Parameter
Type Pos. Display Description
UOM Range Default
Notes
Min. time between
stops of different
compressors :
R/W C
C04 Minimum time between two stop calls for compressors.
s
0 to 999
20
Min. time between
starts of same
compressor :
R/W C
C05 Minimum time between two effective starts of the same compressor
s
0 to 999
360
Time between
compressor OFF call
with prevent active
R/W C
C06 Time between compressor stop call with high pressure prevention active.
s
0 to 999
30
Only if prevent
active
Compressor operating
hour threshold for
maintenance alarm
R/W I C07
Compressor operating hour threshold for maintenance alarm. If set to
0, no maintenance alarms.
h X 10 0 to 999
200
This means 2000
hours
Compressor 1 operating
hours
R
I
C08 Display compressor 1 operating hours
h X 10 0 to 999
0
RESET Compressor 1
operating hours
R/W I C09
Reset comp.1 operating hours
0) NO RESET
1) RESET
0 / 1
0
Compressor 2 operating
hours
R
I
C10 Display compressor 2 operating hours
h X 10 0 to 999
0
RESET Compressor 2
operating hours
R/W I C11
Reset comp.2 operating hours
0) NO RESET
1) RESET
0 / 1
0
Compressor 3 operating
hours
R
I
C12 Display compressor 3 operating hours
h X 10 0 to 999
0
RESET Compressor 3
operating hours
R/W I C13
Reset comp.3 operating hours
0) NO RESET
1) RESET
0 / 1
0
Compressor 4 operating
hours
R
I
C14 Display compressor 4 operating hours
h X 10 0 to 999
0
RESET Compressor 4
operating hours
R/W I C15
Reset comp.4 operating hours
0) NO RESET
1) RESET
0 / 1
0
Compressor set point 2:
Offset
R/W I C16
Auxiliary compressor set point offset. Used when changing the set
point from digital input.
bar
-99.9 to
99.9
0
Control menu
Compressor set point
circuit 1
R/W U
r01 Compressor set point first circuit
bar / °C
min to max
comp. set
1.0
Compressor differential
circuit 1
R/W U
r02 compressor differential first circuit
bar /°C 0 to 20.0
0.5
Compressor set point
circuit 2
R/W U
r03 Compressor set point second circuit
bar / °C
min to max
comp. set
1.0
For two circuits
only
Compressor differential
circuit 2
R/W U
r04 compressor differential second circuit
bar /°C 0 to 20.0
0.5
For two circuits
only
Comp. rotation
R/W C
r05 Type of compressor rotation
0 = LIFO
1 = FIFO
2 = Time
1
Compressor control:
R/W C r06
Type of compressor control:
0) Proportional,
1) Dead band.
2) Dead band with time
0 / 2
1
Min call time start in
dead band
R/W
I
r07 Set minimum call time for compressor starts in dead band
s
0 to 999
20
Only if dead band
control is enabled
Max call time start in
dead band
R/W
I
r08 Set maximum call time for compressor starts in dead band
s
0 to 999
60
Only if dead band
control is enabled
Min call time stop in
dead band
R/W
I
r09 Set minimum call time for compressor stops in dead band
s
0 to 999
10
Only if dead band
control is enabled
Max call time stop in
dead band
R/W
I
r10 Set maximum call time for compressor stops in dead band
s
0 to 999
60
Only if dead band
control is enabled
Dead band diff.
pressure in which the
time varies
R/W I r11
Pressure differential in which the compressor start/stop time is
proportional to the suction pressure
bar 0 to 20.0
0.5
Only if dead band
control is enabled
Min compressor set
point
R/W C
r12 Set the lower limit of the compressor set point circuit 1
bar 0 to r14
0.1