ENG
“Power+” +0300050EN - rel. 2.3 - 08.06.2012
17
3.13 DC choke
The DC choke is an optional that can be supplied separately to be used with
the Power+ drives with three-phase power supply (PSD00**4*0) to reduce
the harmonic currents to the levels envisioned by EN61000-3-12.
The choke has four holes for fi xing to the wall.
G
A
B
C
D
F
E
Fig. 3.z
Dimensions (mm)
Weight
(kg)
DC choke code
A
B
C
D
E
F
G (diam)
PSACH10000
PSACH10100
86
96
98
94
84
71
5
2,7
Attention:
• Position the choke as near as possible to the drive in a way to minimise
connection cable length (max 2m).
• For connection to the drive use cables with section at least equal to the
power supply cable.
• Envision the space necessary for connection of the cables to the choke
terminals.
3.14 EMI fi lter
The EMI fi lter is an optional that can be supplied separately to be used with
Power + drives with single-phase power supply (PSD00**2*0) to reduce the
emissions to the levels envisioned by EN61800-3 category C1.
The fi lter must be connected between the power supply and terminals L1/L,
L2/N and earth of the drive.
Fig. 3.aa
Dimensions (mm)
Weight
(kg)
EMI fi lter code
L1
L2
L3
B1
B2
B3
H
D
PSARF10000
(CNW102.1/30)
180
150
90
98
88
70
70
5
1,3
Technical specifi cations
Current
30A
Leakage current
< 3,5mA
Voltage
250V
Connection by terminal
4mm
2
Temperature
60°C
Attention:
• Connect power supply cable and drive as shown on the label.
• Position the fi lter as near as possible to the drive in a way to minimise
connection cable length.
• Connect the fi lter metal casing to earth.
Summary of Contents for Power+
Page 2: ......
Page 4: ......
Page 6: ...ENG Power 0300050EN rel 2 3 08 06 2012 6 ...
Page 35: ......