19
ENG
Direct version for room applic. +0300062EE - rel. 1.4 - 24.09.2020
9. CONFIGURATION PARAMETERS
To access and set the following parameters, see chapters 7 and 10.
9.1 Basic
parameters
Parameter
UoM
R
ange
def
note
A0 Operating mode
0 = On/Off mode from auxiliary card probe input
1 = Proportional mode from auxiliary probe input
2 = Humidity probe mode from auxiliary card probe input
3 = AUTO mode: if fitted, humidity probe TH reading is used, otherwise On/Off mode from contact on main
board. Parameter A2 is not used
4 = Dew point control mode by reading the temperature and humidity probe TH
-
0 to 4
3
A1 Unit of measure 0 = International system; 1 = Imperial system
-
0-1
0
A2 Type of external sensor (auxiliary card) (0 = On/Off; 1 = 0-10V; 2 = 2-10V; 3 = 0-20 mA; 4 = 4-20 mA)
-
0 to 4
1
P0
Maximum production
%
Pn...100
100
P1
Proportional control hysteresis for mode A0=1
%
2 to 20
2
Pn Minimum production
%
5...P0
10
SP
Humidity (1) / dew point set point
%rH
20 to 80
50
only if terminal connected,
otherwise values set by
dipswitch
°C
(°F)
-16 to 35
(3 to 95)
10
(50)
only editable on the terminal
SL
Humidity / dew point limit set point
%rH
0 to 80
70
°C
(°F)
-16 to 35
(3 to 95)
15
(59)
bP Proportional band for control with probe
%rH
2 to 20
10
°C
(°F)
1 to 10 (2
to 20)
3
(5)
bL Proportional band for humidity / dew point limit
%rH
2 to 20
10
°C
(°F)
1 to 10 (2
to 20)
3
(5)
C0 Default display (terminal) 0 = Probe reading/control signal; 1 = Hour counter
-
0-1
0
Tab. 9.a
9.2 Service
parameters
Parameter
UoM
range
def
note
A3
Probe minimum
%rH
0 to 100
0
A4
Probe maximum
%rH
0 to 100
100
A5
Probe offset
%rH
-99 to 100
0
A6
Fan off delay time
min
0 to 15
5
A7
Fan speed
%
40 to 100
50
A8
Maximum evaporation time for reduced production alarm
min
0 to 200
30
A9
Minimum evaporation time for reduced production alarm
min
0 to A8
1
AA
Waiting time for retry
min
1 to 60
10
Ab
Percentage of A8 to carry out level test
%
50 to 90
70
AC
Maximum time to measure level when refilling
s
1 to 240
40 (UU02) - 60 (UU04) -
80 (UU06) - 100 (UU08)
Ad
Maximum time to measure high level
s
1 to 60
10
AE
Restart fan time in standby for built-in probe reading
min
0 to 120
10(**)
AF
Piezoelectric transducer working life
h
0 to 9999
9999
with demineralised water
b0
Operating options (see table for parameter b0)
-
0 to 255
135
b1
Time between two washing cycles
min/h
0 to 120
12
b2
Inactivity time for washing
h
1 to 240
24
b3
Washing time (fill + drain)
min
0 to 10
1
b4
Start delay time
s
0 to 120
10
b5
Operating hours for CL alarm
h
0 to 9999(*)
5000
b6
Time to display new CL alarm after reset from keypad (without resetting hour counter)
min
0 to 240
60
b7
Transducer modulating control period
s
0 to 10
1
b8
Probe disconnected delay
s
0 to 200
30
b9
Reserved
s
0 to 60
2
bA
Maximum fill time
min
0 to 30
6 (UU02) - 9 (UU04) -
12 (UU06) - 15 (UU08)
bb
Water refill time in production
s
0 to 120
20 (UU02) - 28 (UU04) -
40 (UU06) - 52 (UU08)
bC
Maximum drain time
s
0 to 1500
75 (UU02) - 100 (UU04) -
150 (UU06) - 200 (UU08)
bd
Drain opening time to completely empty tank
s
0 to 1500
60 (UU02) - 80 (UU04) -
120 (UU06) - 160 (UU08)
bE
Delay time after measuring low level for refilling
s
1 to 20
10
bF
Drain activation delay in standby (if drain solenoid valve in standby = OPEN)
h
0 to 48
1
bH
Enable TH probe as humidity limit (bH=1) or as dew point limit (bH=2)
-
0 to 2
0
can be set to 1 or 2 only in
modes A0 = 0, 1, 2
bL
Proportional band for humidity / dew point limit
%rH
2 to 20
10
°C
(°F)
1 to 10 (2
to 20)
3
(5)
bn
Disable alarm buzzer 0 = enabled; 1 = disabled
-
0 to 1
0
bP
Proportional band for control with probe
%rH
2 to 20
10
°C
(°F)
1 to 10 (2
to 20)
3
(5)
P1
Proportional control hysteresis for mode A0=1
%
2 to 20
2
P2
Low humidity alarm threshold
%rH
0 to 100
20
P3
High humidity alarm threshold
%rH
0 to 100
80
Tab. 9.b
(1)
To be able to modify the value on the terminal, the corresponding dipswitches must all be Off. To be able to use the value set by the dipswitches again, set one of the dipswitches to On
and power off. When powering on again, the controller will use the values set by the dipswitches.
(*)
after 999 the display shows
to indicate the 1000s (the three digits are displayed with a dot at the top between the first and second digit).
(**)
the default is 0 (zero), for humidifiers without auxiliary card and without humidity/temperature probe.