen Energieanalysator BETRIEBSANLEITUNG...
Page 59: ...EM24 IS R2 O2 XX Analyseur d nergie triphas MANUEL D EMPLOI...
Page 78: ...EM24 IS R2 O2 XX Analizador de energ a trif sico INSTRUCCIONES DE USO...
Page 97: ...EM24 IS R2 O2 XX Trefaset energianalyseapparat BRUGERMANUAL...