background image

Energy management

 

           EM24-DIN Communication Protocol 

6

 

1.3 

 Application notes 

1.3.1 

RS485 general considerations  

 
1.  To avoid errors due to the signal reflections or line coupling, it is necessary to terminate the bus at 

the beginning and at the end (inserting a 120 ohm 1/2W 5% resistor between line B and A in the last 
instrument and in the Host interface).  

2.  The network termination is necessary even in case of point-to-point connection and/or of short 

distances. 

3.  For  connections longer than 1000m or if in the network there are more than 160 instruments (with 

1/5 unit load as used in EM21 interface), a signal repeater is necessary. 

4.  For bus connection it is suggested to use an AWG24 balanced pair cable and to add a third wire for 

GND connection. Connect GND to the shield if a shielded cable is used.  

5.  The GND is to be connected to ground only at the host side. 
6.  If an instrument does not answer within the “max answering time”, it is necessary to repeat the 

query. If the instrument does not answer after 2 or 3 consecutive queries, it is to be considered as 
not connected, faulty or reached with a wrong address. The same consideration is valid in case of 
CRC errors or incomplete response frames. 

 
 

1.3.2 

MODBUS timing 

 

 

 
Fig. 1 : 2-wire timing diagram 

 
 

Timing characteristics of reading function: 

msec 

T response: Max answering time 

500ms 

T response: Typical answering time 

40ms 

T delay: Minimum time before a new query 

3,5char 

T null: Max interruption time during the request frame 

2,5char 

 

Summary of Contents for EM 21

Page 1: ...EM21 COMMUNICATION PROTOCOL Version 1 Revision 0 April 7th 2008...

Page 2: ...tation In Carlo Gavazzi instruments 7 2 1 1 Geometric representation 7 2 2 Maximum and minimum electrical values in EM21 7 2 3 Instantaneous variables and meters 8 2 4 Firmware version and revision co...

Page 3: ...d in the communication frame 2 The functions 03h and 04h have exactly the same effect and can be used indifferently 3 The communication parameters are to be set according to the configuration of the i...

Page 4: ...1 to 11 Byte order MSB LSB CRC 2 bytes Response frame correct action Description Length Value Note Physical address 1 byte 1 to F7h 1 to 247 Function code 1 byte 04h Quantity of requested bytes 1 byt...

Page 5: ...sage should be identical to the request Request frame Description Length Value Note Physical address 1 byte 1 to F7h 1 to 247 Function code 1 byte 08h Sub function 2 bytes 0000h Data N word N 2 bytes...

Page 6: ...connection it is suggested to use an AWG24 balanced pair cable and to add a third wire for GND connection Connect GND to the shield if a shielded cable is used 5 The GND is to be connected to ground...

Page 7: ...rmats the word order is LSW MSW 2 1 1 Geometric representation According to the signs of the power factor the active power P and the reactive power Q it is possible to obtain a geometric representatio...

Page 8: ...2 Value weight var 10 300047 002Eh 1 PF L1 INT16 300048 002Fh 1 PF L2 INT16 300049 0030h 1 PF L3 INT16 300050 0031h 1 PF INT16 Negative values correspond to lead C positive value correspond to lag L V...

Page 9: ...ue 999d 2 7 2 Application menu MODBUS read and write mode Table 2 7 2 Modicom address Physical address Length words VARIABLE ENG UNIT Data Format Notes 304098 1001h 1 Type of application UINT 16 Value...

Page 10: ...t address UINT 16 Value min 1 Value max 247 Note The number of stop bits is fixed to 1 and the parity control is fixed to none 2 7 7 Reset commands MODBUS write only mode Table 2 7 12 Modicom address...

Reviews: