Direct version for room applic. +0300062IE - rel. 1.1 - 16.11.2017
8. HUMIDIFIER CONTROL VIA NETWORK
The variables shown in the list are a set of all the internal variables.
DO
NOT CONFIGURE ANY VARIABLES THAT ARE NOT SHOWN IN THE TABLE,
OTHERWISE HUMIDIFIER OPERATION MAY BE AFFECTED.
The serial connection (M11) is configured by default with the following
parameters:
- Address 1
- Baud rate 19200 bps
- Frame 8,N,2
8.1 Supervisor variable list
“A”
analogue variables* (Modbus®: REGISTERS)
R/W
CAREL - Modbus®
1
param. d0: Th probe temperature reading
R
2
param. d1: Th probe humidity reading
R
3
param. d2: Probe reading
R
4
param. d5: Instant production
R
“I”
integer variables (Modbus®: REGISTERS)
R/W
CAREL
Modbus®
1
128
Level access password
R/W
2
129
Firmware release
R
15
142
Alarms, refer to Chap.8 ALARMS:
•
bit0: Alarm E0
•
bit1: Alarm Et
•
bit2: Alarm EF
•
bit3: Alarm Ed
•
bit4: Alarm EP
•
bit5: Alarm PU
•
bit6: Alarm H ¯
•
bit7: Alarm H_
•
bit8: Alarm EE
•
bit9: Alarm CL
R/W
20
147
Parameter A0: Operating mode
R/W
21
148
Parameter A2: Type of external probe
R/W
22
149
Parameter A3: Probe minimum
R/W
23
150
Parameter A4: Probe maximum
R/W
24
151
Parameter A5: Probe offset
R/W
25
152
Parameter A6: Fan off delay time
R/W
26
153
Parameter A7: Fan speed
R/W
27
154
Parameter A8: Maximum evaporation time for no production alarm
R/W
28
155
Parameter A9: Minimum evaporation time for no production alarm
R/W
29
156
Parameter b0: Operating options
R/W
30
157
Parameter b1: Time between two washing cycles
R/W
31
158
Parameter b2: Inactivity time for washing on next start
R/W
32
159
Parameter b3: Washing time (fill + drain)
R/W
33
160
Parameter b4: Start delay time
R/W
34
161
Parameter b5: Operating hours for CL alarm
R/W
35
162
Parameter b6: Time to display new CL alarm in minutes
R/W
36
163
Parameter b7: Transducer On/Off control interval
R/W
37
164
Parameter b8: Probe delay disconnected
R/W
38
165
Parameter b9 TAM OFF delay
R/W
39
166
Parameter bA: Maximum fill time
R/W
40
167
Parameter bb: Refill time in evaporation
R/W
41
168
Parameter bC: Maximum drain time
R/W
42
169
Parameter bd: Drain opening time to completely empty tank
R/W
43
170
Parameter bE: Delay time after measuring low level for refilling
R/W
44
171
Parameter C0: Default display (Terminal)
R/W
45
172
Parameter C1: Parameter A0: Baud rate
R/W
46
173
Parameter C2: tLAN address (If 0 Master controller)
R/W
47
174
Parameter C3: Serial address
R/W
48
175
Parameter P0: Maximum flow-rate
R/W
49
176
Parameter P1: Humidity control hysteresis
R/W
50
177
Parameter P2: Low humidity alarm threshold
R/W
51
178
Parameter P3: High humidity alarm threshold
R/W
52
179
Parameter SP: Humidity set point
R/W
53
180
Parameter d3: Operating hour counter
R
54
181
Parameter d4: Unit hour counter (not resettable)
R/W
60
187
Request via serial (if digital 37 set)
R/W
62
189
Identification of variable on slave unit to read/write from supervisor (see paragraph 14.4)
R/W
63
190
Value of variable on slave unit identified by integer 62 (see paragraph 14.4)
R/W
65
192
Parameter C4: Timeout for master serial offline
R/W
69
196
AA: Waiting time for retry
R/W
Summary of Contents for humiSonic UU02
Page 2: ......
Page 4: ......
Page 6: ...6 ITA Direct version for room applic 0300062IE rel 1 1 16 11 2017 ...
Page 34: ...34 ITA Direct version for room applic 0300062IE rel 1 1 16 11 2017 Note ...
Page 36: ......
Page 38: ...6 ENG Direct version for room applic 0300062IE rel 1 1 16 11 2017 ...
Page 66: ...34 ENG Direct version for room applic 0300062IE rel 1 1 16 11 2017 Notes ...
Page 67: ......