Important:

l

do not install a stop valve in the steam hose;

l

when installation is complete, flush the steam line to remove any contaminants and processing
residues.

l

exposure of the skin to a jet of hot steam may cause severe burns;

l

do not over-tighten the hose clamps (max. torque=180 N·cm).

2.1.2 Condensate hose

Follow these instructions when installing the condensate hose:

l

the condensate hose may be filled with hot water or steam: contact with the skin can cause serious
burns;

l

connect the hose to a drain in accordance with national and local regulations in force;

l

the condensate hose must have a minimum downward slope and must flow into a 200 mm high drain
trap: the drain trap must be at least 300 mm below the connection to the blower. Alternatively, the
condensate hose can be connected to the condensate drain tank located at the top of the humidifier;

l

condensate drains must be installed at all the lowest points and wherever the drain line goes from
horizontal to vertical. The drain line must be connected to a “T” connector and have a minimum
downward slope. The drain trap must be at least 300 mm below the connection.

l

make sure that the condensate drain lines are not blocked;

l

do not over-tighten the clamps on the condensate hose.

Important:

before starting the humidifier, fill the drain traps with water.

Fig.2.b

ENG

VSDU0A0003

 

+030222190

 

rel.

 

1.4 – 11.02.2021

2. Preparing for assembly  |  

11

Summary of Contents for VSDU0A0003

Page 1: ...MANUALE D USO USER MANUAL VSDU0A0003 030222190 ITA ENG Up to date version available on www carel com VSDU0A0003 Testata ventilante Steam blower ENG ITA...

Page 2: ......

Page 3: ...lizzare il prodotto nelle vicinanze di oggetti che possono danneggiarsi a contatto con l acqua o condensa d acqua CAREL declina ogni responsabilit per danni conseguiti o diretti a seguito di perdite d...

Page 4: ...lla sicurezza sul posto di lavoro e la prevenzione degli incidenti l La testata ventilante destinata esclusivamente per l umidificazione dell aria nelle condizioni operative previste l Per far funzion...

Page 5: ...E AL MONTAGGIO 10 2 1 Prescrizioni 10 3 MONTAGGIO 12 3 1 Operazioni preliminari 12 3 2 Montaggio 12 4 MANUTENZIONE E PARTI DI RICAMBIO 15 4 1 Componenti 15 4 2 Sostituzione componenti 15 5 CARATTERIST...

Page 6: ......

Page 7: ...gio sul coperchio dell umidificatore 4 Tab 1 b 1 1 3 Accessori Cod Descrizione VSDREM0003 Kit per installazione a parete viti tasselli 2 staffe pressacavo attacco tubo vapore fondo 1312368AXX Tubo con...

Page 8: ...vapore entra nella testata dopo un certo tempo il termostato raggiunge la temperatura di 50 C oppure l uscita morsetto J19 del controllo c phc d il consenso e i ventilatori si attivano L aria preleva...

Page 9: ...i umidificatori da cui necessario rimuovere il ponticello vedere la tabella seguente Svitare le viti per rimuovere il ponticello P Fig 1 e La testata ventilante esce di fabbrica con il ponticello mont...

Page 10: ...el vapore seguire le seguenti avvertenze l usare esclusivamente tubi forniti da CAREL tubi di altro materiale possono influenzare negativamente il funzionamento del sistema l il tubo del vapore deve e...

Page 11: ...ve avere una pendenza minima e deve confluire in un sifone alto 200 mm il sifone deve trovarsi almeno 300 mm sotto l attacco della testata ventilante In alternativa il tubo della condensa pu essere co...

Page 12: ...e i pannelli superiore e anteriore dell umidificatore 2 Rimuovere i tappi 1 e 2 del pannello superiore dell umidificatore 3 Tagliare a misura il tubo del vapore 3 fornito a corredo e collegarlo all a...

Page 13: ...A collegare come in figura gli elementi A e B per formare la staffa a L B fissare le viti e i dadi C collegare le 2 staffe con il traverso Fissare a muro la struttura portante con i tasselli in corris...

Page 14: ...re le viti dell attacco del tubo vapore 4 Sostituire l attacco curvo A con l attacco diritto B Fig 3 h Fig 3 i 5 Infilare il fondo S fino a fine battuta 6 Avvitare le viti di fissaggio agli inserti fi...

Page 15: ...azione elettrica all umidificatore portando l interruttore generale dell impianto su spento OFF rimuovere il coperchio della testata ventilante vedere paragrafo precedente sostituire il componente gua...

Page 16: ...mentazione l Verificare il fusibile l Verificare che l umidificatore funzioni e vi sia richiesta di umidit Ventilatore non funziona ma l umidificatore sta generando vapore l Linea vapore installata in...

Page 17: ...elle accoppiamento umidificatori humiSteam uscita umidificatore mm 22 30 0 9 1 2 30 1 2 40 1 6 2x 40 1 6 4x 40 4x 1 6 capacit umidificatore kg h 1 3 5 8 9 10 15 18 25 35 45 65 90 130 umidificatore UE0...

Page 18: ......

Page 19: ...corrosive chemicals solvents or aggressive detergents to clean the inside and outside parts of the humidifier unless specifically indicated in the user manual l Do not drop hit or shake the humidifier...

Page 20: ...l and in particular the safety instructions must be scrupulously observed l This appliance can be used by children over the age of 8 and by persons with reduced physical sensory or mental capabilities...

Page 21: ...RING FOR ASSEMBLY 10 2 1 Requirements 10 3 ASSEMBLY 12 3 1 Preliminary operations 12 3 2 Assembly 12 4 MAINTENANCE AND SPARE PARTS 15 4 1 Components 15 4 2 Component replacement 15 5 TECHNICAL SPECIFI...

Page 22: ......

Page 23: ...e humidifier cover 4 Tab 1 b 1 1 3 Accessories P N Description VSDREM0003 Wall mounting kit screws anchors 2 brackets cable gland steam hose fitting base 1312368AXX Condensate hose ID 9 mm 0 35 in 131...

Page 24: ...n steam enters the blower after a certain time either the thermostat detects a temperature of 50 C or the output terminal J19 on the c pHC controller gives the signal and the fans are activated The ai...

Page 25: ...of humidifiers where the jumper must be removed see the following table Unscrew the screws to remove the jumper P Fig 1 e The blower leaves the factory with the jumper inserted blower managed by the...

Page 26: ...eam hose Follow these instructions when installing the steam hose l only use hoses supplied by CAREL hoses made from other materials may adversely affect operation of the system l the steam hose must...

Page 27: ...a minimum downward slope and must flow into a 200 mm high drain trap the drain trap must be at least 300 mm below the connection to the blower Alternatively the condensate hose can be connected to th...

Page 28: ...the front and top of the humidifier 2 Remove the caps 1 and 2 on the humidifier top panel 3 Cut the steam hose 3 supplied to the right length and connect it to the fitting 4 To secure it tighten the...

Page 29: ...nts A and B to form the L shaped bracket as shown in the figure B fasten the bolts and nuts C connect the two brackets with the crossbar Secure the supporting structure to the wall using anchors throu...

Page 30: ...remove the screws from the steam hose fitting 4 Replace the curved fitting A with the straight fitting B Fig 3 h Fig 3 i 5 Slide the support S fully in 6 Tighten the fixing screws to the threaded inse...

Page 31: ...ect power to the humidifier by turning the main system switch to OFF l remove the cover from the blower see the previous paragraph l replace the faulty component l once having completed maintenance re...

Page 32: ...wered l Faulty fan l Check power supply l Check fuse l Make sure that the humidifier is operating and humidity production is required The fan is not working but the humidifier is generating steam l St...

Page 33: ...4 R1999 5 0 1 Humidifier connection tables humiSteam humidifier outlet mm 22 30 0 9 1 2 30 1 2 40 1 6 2x 40 1 6 4x 40 4x 1 6 humidifier capacity kg h 1 3 5 8 9 10 15 18 25 35 45 65 90 130 humidifier U...

Page 34: ...ENG 18 VSDU0A0003 030222190 rel 1 4 11 02 2021...

Page 35: ......

Page 36: ...dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 email carel carel com www carel com VSDU0A0003 030222190 rel 1 4 11 02 2021 CAREL can accept no responsibility for po...

Reviews: