16
Essential information
EM24 IS - Instruction manual | CARLO GAVAZZI Controls SpA
EM24 IS - Instruction manual | CARLO GAVAZZI Controls SpA
Programming pages
The following table shows which programming pages are available for each application, according to the model.
Page
Application
A
B
C
D
E
F
G
H
Cng PASS
x
x
x
x
x
x
x
x
APPLiCAt
x
x
x
x
x
x
x
x
User
-
-
-
x
-
-
-
-
SELECtor
-
x
x
-
x
x
x
x
SYS
x
x
x
-
x
x
x
x
Ut rAtio
x
x
x
x
x
x
x
x
Ct rAtio
x
x
x
x
x
x
x
x
P int.ti
x
x
x
-
x
x
x
x
diG in
-
x
-
x
x
x
x
x
FiLtEr.S
-
-
-
-
-
x
x
x
FiLtEr.Co
-
-
-
-
-
x
x
x
AddrESS
x
x
x
x
x
x
x
x
Dig Out 1
x
x
x
-
x
x
x
x
Dig Out 2
x
x
x
-
x
x
x
x
Ene t.rES
x
x
x
x
x
x
x
x
End
x
x
x
x
x
x
x
x
Tariff management (IS model)
Managing tariffs via Modbus command
Change the tariff by entering the value corresponding to the current tariff according to the following table in the
1127h
registry
(04h or 06h
Modbus function):
Current
tariff
Register
value
T1
005Ah (90d)
T2
015Ah (346d)
T3
025Ah (602d)
T4
035Ah (858d)
Note:
Modbus tariffs management is disabled by writing 0 in register 1127h.
The tariff management is not available in SFA models
Managing tariffs via digital inputs
1.
Set
diG in 1
and
diG in 2
as “
tAr
”.
2.
Change tariff by changing input status according to the table below:
Current
tariff
input 1
input 2
T1
ON
ON
T2
OFF
ON
T3
ON
OFF
T4
OFF
OFF
Note:
the tariff management is not available in SFA models
Summary of Contents for EM24 IS-R2-O2 Series
Page 2: ...EM24 IS R2 O2 XX Three phase energy analyzer USER MANUAL...
Page 21: ...EM24 IS R2 O2 XX Analizzatore di energia per sistemi trifase MANUALE UTENTE...
Page 40: ...EM24 IS R2 O2 XX Dreiphasen Energieanalysator BETRIEBSANLEITUNG...
Page 59: ...EM24 IS R2 O2 XX Analyseur d nergie triphas MANUEL D EMPLOI...
Page 78: ...EM24 IS R2 O2 XX Analizador de energ a trif sico INSTRUCCIONES DE USO...
Page 97: ...EM24 IS R2 O2 XX Trefaset energianalyseapparat BRUGERMANUAL...