KRPH6WHDP
cod. carel +030221900 rel. 2.0 dated 05/03/01
41
6HTXHQFHRI/('IODVKHVRQVWDUWXS
The green LED remains on for the entire time the machine is on, irrespective of the operating status.
The flashing sequence consists of the following operations:
1. power connected: the yellow and red LEDs remain off for 1 second;
2. initialisation: the yellow and red LEDs flash a number of times to indicate the version of the program that the board is
configured with; this occurs once each time the machine is started;
a.
first the yellow LED - the number of flashes indicates the tens (0=no flash);
b.
then the red LED - the number of flashes indicates the units (0=no flash);
H[DPSOH
version 1.1: 1 flash of the yellow LED, then 1 flash of the red LED;
c.
once the sequence of flashes corresponding to the unit is completed, the LEDs are turned of for 3 seconds, then
remain off for 3 seconds and, finally, the normal operational behaviour starts.
3. operation: the humidifier starts operation; the yellow LED indicates that production is in progress, as shown by the
following table:
\HOORZ/('
SURGXFWLRQ
off 0%
1 flash
1% to 19%
2 flashes
20% to 29%
3 flashes
30% to 39%
... ...
9 flashes
90% to 99%
always on
100%
7DE
5HPDUN
: the transient production is signalled by short flashes: on and off twice in 1 second; each sequence of flashes repeats
continuously and, between one sequence and the next one, the yellow LED stays off for 3 seconds
,QGLFDWLRQRIDQDODUPVWDWXV
In the event an anomaly or alarm, the red LED starts to flash. The signal is composed of a sequence of the flashes followed
by a pause. See
$/$5067528%/(6+227,1*
.
$GMXVWPHQWDFFRUGLQJWRDPELHQWKXPLGLW\
The level of humidity in an environment can be controlled using a special ON/OFF regulator (humidistat). This device has
the task of measuring the level of ambient humidity, comparing it against a settable reference value and requesting, when
necessary, the start of steam production by closing an electrical contact connected to the machine, as described in
$X[LOLDU\FRQQHFWLRQV
.
When the humidity measured reaches the reference value, the humidistat will stop production.
6KXWGRZQ
During seasonal shut-down or alternatively shut-down for maintenance of the electrical and/or hydraulic parts, the
humidifier should be placed out-of-service.
1%5(0(0%(572(037<7+(&</,1'(5%()25($1<
/21*7(506+872))72$92,'7+(&25526,212)7+(
(/(&752'(6
Follow the instructions below:
•
open the rocker switch located in the lower right of the frame of the structure,
by placing it position
(see Figs. 6.2.1.2 and 6.4.1) and checking that the green
led is off;
•
open the main power switch to the humidifier;
•
close the water shut-off tap to the humidifier.
If during a shut-down
WKHF\OLQGHUQHHGVWREHHPSWLHG
, before disconnecting
power from the unit press the drain button (see Fig. 6.2.1.1) to open the drain
electrovalve, and hold it manually in this position until the water has been
completely emptied.
In the event of malfunction of the drain electrovalve, the cylinder can be emptied manually by removing it from the
manifold connection and slowly pouring the water into the bottom collection tank.
OFF
)LJ