18
ENG
Direct version for room applic. +0300062IE - rel. 1.1 - 16.11.2017
Setting the value of parameter b0 in the range from 0 to 255 (default
7) changes the humidifier operating options as regards the following
preferences:
1.
Unit of measure of parameter b1 (time between two periodical
washing cycles): M = minutes; H = hours;
2.
Backup: ON = if two humiSonic units are connected together in
master/slave mode (see chapter “Network connection”), the slave
becomes the backup unit for the master, i.e. it starts production only
if the master has shut down due to an alarm; OFF = backup function
disabled;
3.
Position of the drain solenoid valve in standby: OPEN = standby
empty, the NO valve is not powered and the humidifier tank is
emptied; CLOSED = standby full, the NO valve remains powered,
keeping the humidifier tank full during standby;
4.
Alarm relay activation: AL = signals alarms are present; SP = signals
the set point has been reached;
5.
Alarm relay operating logic: NO = normally open; NC = normally
closed;
6.
Enable washing due to inactivity: ON/OFF;
7.
Washing due to inactivity: ON = the humidifier performs the washing
cycle regularly when the time between two washing cycles due to
inactivity expires (parameter b2); OFF = the humidifier performs the
washing cycle before starting production (the time b2 must have
already elapsed);
8.
Enable autotest when starting from unit off: ON/OFF.
Note
: if connecting to a reverse osmosis system, it is recommended
to leave preferences 6 and 7 ON.
b0
1.
Unit of
measure of
parameter b1
M = minutes;
H = hours
2. Enable backup function
(only for units with network
connection)
3.
Drain solenoid
valve in standby
4.
Alarm relay activation AL=
alarms present
SP= set point reached
5.
Alarm relay logic
NO= norm. open
NC= norm. closed
6.
Enable wash due
to inactivity
7.
Off = wash due to
inactivity at next start
On= standard wash due to
inactivity
8.
Auto- test
0
M
OFF
Open
AL
NO
Off
Off
Off
1
M
OFF
Open
AL
NO
Off
Off
On
2
M
OFF
Open
AL
NO
On
Off
Off
3
M
OFF
Open
AL
NO
On
Off
On
4
M
OFF
Open
AL
NO
Off
On
Off
5
M
OFF
Open
AL
NO
Off
On
On
6
M
OFF
Open
AL
NO
On
On
Off
7
M
OFF
Open
AL
NO
On
On
On
8
M
OFF
Open
AL
NC
Off
Off
Off
9
M
OFF
Open
AL
NC
Off
Off
On
10
M
OFF
Open
AL
NC
On
Off
Off
11
M
OFF
Open
AL
NC
On
Off
On
12
M
OFF
Open
AL
NC
Off
On
Off
13
M
OFF
Open
AL
NC
Off
On
On
14
M
OFF
Open
AL
NC
On
On
Off
15
M
OFF
Open
AL
NC
On
On
On
16
M
OFF
Open
SP
NO
Off
Off
Off
17
M
OFF
Open
SP
NO
Off
Off
On
18
M
OFF
Open
SP
NO
On
Off
Off
19
M
OFF
Open
SP
NO
On
Off
On
20
M
OFF
Open
SP
NO
Off
On
Off
21
M
OFF
Open
SP
NO
Off
On
On
22
M
OFF
Open
SP
NO
On
On
Off
23
M
OFF
Open
SP
NO
On
On
On
24
M
OFF
Open
SP
NC
Off
Off
Off
25
M
OFF
Open
SP
NC
Off
Off
On
26
M
OFF
Open
SP
NC
On
Off
Off
27
M
OFF
Open
SP
NC
On
Off
On
28
M
OFF
Open
SP
NC
Off
On
Off
29
M
OFF
Open
SP
NC
Off
On
On
30
M
OFF
Open
SP
NC
On
On
Off
31
M
OFF
Open
SP
NC
On
On
On
32
M
OFF
Closed
AL
NO
Off
Off
Off
33
M
OFF
Closed
AL
NO
Off
Off
On
34
M
OFF
Closed
AL
NO
On
Off
Off
35
M
OFF
Closed
AL
NO
On
Off
On
36
M
OFF
Closed
AL
NO
Off
On
Off
37
M
OFF
Closed
AL
NO
Off
On
On
38
M
OFF
Closed
AL
NO
On
On
Off
39
M
OFF
Closed
AL
NO
On
On
On
40
M
OFF
Closed
AL
NC
Off
Off
Off
41
M
OFF
Closed
AL
NC
Off
Off
On
42
M
OFF
Closed
AL
NC
On
Off
Off
43
M
OFF
Closed
AL
NC
On
Off
On
44
M
OFF
Closed
AL
NC
Off
On
Off
45
M
OFF
Closed
AL
NC
Off
On
On
46
M
OFF
Closed
AL
NC
On
On
Off
47
M
OFF
Closed
AL
NC
On
On
On
48
M
OFF
Closed
SP
NO
Off
Off
Off
49
M
OFF
Closed
SP
NO
Off
Off
On
50
M
OFF
Closed
SP
NO
On
Off
Off
51
M
OFF
Closed
SP
NO
On
Off
On
52
M
OFF
Closed
SP
NO
Off
On
Off
53
M
OFF
Closed
SP
NO
Off
On
On
54
M
OFF
Closed
SP
NO
On
On
Off
55
M
OFF
Closed
SP
NO
On
On
On
56
M
OFF
Closed
SP
NC
Off
Off
Off
57
M
OFF
Closed
SP
NC
Off
Off
On
58
M
OFF
Closed
SP
NC
On
Off
Off
59
M
OFF
Closed
SP
NC
On
Off
On
60
M
OFF
Closed
SP
NC
Off
On
Off
61
M
OFF
Closed
SP
NC
Off
On
On
62
M
OFF
Closed
SP
NC
On
On
Off
63
M
OFF
Closed
SP
NC
On
On
On
64
M
ON
Open
AL
NO
Off
Off
Off
65
M
ON
Open
AL
NO
Off
Off
On
66
M
ON
Open
AL
NO
On
Off
Off
67
M
ON
Open
AL
NO
On
Off
On
68
M
ON
Open
AL
NO
Off
On
Off
69
M
ON
Open
AL
NO
Off
On
On
70
M
ON
Open
AL
NO
On
On
Off
71
M
ON
Open
AL
NO
On
On
On
72
M
ON
Open
AL
NC
Off
Off
Off
73
M
ON
Open
AL
NC
Off
Off
On
74
M
ON
Open
AL
NC
On
Off
Off
75
M
ON
Open
AL
NC
On
Off
On
76
M
ON
Open
AL
NC
Off
On
Off
77
M
ON
Open
AL
NC
Off
On
On
78
M
ON
Open
AL
NC
On
On
Off
79
M
ON
Open
AL
NC
On
On
On
80
M
ON
Open
SP
NO
Off
Off
Off
81
M
ON
Open
SP
NO
Off
Off
On
Summary of Contents for humiSonic UU02
Page 2: ......
Page 4: ......
Page 6: ...6 ITA Direct version for room applic 0300062IE rel 1 1 16 11 2017 ...
Page 34: ...34 ITA Direct version for room applic 0300062IE rel 1 1 16 11 2017 Note ...
Page 36: ......
Page 38: ...6 ENG Direct version for room applic 0300062IE rel 1 1 16 11 2017 ...
Page 66: ...34 ENG Direct version for room applic 0300062IE rel 1 1 16 11 2017 Notes ...
Page 67: ......