6
+050001570 - 1.2 - 22.06.11
ENG
2.6 Analogue inputs
analogue conversion
10 bit A/D converter in the CPU
maximum number
7, 12 on the small, medium boards respectively
type
B1, B2, B3, B4, B8, B9
low temperature NTC: 10 kΩ ± 0.1% at 25 °C, -50T90 °C;
high temperature NTC: 50 kΩ at 25 °C, 0T150 °C;
0 to 1 V input;
B5, B10
low temperature NTC: 10 kΩ at 25 °C, -50T90 °C;
high temperature NTC: 50 kΩ at 25 °C, 0T150 °C;
0 to 1 V input;
4 to 20 mA input;
B6, B7, B11, B12
low temperature NTC: 10 kΩ at 25 °C, -50T90 °C;
high temperature NTC: 50 kΩ at 25 °C, 0T150 °C;
0 to 1 V input;
ratiometric pressure sensor (0 to 5 V);
constant time for each input
0.5 s
input precision
±0.3% of full scale
classifi cation of the measuring circuits (CEI EN 61010-1) Category I
Tab. 2.c
Note:
the Vdc available at the +Vdc terminal can be used to power any active probes.
The voltage dipends on the model:
+26Vdc +-15% per UPCA****** (230Vac)
+21Vdc +-5% per UPCB****** (24Vac/Vdc).
The maximum current is 150 mA, thermally protected against short-circuits. To supply the ratiometric
0 to 5 V probes, use the +5VREF (Imax: 60 mA).
2.7 Digital outputs
Insulation distance
Note:
the relays in the same group with basic insulation must have the same power
supply.
Makeup of groups
Version Group1
Group 2
Group 3
SMALL
1 to 6
7
MEDIUM
1 to 6
7
8 to 12
Note:
the relays in the game group have basic insulation between them; relays between
groups (group1, group2, group3) have double insulation
Switchable power
Small
relay from 1 to 7
EN60730-1: NO 1(1)A 250 Vac cos phi = 0.4; 100.000 cycles
UL-873: NO 1A resistive load 24 Vac, 30 Vdc, 100,000 cycles/
PILOT DUTY: 24 Vac, pulse 15 A, continuous 1A 30,000 cycles
Medium
relay from 1 to 12
EN60730-1: NO 1(1)A 250 Vac cos phi = 0,4; 100.000 cycles
UL-873: NO 1A resistive load 24 Vac, 30 Vdc, 100,000 cycles/
PILOT DUTY: 24 Vac, pulse 15 A, continuous 1A 30,000 cycles
SSR outputs
Output 7:
working voltage, 24 Vac/Vdc;
maximum power, 10 W, resistive load (where applicable)
Output 12:
working voltage, 110/230 Vac/Vdc;
maximum power, 10 W, resistive load (where applicable)
Tab. 2.d