When the line selected is 3P, t

apping on the “

Electrical Values

” folder the top part of the page 

displays the Line

 

to Line voltages.

 

When the line selected is 3P + N, a second set of measurements is

 

displayed with the Line to 

neutral voltages. 
At the bottom of the page, the neutral unbalance, the line asymmetry and frequency values are 
displayed. 
The graphs show the distance between the set nominal voltage and the measured voltage.  
The filling of the bar graphs shows at a glance this distance.

 

Positive deviations are clockwise (CW), negative deviations are counterclockwise (CCW).

 

The graph ranges from -30% (CCW) to + 30% (CW).  
Below -30% and above 30% the fill of the bar is considered out of range.

 

 

 

Summary of Contents for DPD02DM44B

Page 1: ...DPD Manager Windows Desktop App for DPD setup via NFC communication User Manual...

Page 2: ...hich are the most commonly used If factory default parameters are not completely suitable they can be modified according to own requirements by Windows PC tablet or smartphone Windows and Mobile apps...

Page 3: ...ry DPD Manager Installation 4 Create DPD Configurations 6 Load Configuration from another DPD 14 Actions on the Configuration File 16 DPD locking unlocking 18 Real Time Reading 21 Country Default Sett...

Page 4: ...lowing links http www productselection net Download UK ACR1252_Winx86_32bit zip http www productselection net Download UK ACR1252_Winx64_64bit zip Select the 32 bit or 64 bit driver based on your syst...

Page 5: ...is sitting side by side to confirm which device is going to be used This applies in the following cases apply a configuration to the target DPD see alarms or outputs status and variable values in rea...

Page 6: ...6 Create DPD Configurations Select Create new configuration from the middle screen button or from Configuration in the top left menu...

Page 7: ...480VAC line to line 3 PH N 120 to 277VAC line to neutral Set the inhibition time of the Power ON delay according to the mains instability time at the start up of the load to avoid unnecessary interven...

Page 8: ...oltage Frequency or Asymmetry Select if the alarm is Over or Under In case of asymmetry alarm it is enough to set the percentage Set the setpoint values based on the following ranges 3PH voltage 177 t...

Page 9: ...mmetry 1 to 5 frequency 0 1 to 5 Set the delay values in the range delay ON alarm 0 to 60s alarm OFF delay 0 to 600s The configured alarms show the type and value of the measurement When all alarms ar...

Page 10: ...value is 85 for delta voltages Setting the threshold below 85 can cause insensitivity to the regenerated voltage while setting the threshold above 85 can cause excessive sensitivity to small network...

Page 11: ...T AWARE OF THEIR FUNCTION In the OUTPUT 1 and OUTPUT 2 pages one or more of the previously set non priority alarms are associated with the outputs When multiple alarms are set they are associated with...

Page 12: ...configuration settings If the configuration is correct tap Apply Configuration to upload it to the target DPD When the popup appears place the ACR1252U next to the DPD front face If serial number con...

Page 13: ...of the DPD If the DPD is correct tap Confirm Relay otherwise tap Change Relay and try again If serial number confirmation is disabled the configuration is immediately applied When the popup shown abov...

Page 14: ...ed from an already configured DPD to replicate it to another DPD or modify it before using it To apply this operation select from the main page Load from a device or Configuration then Load from a dev...

Page 15: ...rial number of the source DPD If serial number confirmation is disabled the configuration is immediately loaded When the popup shown above appears the download is completed and the configuration is sa...

Page 16: ...guration as shown above The file can be saved on the PC or sent by email Skype etc The configuration can be modified by pressing Edit Configuration or the pencil at the top right The configuration can...

Page 17: ...17 The configuration can be imported as a file on the PC by pressing Configuration then Import from file...

Page 18: ...8 DPD locking unlocking When commissioned the DPDs can be locked to prevent tampering with the configuration Select Lock device or Unlock device as shown above Place the ACR1252U next to DPD front fac...

Page 19: ...n is enabled the popup shown above appears Check the serial number of the source DPD If serial number confirmation is disabled the app immediately proceeds to the next step Enter a 4 digit numeric pas...

Page 20: ...follow the steps below 1 provide the serial number printed on the front face of the DPD to be unlocked 2 wait to receive from the customer support a password valid only for the DPD whose serial number...

Page 21: ...nly possible when the DPD is operating The real time allows reading all the alarms status the last alarm triggered and the measurement values voltages L1 L2 and L3 frequency and asymmetry Tap Real Tim...

Page 22: ...the status of all configured non priority alarms and the status of all priority alarms The characters are GREEN when all is correct while anomalies are displayed in RED The last triggered alarm is dis...

Page 23: ...At the bottom of the page the neutral unbalance the line asymmetry and frequency values are displayed The graphs show the distance between the set nominal voltage and the measured voltage The filling...

Page 24: ...e commonly used in Europe Default USA are those commonly used in USA Default Australian are those commonly used in Australia If serial number confirmation is enabled the popup shown above appears Conf...

Page 25: ...s 0s DELAY OFF 0s 0s 0s PRIORITY ALARMS PHASE LOSS ENABLE ON ON ON PHASE LOSS THRESHOLD 85 85 85 NEUTRAL LOSS NOT ACTIVE NOT ACTIVE NOT ACTIVE PHASE SEQUENCE ENABLE ON ON ON OUT OF RANGE MEASUREMENT O...

Reviews: