Carlin 201GAS Instruction Manual Download Page 11

Model 201GAS burner — Instruction manual

Carlin part number MN201GAS Rev.  03/14/11

– 11 –

Where appliance instructions differ from this manual, follow the appliance instructions.

4.  Check sytem • start-up burner/appliance

Inspect/check system

Before starting the burner and appliance, verify the system has been installed 

as directed by this manual and the appliance instructions.

Check gas piping for leaks

  Disconnect the burner from the gas supply line if gas line 

test pressure will exceed 14 inches w.c. Exposing the burner 
combination gas valve to pressure higher than 14 inches w.c. 

can damage the valve seat, resulting in potentially unsafe 
operation.

You can usually test the gas piping by allowing the line to fill with gas to 
main regulator outlet pressure. 
1.  Shut off gas flow to all equipment connected to the meter.

2.  If test pressure will be less than 14 inches w.c., turn the burner com

-

bination gas valve knob to OFF. If test pressure will be higher than 14 

inches, remove the burner from the gas line by shutting off the main 

manual gas valve installed near the burner (per Figure 7, page 9) and 

disconnecting the ground joint union. See warning above.

3.  Watch the gas meter dial. For a one half cubic foot per revolution dial, 

there should be no movement of the dial for at least 5 minutes. For 

larger volumes per revolution, increase this time proportionately.

4.  If you detect a gas leak, locate the leak with a soap suds mixture and 

repair it. Then test the system for leaks again.

  Do not test for leaks with an open flame. And do not use 

oxygen as a test gas. Either of these could cause an explo-
sion, resulting in severe personal injury, death or substantial 
property damage.

Verify flame failure Lockout of 60200FR control

1.  Install a hose barb fitting in the combination gas valve outlet pressure 

tap and connect with a hose to a U-tube manometer.

2.  Close the main manual gas valve and turn the combination gas valve 

knob to ON.

3.  Turn on power to appliance and set appliance limit(s) to call for heat.

4.  Burner motor will start. The 60200FR will run for its prepurge timing, 

then start the ignitor. Approximately one second later, the combination 
gas valve will open. (The manometer should show almost no pressure, 
because the main manual gas valve is closed.) 

5.  After the Trial for Ignition Period, the 60200FR will lockout and turn on 

the red LED. The ignitor will shut off and the gas valve will close. Turn 

off power and set controls to stop call for heat.

6.  If Lockout does not occur, replace the 60200FR control.

Inspect/check system

Before starting the burner and appliance, verify the system has been installed 

as directed by this manual and the appliance instructions.

  Do not start the burner if you smell gas or if there may be gas 

present in the appliance combustion chamber, appliance or 
the vent system. An explosion could occur,  causing severe 
personal injury, death or substantial property damage. 

  During  initial  start-up,  you  must  be  constantly  alert  for 

emergency conditions such as fuel leaks, electrical malfunc-
tions, etc. Familiarize yourself with the location of manual 
shutoff valves and switches so you can quickly use them if 
needed.

  If the burner fails to ignite, NEVER attempt to manually bypass 

the normal sequence of the control, which provides purging 
of the combustion chamber. 

Figure 9

  Air band adjustment

Bleed gas line

Purge all air from the gas line. Purge to outside of the building, NEVER into 

the appliance or burner.

Leak test near-burner gas piping

If piping near burner has not already been pressure tested, open main 
manual gas valve on supply to burner and smell around area for any signs of 
gas. Apply a soap suds mixture to all gas piping joints near burner and check 
for any leaks. If any leaks appear, repair before proceeding and retest.

Set burner air band

See Figure 9. Loosen air band locking screw. Then rotate band until it is open 

to the setting given in Table 1, page 7. Tighten air band locking screw.
The Table 1 setting will probably be satisfactory without change. If the 
combustion test indicates a need for more or less air, however, you will 
have to adjust the band accordingly.

Check burner and primary control

Inspect burner thoroughly. Verify that hinged cover gasket is closed and 
screw is tight. Verify all wiring is in place and all components are secure 

and in position.

Summary of Contents for 201GAS

Page 1: ...trol Carlin Model 60200FR microprocessor control Agencies UL Listed Installer servicer Except where specifically stated otherwise this manual must be used only by a quali fied service technician In th...

Page 2: ...liance service When servicing the burner Disconnect electrical supply to burner before attempting to service to avoid electrical shock or possible injury from moving parts Burner and appliance compone...

Page 3: ...volts continuous duty rated 11 Primary control Carlin Model 60200FR microprocessor based inter rupted ignition flame supervisory control flame rectification 12 Flame current test jack O F F O N 20100...

Page 4: ...ate do not vent into a masonry chimney that has one or more sides exposed to the outside Install a listed stainless steel liner to vent the flue products A defective vent system could result in severe...

Page 5: ...construction is unusually tight see National Fuel Gas Code NFPA 54 ANSI Z223 1 or B149 1 B149 2 Installation Code for Canadian installations for definition you will need to provide air openings into t...

Page 6: ...ional forced draft flange Failure to comply could result in severe personal injury death or substantial property damage See page 19 for required dimensions and bolt locations 1 Prepare site prepare bu...

Page 7: ...C 4 11 14 8 10 9 Burners with welded flange have fixed usable tube length UTL Verify length is correct for the application Burners with adjustable flange Usable tube length UTL varies with air tube l...

Page 8: ...ect redrill gas orifice when required Turn off power to the burner appliance before proceeding Close main manual gas valve in gas line to burner Then disconnect the ground joint union to allow rotatin...

Page 9: ...ply pressure 14 inches w c Minimum supply pressure 5 inches w c Do not expose the combination gas valve to gas pressure in excess of 14 inches water column Higher pressure could dam age the valve seat...

Page 10: ...rner requires a 120 vac 60 hz single phase power supply with at least a 10 amp fuse The current draw will be when equipped with typical motor and Carlin 41800 electronic ignitor approximately 2 The 12...

Page 11: ...s prepurge timing then start the ignitor Approximately one second later the combination gas valve will open The manometer should show almost no pressure because the main manual gas valve is closed 5 A...

Page 12: ...restart Releasing the button before the LED s turn off will cause the control to remain in latch up The 60200FR control will not reset from lockout or latch up if power is interrupted Power ON Open al...

Page 13: ...k at flame through appliance observation port The flame should be a soft blue with well defined orange and yellow tips for natural gas or well defined yellow tips for propane gas If you make air or ga...

Page 14: ...ontinue with normal operation If switch fails to operate correctly replace the switch and retest NEVER attempt to adjust the air pressure switch setting This could allow unsafe operation of the burner...

Page 15: ...urner from appliance and inspect diffuser plate ignitor electrode and flame rod see Figures 5 and 6 page 8 Remove ignitor electrode flame rod assembly to clean and adjust if necessary To remove assemb...

Page 16: ...aced remove the two bolts securing the motor to housing 2 Disconnect the motor wires in the burner junction box 3 Loosen the Allen screw securing the blower to the motor shaft and remove the wheel 4 W...

Page 17: ...Model 201GAS burner Instruction manual Carlin part number MN201GAS Rev 03 14 11 17 Where appliance instructions differ from this manual follow the appliance instructions 7 Troubleshooting...

Page 18: ...on of ignitor electrode per Figures 5 and 6 page 8 Adjust if needed Check primary voltage to ignitor If ignitor receives 120 VAC and doesn t generate spark replace ignitor Airflow Check air band setti...

Page 19: ...mbers with negative overfire pres sure For pressurized firing you must obtain a burner with a welded flange designed for use with the appliance You can also use the optional Forced draft flange Failur...

Page 20: ...e 29652 9938440XX Contact factory 10 Blower wheel 28563 11 Motor 1 6 HP 140 WATT PSC 98611 12 Junction box 4 x 4 with grommet lock washer conduit nipple to burner housing and bracket not shown Contact...

Page 21: ...ffer from this manual follow the appliance instructions 9 Replacement parts continued Burner is shown with welded flange supplied only on burners ordered for specific appliance applications Other burn...

Page 22: ...Model 201GAS burner Instruction manual Carlin part number MN201GAS Rev 03 14 11 22 Where appliance instructions differ from this manual follow the appliance instructions...

Page 23: ...Model 201GAS burner Instruction manual Carlin part number MN201GAS Rev 03 14 11 23 Where appliance instructions differ from this manual follow the appliance instructions...

Page 24: ...Model 201GAS burner Instruction manual Carlin part number MN201GAS Rev 03 14 11 24 Where appliance instructions differ from this manual follow the appliance instructions...

Reviews: