Energy management
EM24-DIN Communication Protocol
9
2.6
Carlo Gavazzi Controls identification code
MODBUS
: read only mode with functions code 03 and 04 limited to a word at a time
Table 2.6-1
Modicom
address
Physical
address
Length
(words)
VARIABLE
ENG. UNIT
Data
Format
Notes
3
00012
000Bh
1
Carlo Gavazzi Controls
identification code
UINT 16
Value=57: EM21 AV5 input model
Value=58: EM21 AV6 input model
.
2.7
Programming parameter tables
2.7.1
Password configuration menu
MODBUS
: read and write mode
Table 2.7-1
Modicom
address
Physical
address
Length
(words)
VARIABLE
ENG. UNIT
Data
Format
Notes
3
04097
1000h
1
PASSWORD
UINT 16
Minimum valid value: 0d
Maximum valid value: 999d
2.7.2
“Application” menu
MODBUS
: read and write mode
Table 2.7-2
Modicom
address
Physical
address
Length
(words)
VARIABLE
ENG. UNIT
Data
Format
Notes
3
04098
1001h
1
Type of application
UINT 16
Value=0: “A” application
Value=1: “B” application
Value=2: “C” application
2.7.3
System configuration menu
MODBUS
: read and write mode
Table 2.7-3
Modicom
address
Physical
address
Length
(words)
VARIABLE
ENG. UNIT
Data
Format
Notes
3
04099
1002h
1
Measuring system
UINT 16
Value=0: “3Pn”
Value=1: “3P1”
Value=2: “2P”
Value=3: “1P”
Value=4: “3P”
2.7.4
PT and CT configuration menu
MODBUS
: read and write mode
Table 2.7-4
Modicom
address
Physical
address
Length
(words)
VARIABLE
ENG. UNIT
Data
Format
Notes
3
04100
1003h
2
Current transformer ratio
UINT 32
Value min = 10 (CT=1,0)
Value max = 600000 (CT=60000.0)
3
04102
1005h
2
Voltage transformer ratio
UINT 32
Value min = 10 (VT=1,0)
Value max = 60000 (VT=6000.0)