Carel srl: pCO Stage Controller
page 35
Chiller unit consisting of:
•
2 compressors
•
2 temperature active probes:
•
2 stages of voltage control for comp.
(chiller water input/output)
•
setpoint regulation from analog input
ID11R
ID11
ID12R
ID12
J21
G
G0
J17
NO11
C11
NO10
C10
J22
NO9
C9
NO8
C8
NC7
C7
J24
NO6
C6
NO12
C12
NO5
C5
J6
NO4
C4
NO3
C3
NO2
C2
NO1
C1
J5
ID1
ID2
ID3
ID4
J4
ID5
IDCM1
ID6
ID7
ID8
ID9
J3
ID10
IDCM2
B1
AVSS
B2
B3
J2
AVSS
B4
B5
AVSS
B6
BCP1
24V~
BCP2
220V~
FLX
AF
24V~
CMP2
CMP1
AL
F
N
F
N
K
K
P1C2
P1C1
PST
P2C1
P2C2
M
OUT
+V
M
OUT
+V
J1
+24V
TAP
TAP
POWER SUPPLY
ANALOG INPUTS
DIGITAL OUTPUTS
DIGITAL INPUTS
INPUTS
OUTPUTS
AF
antifreeze lock
AL
general alarm
BCP
compressor lock device
CINV
compressor 1 / valve inverter
FLX
flow switch
CMP
compressor
PST
potentiometer for setpoint regulation
P1C
first stage of voltage control
TAP
temperature active probes (IN/OUT)
P2C
second stage of voltage control
F
phase
N
neuter
Note: Fans must be electromechanically controlled by means of a contact by the contactor of the relative
compressor, or they must be controlled through an external pressure switch.
APPENDIX D: MATERIALS AND CODES
pCO kit Universal Inserter:
PCOKITSTG0
The kit includes:
Interface 8 screw fixed analog input connectors
PCOB000B21
Terminal pCO 6 digit LED
PCOT01SL60
Telephone connector 1.5m long
S90CONN000
Clock board
CLK0000000
EPROM with programme
EPSTDIIU0A
Optional:
Serial board
PCOSER0000
Serial board
PCOSER4850
Carel reserves the right to modify its products without prior notice.