5. ATOMISED WATER DISTRIBUTION
5.1 Atomised water distributor
NOTICE
:
the atomised water delivery hose, the distributor, the fan conveyor,
the elbow connection and the diffuser are not supplied with the humidifier.
Code
Lenght (mm)
UUKDP02500
250
UUKDP05300
530
UUKDP06100
610
UUKDP08500
850
Requirements:
•
humidifier delivery hose Øext 40mm;
•
make sure the atomised water outlet area is 1100 mm2 (e.g. 22 holes
8 mm in diameter);
•
if the customer has to provide a distributor with different length, it is
important to respect a maximum length of 1m. For greater lengths,
please contact the Service Department Carel;
•
the hose running to the distributor should have a minimum upward
gradient of 2° so that any condensate flows back into the humidifier or
a special condensate drain system;
•
make sure there are no condensate leaks from the water vapour
distributor;
•
position the distributor in such a way that the air is not directed against
nearby objects (minimum distance 10 cm);
•
bends or choking of the hose may cause condensate to form and
decrease humidity delivery;
•
avoid loads that may cause mechanical stress on the humidifier outlet
connector.
Fig. 5.a
Fig. 5.b
5.2 Accessories
Fan conveyor
Fig. 5.c
The air flow conveyor UUKCY00000 can be installed on the top of the fan
(removing the protection grill) so as to take in air from a different place to
where humiSonic is installed.
Elbow connector
Fig. 5.d
The elbow connector UUKHS00000 can be installed on the cover and/or the
fan conveyor, so as to reduce the overall height occupied by the product.
Diffuser
Fig. 5.e
The diffuser UUKDF00000 can be installed on the cover, so as to deliver
atomised water directly into the room.
Filter: 50 micron
Fig. 5.f
A filter UUKFL00000 is available to be installed on the fan, using the conveyor
(with or without the elbow). The filter is delivered disassembled (cap not
fixed) because on one side it is possible to mount it on the conveyor, on the
other side on the elbow (to mount with a slight interference). Once mounted,
insert the cap. It’s necessary to clean the filter (with compressed air or running
water) periodically: frequency depends on the environment in which the
system is installed.
Features filter: 50 micron, H = 13 cm, D = 5 cm
Hose (cod. UUKPE00100)