1.1.5 Dimensions - mm (in)
Fig.1.b
1.1.6 Structure
Fig.1.c
Ref.
Description
1
Steam outlet
2
Air outlet
3
Light
4
Fans
5
Thermostat (Klixon)
Ref.
Description
6
Terminal block
7
Fuse holder
8
Condensate outlet fitting (Ø 9 mm - 0.35 in)
9
Steam hose fitting (Ø 30 mm - 1.18 in)
1.1.7 Operating principle
The blower is connected to the power terminals provided inside the humidifier and is powered even
when the humidifier is off. When steam enters the blower, after a certain time either the thermostat
detects a temperature of 50°C or the output (terminal J19) on the c.pHC controller gives the signal and
the fans are activated. The air, taken in from the rear, is mixed with steam before being delivered into the
room, where it is easily absorbed. The blower features two different types of operating logic:
1. independent of the humidifier;
2. managed directly by the humidifier (c.pHC). The controller delays blower activation for a set time.
Deactivation can also be delayed to allow the blower to dry.