1.3 Plumbing
1.3.1 Water supply
The HumiSteam must be supplied with water (not softened)
having the following characteristics:
The water feed line should be ½” copper, PVC or poly tubing
run to within 3 feet of the humidifier, then bushed down to ¼”
O.D. copper or poly to make the final connection to the ¼”
O.D. compression fitting underneath the humidifier. With poly tubing an insert should be used to support the
tubing and prevent leaks. This insert is not provided.
SUPPLY WATER LIMIT VALUES FOR THE
MEDIUM-LOW
MEDIUM-HIGH
IMMERSED ELECTRODE HUMIDIFIERS
CONDUCTIVITY
CONDUCTIVITY
MINIMUM MAXIMUM MINIMUM MAXIMUM
Specific conductivity at 20°C
σ
20
µS/cm
125
550
300 1250
Total dissolved solids
TDS
mg/l
116 (1)
512 (1)
279 (1)
1163 (1)
Dry residue at 180°C
R
180
mg/l
81 (1)
358 (1)
195 (1)
813 (1)
Hydrogen ion activity
pH
7
8.5
7
8.5
Total hardness
TH mg/l CaCO
3
50 (2)
250
100 (2)
400
Temporary hardness
mg/l CaCO
3
30 (3)
150
60 (3)
300
Chlorides
ppm Cl
=
20
=
30
Iron + Manganese
mg/l Fe+Mn
=
0.2
=
0.2
Silica
mg/l SiO
2
=
20
=
20
Residual chlorine
mg/l Cl
-
=
0.2
=
0.2
Calcium sulphate
mg/l CaSO
4
=
60
=
100
Metal impurities
mg/l
0
0
0
0
Solvents, thinners, detergents, lubricants
mg/l
0
0
0
0
(1) Values depend on the specific conductivity; in general: TDS @0.93 * s20 ; R180 @0.65 * s20
(2) No less than 200% of the chloride content in mg/l Cl-
(3) No less than 300% of the chloride content in mg/l
NOTE: Softened water should NOT be used as it is generally corrossive to the electrode plating.
UE003, UE005
Instant flow rate
0.2 gpm
Connection
1/4" O.D. Compression
Temperature limits
34 to 104°F
Pressure limits
15 to 116 psi
Hardness limits
<= 400 ppm CaCO3
Conductivity range
125 to 1250
µS
/cm (micromhos)