Direct version for room applic. +0300062EE - rel. 1.4 - 24.09.2020
11.1 Troubleshooting
NO
TICE:
if the problem identified cannot be solved using the following
guide, contact CAREL technical service.
1. Firstly, check the humidifier and the surrounding area.
Problem
Cause
Verification
Solution
No atomised water
production
Power supply
Humidifier switch in the OFF position
Check the switch
Switch ON
No power
Measure the voltage at the
humidifier input terminals
Connect power
Power supply fault
Measure the voltage at the power
supply output terminals
Replace the power supply
Feedwater system
Valve closed upstream
Check
Open the valve
The quantity of atomised
water is too low
Power supply
Low power supply voltage
Check the voltage at the power
supply output terminals
Replace the power supply, if
damaged
Feedwater system
Water level during production is too
high and overflowing
Check visually
See the following table
Other
The humidifier is not installed
horizontally
Check visually
Adjust
No atomised water
production
Dust and foreign matter accumulated in the tank (*)
Clean the inside of the tank
Transducer deterioration
The average life of the transducer is
around 10,000 to 15,000 operating
hours
Replace
The quantity of atomised
water is too low
Dust and foreign matter accumulated in the tank (*)
Visually check the inside of the tank
Clean the inside of the tank
and replace the transducers
Scale build-up on the surface of the piezoelectric transducers (*)
Tab. 11.b
(*) These malfunctions can be avoided by carrying out preventive
maintenance.
2. If the cause has not been identified with the previous checks, there
may be faulty components. Check the inside of the humidifier.
Problem
Cause
Verification
Solution
No atomised water
production
Feedwater system
Float level sensor fault
Empty the tank, remove the
electronic board and check
continuity of the level sensor
Contact service to replace the level
sensor
Float level sensor blocked
Clean the sensor. If normal
operation is not restored, replace
Fill valve fault
No water filled even when the tank
has been emptied
Replace the valve
Clean the sensor. If normal
operation is not restored, replace
Other
The fan cables are loose or
detached
Check connection after removing
the humidifier cover
Restore correct connection to the
terminals
The quantity of atomised
water is too low
Water level overflow
Float level sensor blocked
If the water level in the tank
reaches the overflow pipe, remove
the connector from the control
board and check continuity of the
level sensor
If there is continuity, contact service
to replace the level sensor
Fill valve fault
Water is filled even after switching
off the appliance
Replace the fill valve
Tab. 11.c