“Ultrasound for fancoil” +0300059PT - rel. 1.6 - 06.10.2020

6.4 Dipswitch 

configuration: 

2

3

6

4

7

5

1

8

ON

Fig. 6.d

1.

Communication  
OFF   Serial 485 Carel/Modbus 
ON    tLAN

2-3

tLAN address (if 1 is ON)
OFF/OFF  - -
OFF/ON   address 1
ON/OFF   address 2
ON/ON    address 3

4

Serial 485 / tLAN baud rate
OFF          19200
ON           9600

5-6

Humidity set point
OFF/OFF   50 %rH
OFF/ON     30 %rH
ON/OFF     40 %rH
ON/ON      60 %rH

7

TAM
OFF          disabled
ON           enabled

8

Production transducer management (only for 2-transducer version)
OFF --> parallel management (modulation of all 2)
ON  --> if demand is less than 50%, it works only one transducer at a 
time, alternately

Tab. 6.c 

6.5  Main board connections 

Depending on the type of signal used, atomized water production can be 
enabled and/or managed in different ways.

HUMIDOSTAT OR REMOTE CONTACT (ON/OFF action)

Production is enabled by closing terminal M14.
M14 can be connected to a switch, a humidistat or a controller (voltage-
free contact, max 5 Vdc open, max 7 mA closed).

TH TEMPERATURE/HUMIDITY PROBE (Optional)

If the TH TEMPERATURE/HUMIDITY PROBE is connected to the G termina, 
atomized water production starts if:

• 

the terminal M14 is closed;

• 

in humidity control mode (A0 = 3), The humidity value measured by 
the probe is lower than the set point (pre-set at 50% rH and modifiable 
via dipswitches 5-6 or on the display);

• 

in dew point temperature control mode (A0 = 4), the dew point value 
calculated based on the temperature and humidity measured by the 
probe is lower than the set point (pre-set at 10°C/50°F and modifiable 
via the optional display).

R

e

m

ote

 

ON

/

OFF

M 1

4

+    

GND

Fig. 6.e

485 SERIAL CONNECTION
Carel/Modbus protocol 

R

S 485

R

X+

/

TX+

G

N

D

M

 11

R

X

-/

TX

-

Fig. 6.f

NOTICE:

 for RS485 connections in household (IEC EN 55014-1) and 

residential (IEC EN 61000-6-3) environments, use shielded cable (with 
shield connected to PE both on the terminal and controller ends), 
maximum length specified by the EIA RS485 protocol, equivalent to 
European standard CCITT V11, using AWG26 twisted pair cable; the input 
impedance of the 485 stage is 1/8 unit-load (96 kOhm). 

This configuration allows a maximum of 256 devices to be connected, 
with cables in separate conduits from the power cable

.

ALARM RELAY

This is used to signal one or more alarms via a remote connection.

A

l

ar

re

l

a

y

NO

CO

MM

ON

M 1

5

Fig. 6.g

ALARM RELAY POWER SUPPLY

The connections shown in figure can be used to directly control a light or 
an auxiliary relay coil  30 Vdc (24 Vac rectified), 3 W max.

+24 V

GND

Alarm signal 

(max 3W)

M 15

Fig. 6.h

NOTICE: 

in industrial environments (IEC EN61000-6-2) the signal cables 

leaving the unit must not exceed 10 m (33 ft)

(1)

 in length: remote on/

off digital input (terminals M14.1...M14.2) and shielded cable for RS485 
communication.

Summary of Contents for UU01F1

Page 1: ... o l u t i o n s Compact NO POWER SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT LEIA E CONSERVE ESTAS INSTRUÇÕES READ AND SAVE THESE INSTRUCTIONS Manual de utilização Umidificadores de ultrassons User manual Ultrasound humidifier ...

Page 2: ......

Page 3: ...zação de atualização de Software 17 8 6 Acesso e modificação dos parâmetros 17 8 7 Par Visualização dos valores de fábrica 17 8 8 Rein o do contador a partir do visor 17 9 PRINCÍPIOS DE FUNCIONAMENTO 18 9 1 Nebulização por ultrassons 18 9 2 Princípios de regulação 18 9 3 Modulação da capacidade em paralelo Dipswitch 8 em Off 18 9 4 Modulação da capacidade em série apenas versão 1l h Dip switch 8 em ...

Page 4: ...4 POR Ultrasound for fancoil 0300059PT rel 1 6 06 10 2020 ...

Page 5: ...não permitidos pelo fabricante são ilícitos CAREL não assume qualquer responsabilidade por utilizações modificações ilícitas Não tente abrir o umidificador de modos diversos daqueles indicados no manual CAREL adota uma política de desenvolvimento contínuo portanto a CAREL reserva se o direito de efetuar alterações e otimizações em qualquer componente descrito no presente documento sem aviso prévio O...

Page 6: ...ifique regularmente se todos os dispositivos de segurança e monitoramento estão funcionando corretamente Não remova ou desative os dispositivos de segurança AVISO Possibilidade de vazamentos de água devido a conexões defeituosas ou mau funcionamento A água é continuamente e automaticamente introduzida e descarregada no umidificador As conexões e os componentes de transporte de água devem ser verifica...

Page 7: ... a um transporte incauto ou impróprio Ƒ transporte o umidificador até o local de instalação antes de removê lo da embalagem segurando a embalagem pela parte de baixo Ƒ abra a caixa de papelão retire os separadores de material anticolisão e retire o umidificador Ƒ a unidade deve ser colocada sempre em um local seco antes da instalação 3 5 Material incluído Verifique a presença de Modelo 230 V 115 V 1 ...

Page 8: ...cador permitem expelir as partículas de umidade e difundi la no ambiente circundante a reposição da água é feita a pedido da boia depois de perceber que o nível desceu abaixo do valor recomendado A tecnologia por ultrassons é gerada por uma tensão em entrada que é transformada através de circuito oscilante em um sinal de alta frequência de 1 7 MHz O sinal é transmitido para um transdutor com a par...

Page 9: ...ue a tubulação de alimentaçãodurantecercade30minutoscanalizandoaáguadiretamente na descarga sem a introduzir no umidificador Isso para eliminar eventuais resíduos e substâncias de laboração que poderiam entupir a válvula de carga 4 1 Água de alimentação O umidificador de ultrassom funciona com água desmineralizada Se utilizar a água normal isso irá diminuir a vida dos transdutores e em especial o in...

Page 10: ...o de curvas e estrangulamentos pode causar condensação e diminuir a quantidade de umidade imitida evite solicitações que comportem estresse mecânico no terminal de saída da umidade Fig 5 a Fig 5 b 5 1 Acessórios Ducto para ventilador Fig 5 c O ducto UUKCY00000 pode ser instalado na parte superior do ventilador removendo a grelha de proteção de modo a tomar o ar de um sítio diferente daquele onde e...

Page 11: ...carga Se na instalação for utilizado o sistema de distribuição UUKDP0 00 rode o tubo até os furos ficarem na direção do fluxo de ar veja figura Fig 5 i Atenção a união dos tubos em relação à entrada de ar no humiSonic e ao envio da água nebulizada no ducto tem de ser posicionada de modo a evitar as diferenças de pressões Um excessivo desequilíbrio das pressões poderia causare uma anomalia no funciona...

Page 12: ...tricas o aparelho deve ser desconectado da fonte de alimentação e deve ser protegido contra a reinicialização A desconexão elétrica deve ser garantida por uma medição AVISO O correto cabeamento do umidificador de ultrassons é confiado ao instalador final segundo o quanto exigido pelas normas vigentes CEI EN 60335 1 6 1 Predisposições elétricas Placa principal Fig 6 a Legenda A Entrada de alimentação ...

Page 13: ...para 50 rH e modificável através de dip 5 6ou através do visor no modo de regulação de temperatura de orvalho A0 4 o valor da temperatura de orvalho calculado a partir da temperatura e umidade detectada pela sonda é inferior ao ponto de ajuste predefinido em 10 C 50 F e pode ser modificado através de visor opcional Remote ON OFF M 14 GND Fig 6 e CONEXÃO SERIAL 485 Protocolo Carel Modbus RS 485 RX TX ...

Page 14: ...rnes M10 1 e M10 2 O borne de alimentação M10 3 pode ser conectado através de cabo com comprimento máximo de 2 m 6 6 ft para comprimentos maiores utilize uma alimentação externa com massa eletricamente conectada à massa do controle definir o parâmetro A0 2 para ativar a regulação da sonda veja cap Parâmetros de configuração e o parâmetro A2 em função do sinal escolhido 0 10V 2 10V 0 20 4 20mA veja c...

Page 15: ...uer um uso frequente para evitar anomalias de funcionamento Através de b0 veja tabela parâmetro b0 Osmose é possível fazer com que a lavagem seja efetuada na primeira partida sucessiva às horas de inatividade contínuas definidas em b2 7 ARRANQUE INTERFACE COM O USUÁRIO E FUNÇÕES DE BASE Antes de ligar o umidificador verifique Ƒ ligações hidráulicas em caso de vazamentos de água não ligue o umidificado...

Page 16: ... está normalmente aberta Tab 8 a 8 3 Teclado Tecla Função retorno à visualização anterior UP na máscara principal visualização dos valores da umidificação veja parágrafo sucessivo na lista dos parâmetros navegação no sentido circular dos pa râmetros e modificação dos valores dos parâmetros DOWN na máscara principal visualiz dos valores da umidificação na lista dos parâmetros navegação no sentido circ...

Page 17: ...ões e o estado do umidificador Na máscara principal pressione ENTER por 2 segundos introduza a senha 77 com as teclas UP ou DOWN ENTER para confirmar e acessar a lista dos parâmetros UP ou DOWN para rolar a lista circular ENTER para selecionar um parâmetro visor set UP para modificar aumentando o valor do parâmetro Para rolar mais rapidamente pressione também DOWN DOWN para modificar diminuindo o valo...

Page 18: ...vidas por meio de ar forçado A quantidade de água nebulizada depende do nível da água da temperatura da água e da distribuição no ar O nível da água é mantido constante mediante a utilização de válvulas de carga e descarga e de um sensor de nível É recomendável utilizar água desmineralizada no caso em que se utilize água de rede os sais que se depositam com o tempo são causa da progressiva incrust...

Page 19: ...não descer abaixo do nível baixo a produção é bloqueada A unidade espera alguns minutos com base no valor definido no parâmetro AA padrão 10 minutos No visor aparece a mensagem Rty depois disso o controle reativa a produção Se a condição se apresentar novamente é gerado o alarme bloqueante EP Se após uma porcentagem de tempo de A8 definida pelo parâmetro Ab default 70 a água estiver acima do nível a...

Page 20: ...étricos h 0 9999 9999 com água desmineralizada b0 Opções de funcionamento veja tabela parâmetro b0 0 255 7 b1 Tempo de intervalo entre duas lavagens min h 0 120 60 b2 Tempo de inatividade para lavagem h 1 240 24 b3 Tempo de lavagem carga descarga min 0 10 1 b4 Tempo de atraso do o início s 0 120 10 b5 Horas de funcionamento por alarme CL h 0 9999 5000 b6 Tempo de nova visualização do alarme CL apó...

Page 21: ...Ligado 24 M OFF Aberto SP NF Desligado Desligado Desligado 25 M OFF Aberto SP NF Desligado Desligado Ligado 26 M OFF Aberto SP NF Ligado Desligado Desligado 27 M OFF Aberto SP NF Ligado Desligado Ligado 28 M OFF Aberto SP NF Desligado Ligado Desligado 29 M OFF Aberto SP NF Desligado Ligado Ligado 30 M OFF Aberto SP NF Ligado Ligado Desligado 31 M OFF Aberto SP NF Ligado Ligado Ligado 32 M OFF Fech...

Page 22: ... Ligado Desligado Ligado 124 M ON Fechado SP NF Desligado Ligado Desligado 125 M ON Fechado SP NF Desligado Ligado Ligado 126 M ON Fechado SP NF Ligado Ligado Desligado 127 M ON Fechado SP NF Ligado Ligado Ligado 128 H OFF Aberto AL NA Desligado Desligado Desligado 129 H OFF Aberto AL NA Desligado Desligado Ligado 130 H OFF Aberto AL NA Ligado Desligado Desligado 131 H OFF Aberto AL NA Ligado Desl...

Page 23: ...ligado Ligado Ligado 214 H ON Aberto SP NA Ligado Ligado Desligado 215 H ON Aberto SP NA Ligado Ligado Ligado 216 H ON Aberto SP NF Desligado Desligado Desligado 217 H ON Aberto SP NF Desligado Desligado Ligado 218 H ON Aberto SP NF Ligado Desligado Desligado 219 H ON Aberto SP NF Ligado Desligado Ligado 220 H ON Aberto SP NF Desligado Ligado Desligado 221 H ON Aberto SP NF Desligado Ligado Ligado...

Page 24: ...enos 500 ms 11 1 Lista das variáveis de supervisão A variáveis analógicas Modbus REGISTERS R W CAREL Modbus 1 0 parâm d0 Leitura de temperatura da sonda TH R 2 1 parâm d1 Leitura de umidade da sonda TH R 3 2 parâm d2 Leitura da sonda R 4 3 parâm d5 Produção instantânea R 9 8 parâm d8 Temperatura de orvalho R I variáveis inteiras Modbus REGISTERS R W CAREL Modbus 1 128 senha de acesso níveis R W 7 ...

Page 25: ...a leitura da sonda integrada R 87 214 Atualização firmware secundário 1 R 89 216 Estado do umidificador secundário 1 R 92 219 Parâmetro d3 secundário 1 Contador de horas funcionamento R W 93 220 Atualização firmware secundário 2 R 95 222 Estado do umidificador secundário 2 R 98 225 Parâmetro d3 secundário 2 Contador de horas funcionamento R W 99 226 Atualização firmware secundário 3 R 101 228 Estado do...

Page 26: ...al è necessário Defina D37 1 Defina o parâmetro A0 1 Carel 20 Modbus 148 Modalidade Regulação Proporcional Defina a variável inteira 60 Carel 188 Modbus ao nível desejado 0 1000 0 100 0 Para gerenciar a produção com uma sonda de umidade lida pelo Principal Defina D37 1 Defina o parâmetro A0 2 Carel 20 Modbus 148 Modalidade Regulação Sonda de umidade Defina a variável inteira 60 Carel 188 Modbus para o v...

Page 27: ... sinal proveniente da sonda indica uma umidade inferior a 20 rH Verifique o sinal cabo da sonda de umiddade sim umidificação interrompida AUTO 4 lampejos lentos EE Alarme EEprom problemi nell EEPROM se o problema persistir contate o centro de assistência CAREL sim umidificação interrompida Se persistir contate a assistência 1 lampejo rápido E0 Teste de funciona mento não efetuado Teste de funcionamen...

Page 28: ...s no tanque Verifique visualmente o interior do tanque Incrustações de calcário depositado na superfície dos transduto res piezelétricos Limpe o interior do tanque e substitua os transdutores Tab 12 b Estas causas de mau funcionamento podem ser evitadas através da manutenção preventiva 2 Se a causa não foi detectada com as verificações anteriores alguns componentes podem estar avariados Verifique o i...

Page 29: ...00000 Parte elétrica UU01 01 UU01G 01 Transformador da alimentação 230 24 50V UUKTFD0010 A Transformador da alimentação 115 24V UUKTF10010 A Transformador da alimentação 115 50V UUKTF30010 A Kit cabos UU01F UUKWR00010 G Kit cabos UU01G UUKWR10010 G Tab 13 a B L A E H D F G Fig 13 a 13 2 Desmontagem A manutenção do umidificador deve ser efetuada pelo Serviço Técnico de Assistência CAREL ou por pesso...

Page 30: ...nte com água canalizada desmineralizada Limpe os transdutores piezelétricos controle o deslizamento do sensor de nível AVISO Em caso de vazamento de água tirar a alimentação do umidificador e eliminar o vazamento 13 4 Limpeza e manutenção de outros componentes Em condições de normal utilização com água desmineralizada os transdutores duram cerca de 10 000 h Se ao contrário for utilizado outro tipo ...

Page 31: ...Driver D Driver Control board Drain valve Fill valve LEVEL FLOW SWITCH FAN HIGH LEV LOW LEV 50 Vac 24 Vac L N L N 230 Vac L N Fig 14 a 14 2 Modelo com alimentação a 115 V GND GND 21V F Level flow switch Fan GND Piezoelectric transducer Pool Driver D Driver Control board Drain valve Fill valve LEVEL FLOW SWITCH FAN HIGH LEV LOW LEV 50 Vac 24 Vac L N L N 115 Vac L N 115 Vac L N Fig 14 b ...

Page 32: ... mm2 ex 22 furos com 8 mm de diâmetro água de alimentação conexão G 1 8 F limites de temperatura C F 1 40 33 8 104 limites de pressão MPa 0 1 0 6 1 6 bar condutibilidade específica a 20 C 3 50 μS cm dureza total 0 25 mg l CaCO3 dureza temporária 0 15 mg l CaCO3 quantidade total de sólidos dissolvidos cR dependente da condutibilidade específica 1 resíduo sólido a 180 C dependente da condutibilidade e...

Page 33: ...orcentagem de pedido passado pelo Principal Fig 3 Contador de horas funcionamento Fig 4 reiniciável pressionando UP DOWN por 5 segundos veja parâmetro d3 Alarmes unidades Fig 5 se ausentes é visualizado reinicáveis pressionando UP DOWN por 5 segundos estado do umidificador Enb habilitado pressionar ENTER para desabilitar o umidificador e exibir dIS na máscara principal Para reabilitar pressionar ENT...

Page 34: ...s MAIN UNIT Connections M 11 TX RX GND GND 1 RS485 Supervisor ON OFF 4 Main Board Connections SECONDARY UNIT Connections 2 3 6 4 7 5 1 8 ON M9 M 11 M 11 M 11 6 6 6 TLan 2 Supervisor 1 Terminal 3 Active Probe 3 Ext Regulator TH probe HYHU000000 5 4 2 3 6 4 7 5 1 8 ON 2 3 6 4 7 5 1 8 ON 2 3 6 4 7 5 1 8 ON Terminal M 14 M 14 tLan POR Ultrasound for fancoil 0300059PT rel 1 6 06 10 2020 ...

Page 35: ...posição OFF dip switch 2 ou 3 na unidade de backup na posição ON sinal de solicitação enviado também à unidade de backup configuração apropriada do parâmetro b0 veja o cap Parâmetros de configuração Tabela do parâmetro b0 tanto na unidade principal quanto no backup para 1 habilitar em ambos a função de backup 2 ativar em ambos o relé de alarme em presença de alarmes AVISO o corpo do conector necessá...

Page 36: ......

Page 37: ...isplay 17 8 5 Display software release 17 8 6 Accessing and setting parameters 17 8 7 Parameters Recall default values 17 8 8 Reset hour counter from display 17 9 OPERATING PRINCIPLES 18 9 1 Ultrasonic atomisation 18 9 2 Control principles 18 9 3 Parallel flow rate modulation dipswitch 8 Off 18 9 4 Series flow rate modulation only model 1l h dipswitch 8 On 19 9 5 Automatic insufficient supply water man...

Page 38: ...4 ENG Ultrasound for fancoil 0300059PT rel 1 6 06 10 2020 ...

Page 39: ...l and on the labels affixed to the appliance All uses modifications not permitted by the manufacturer are illegal CAREL declines all liability for any illegal use of the product Do not attempt to open the humidifier in any way other than described in the manual CAREL adopts a policy of continual development consequently CAREL reserves the right to make changes and improvements to any component describ...

Page 40: ...pliance must not be operated with a DC power supply Regularly check that all safety and monitoring devices are working properly Do not remove or disable the safety devices NOTICE Possibility of water leaks due to faulty connections or malfunctions Water is continuously and automatically fed into and drained by the humidifier The connections and components that carry water must be regularly checked ...

Page 41: ... transport Ƒ move the humidifier to the site of installation before removing from the packaging grasping the neck from underneath Ƒ open the cardboard box remove the protective material and remove the humidifier Ƒ the unit must always be stored in a dry place before installation 3 5 Material supplied Check that the following are present Model 230 V 115 V 1 transformer 230 V primary and dual secondar...

Page 42: ... particles of moisture and distribute them into the surrounding environment water refill based on the float measures that the level has fallen below the recommended value Ultrasound technology uses a voltage input signal that is transformed via an oscillating circuit into a high frequency signal 1 7 MHz This signal supplies a transducer the top of which is in contact with the water which starts vibr...

Page 43: ...ap to prevent bad odours NOTICE When installation is completed flush the supply hose for around 30 minutes by piping water directly into the drain without sending it into the humidifier This will eliminate any scale or processing residues that may block the fill valve 4 1 Supply water The ultrasound humidifier works on demineralised water Using normal water will shorten transducer life specifically mai...

Page 44: ...g of the hose may cause condensate to form and decrease humidity delivery avoid loads that may cause mechanical stress on the humidifier outlet connector Fig 5 a Fig 5 b 5 2 Accessories Fan conveyor Fig 5 c The air flow conveyor UUKCY00000 can be installed on the top of the fan removing the protection grill so as to take in air from a different place to where humiSonic is installed Elbow connector Fi...

Page 45: ... If using the UUKDP0 00 distribution system in the installation turn the hose so that the holes are in the direction of air flow see the figure Fig 5 i NOTICE the connections of the hoses for humiSonic air intake and atomised water delivery into the duct must be positioned so as to avoid pressure differences Excessive unbalances in pressure may cause the system to malfunction preventing atomised wate...

Page 46: ...Vac rectified max 3W M15 3 M15 4 N auxiliary card connection Electrical connections GND GND 21V F Level flow switch Fan GND Piezoelectric transducer Pool Driver D Driver Control board Drain valve Fill valve LEVEL FLOW SWITCH FAN HIGH LEV LOW LEV 230 Vac 50 Vac L N 24 Vac L N L N 24Vac Drivers C A B 1 2 3 4 5 6 7 8 50Vac Fill Drain Fig 6 b 6 2 Internal electrical connections 1 Connect the wires from...

Page 47: ... at 50 rH and modifiable via dipswitches 5 6 or on the display in dew point temperature control mode A0 4 the dew point value calculated based on the temperature and humidity measured by the probe is lower than the set point pre set at 10 C 50 F and modifiable via the optional display Remote ON OFF M 14 GND Fig 6 e 485 SERIAL CONNECTION Carel Modbus protocol RS 485 RX TX GND M 11 RX TX Fig 6 f NOTIC...

Page 48: ...the main board connect the probe to terminals M10 1 M10 2 The power line M10 3 can be connected with cable of maximum lenght of 2 m 6 6 ft for greater lenghts use an external power supply with the signal earth electrically connected to the signal earth of the controller set parameter A0 2 to enable probe control see chapter Configuration parameters and parameter A2 depending on the chosen signal 0 ...

Page 49: ...means an alarm is active See the specific chapter 7 5 Reset tank hour counter NOTICE this operation must only be carried out by authorised personnel The humidifier is fitted with an hour counter that increases during operation After a set number of hours 5000 a signal is activated to indicate maintenance should be performed on the tank and operation of the piezoelectric elements checked see chap Main...

Page 50: ...en display the humidification values see the following paragraph from the list of parameters scroll the parameters and set the values DOWN from the main screen display the humidification values from the list of parameters scroll the parameters and set the values ENTER PRG for 2 seconds access the list of parameters inside the list of parameters select and confirm like Enter on a computer keyboard dra...

Page 51: ...to scroll the list ENTER to select a parameter display set UP to modify increase the value of the parameter To scroll faster press DOWN together DOWN to modify decrease the value of the parameter To scroll faster press UP together ENTER to save the new value and return to the list of parameters or ESC to return to the list without saving the value Press ESC to return to the main screen 8 7 Paramet...

Page 52: ...e proportional band of external signal Y ON OFF P1 P1 P0 Pn Y Atomized water production Fig 9 a Autonomous control with humidity probe Humidity production is controlled based on the reading of the relative humidity probe TH or connection via optional card The humidifier will work at maximum capacity if the humidity measured is less than the set point minus the proportional band while it will modula...

Page 53: ...reshold atomised water production stops The unit waits a number of minutes set in parameter AA default 10 minutes The display shows Rty Retry then the control resumes the production If the situation is repeated alarm EP is activated which shuts down the unit If after a percentage of A8 set by parameter Ab default 70 the water is above the high level threshold atomised water production stops warnin...

Page 54: ... 7 b1 Time between two washing cycles min h 0 120 60 b2 Inactivity time for washing h 1 240 24 b3 Washing time fill drain min 0 10 1 b4 Start delay time s 0 120 10 b5 Operating hours for CL alarm h 0 9999 5000 b6 Time to display new CL alarm after reset from keypad without resetting hour counter min 0 240 60 b7 Transducer modulating control period s 0 10 1 b8 Probe disconnected delay s 0 200 10 b9 ...

Page 55: ...M OFF Open SP NO Off On On 22 M OFF Open SP NO On On Off 23 M OFF Open SP NO On On On 24 M OFF Open SP NC Off Off Off 25 M OFF Open SP NC Off Off On 26 M OFF Open SP NC On Off Off 27 M OFF Open SP NC On Off On 28 M OFF Open SP NC Off On Off 29 M OFF Open SP NC Off On On 30 M OFF Open SP NC On On Off 31 M OFF Open SP NC On On On 32 M OFF Closed AL NO Off Off Off 33 M OFF Closed AL NO Off Off On 34 M OFF Closed AL NO ...

Page 56: ...M ON Closed SP NC Off Off On 122 M ON Closed SP NC On Off Off 123 M ON Closed SP NC On Off On 124 M ON Closed SP NC Off On Off 125 M ON Closed SP NC Off On On 126 M ON Closed SP NC On On Off 127 M ON Closed SP NC On On On 128 H OFF Open AL NO Off Off Off 129 H OFF Open AL NO Off Off On 130 H OFF Open AL NO On Off Off 131 H OFF Open AL NO On Off On 132 H OFF Open AL NO Off On Off 133 H OFF Open AL NO Off On On 134 H O...

Page 57: ... SP NO Off On On 214 H ON Open SP NO On On Off 215 H ON Open SP NO On On On 216 H ON Open SP NC Off Off Off 217 H ON Open SP NC Off Off On 218 H ON Open SP NC On Off Off 219 H ON Open SP NC On Off On 220 H ON Open SP NC Off On Off 221 H ON Open SP NC Off On On 222 H ON Open SP NC On On Off 223 H ON Open SP NC On On On 224 H ON Closed AL NO Off Off Off 225 H ON Closed AL NO Off Off On 226 H ON Closed AL NO On Off Off 2...

Page 58: ...eried by the supervisor of at least 500 ms 11 1 Supervisor variable list A analogue variables Modbus REGISTERS R W CAREL Modbus 1 0 param d0 Th probe temperature reading R 2 1 param d1 Th probe humidity reading R 3 2 param d2 Probe reading R 4 3 param d5 Instant production R 9 8 param d8 Dew point temperature R I integer variables Modbus REGISTERS R W CAREL Modbus 1 128 Level access password R W 7...

Page 59: ...tegrated probe reading R 87 214 Secondary 1 firmware release R 89 216 Secondary 1 humidifier status R 92 219 Parameter d3 secondary 1 Operating hour counter R W 93 220 Secondary 2 firmware release R 95 222 Secondary 2 humidifier status R 98 225 Parameter d3 secondary 2 Operating hour counter R W 99 226 Secondary 3 firmware release R 101 228 Secondary 3 humidifier status R 104 231 Parameter d3 secondary ...

Page 60: ...arameter A0 1 Carel 20 Modbus 148 Proportional Mode Set integer variable 60 Carel 188 Modbus to the desired level 0 1000 0 100 0 To manage the production with a humidity probe managed by the main Set D 37 1 Set parameter A0 2 Carel 20 Modbus 148 Humidity probe Mode Set integer variable 60 Carel 188 Modbus to the desired level 0 1000 0 100 0 rH Set integer variable 52 Carel 180 Modbus to the desire...

Page 61: ... flashes H_ Low humidity The signal from the probe indi cates humidity less than 20 rH Check humidity probe signal cable yes humidification interrupted AUTO 4 slow flashes EE EEPROM alarm Problems in the EEPROM If the problem persists contact the CAREL service centre yes humidification interrupted If this persists contact service 1 fast flash E0 Functional test not performed Functional test not perform...

Page 62: ...nd foreign matter accumulated in the tank Check a view the inside of the tank Scale build up on the surface of the piezoelectric transducers Clean the inside of the tank and replace the transducers Tab 12 b These malfunctions can be avoided by carrying out preventive maintenance 2 If the cause has not been identifi ed with the previous checks there may be faulty components Check the inside of the h...

Page 63: ...ble Kit UU01G UUKWR10010 G Tab 13 a B L A E H D F G Fig 13 a 13 2 Dismantling Maintenance on the humidifier must be carried out by CAREL Technical Service or professionally qualified personnel WARNING electric shock hazard Before carrying out any work the appliance must be disconnected from the mains power supply and must be prevented from being powered on Electrical disconnection must be verified by...

Page 64: ...g and maintenance of other components Using humiSonic with demineralised water transducers last about 10 000 h If it is used another type of water or if the water has impurities and dirt the transducers useful life is reduced proportionally when cleaning plastic parts do not use detergents solvents descaling can be performed using a 20 acetic acid solution followed by rinsing with water To replace...

Page 65: ...river D Driver Control board Drain valve Fill valve LEVEL FLOW SWITCH FAN HIGH LEV LOW LEV 50 Vac 24 Vac L N L N 230 Vac L N Fig 14 a 14 1 Model with 115V power supply GND GND 21V F Level flow switch Fan GND Piezoelectric transducer Pool Driver D Driver Control board Drain valve Fill valve LEVEL FLOW SWITCH FAN HIGH LEV LOW LEV 50 Vac 24 Vac L N L N 115 Vac L N 115 Vac L N Fig 14 b ...

Page 66: ...104 pressure limits MPa 0 1 0 6 1 6 bar specific conductivity at 20 C 3 50 μS cm total hardness 0 25 mg l CaCO3 temporary hardness 0 15 mg l CaCO3 total quantity of dissolved solids cR depending on specific conductivity 1 dry residue at 180 C depending on specific conductivity 1 iron manganese G 1 8 F chlorides 1 40 33 8 104 silicon dioxide 0 1 0 6 1 6 bar chlorine ions 0 50 μS cm calcium sulphate 0 ...

Page 67: ...following fields Percentage request sent to the Main Fig 3 Operating hour counter Fig 4 resettable pressing UP DOWN for 5 seconds see parameter d3 Unit alarms Fig 5 means no alarms are present resettable pressing UP DOWN for 5 seconds humidifier status Enb enabled pressing ENTER disables the humidifier and dIS is shown on the main screen to enable the unit press ENTER again limit probe set point and ...

Page 68: ...s MAIN UNIT Connections M 11 TX RX GND GND 1 RS485 Supervisor ON OFF 4 Main Board Connections SECONDARY UNIT Connections 2 3 6 4 7 5 1 8 ON M9 M 11 M 11 M 11 6 6 6 TLan 2 Supervisor 1 Terminal 3 Active Probe 3 Ext Regulator TH probe HYHU000000 5 4 2 3 6 4 7 5 1 8 ON 2 3 6 4 7 5 1 8 ON 2 3 6 4 7 5 1 8 ON Terminal M 14 M 14 tLan ENG Ultrasound for fancoil 0300059PT rel 1 6 06 10 2020 ...

Page 69: ...dipswitch 1 on the main unit and the backup unit in the OFF position dipswitch 2 or 3 on a backup unit in the ON position request signal also sent to the backup unit parameter b0 configured suitably see chap Configuration parameters table parameter b0 both on the main unit and backup so as to 1 enable the backup function on both 2 activate the alarm relay for active alarms on both NOTICE the connect...

Page 70: ......

Page 71: ......

Page 72: ... INDUSTRIES HQs Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 e mail carel carel com www carel com Agenzia Agency Ultrasound for fancoil 0300059PT rel 1 6 06 10 2020 ...

Reviews: