&KDUDFWHULVWLFVRIWKHGUDLQZDWHU
Inside the humidifier the water boils and is transformed into steam, without the addition of any substances. The drain water,
as a result, contains the same substances that are dissolved in the supply water, yet in greater quantities, depending on the
concentration in the supply water and the set draining cycles, and
PD\UHDFKWHPSHUDWXUHVRI&DQGDQLQVWDQWIORZ
UDWHRIOPLQ
; not being toxic, it may be drained into the sewage system. The drain connection has an external diameter of
40 mm. As well as resisting to high temperatures (100°C min.), the drain must guarantee the correct downflow of water, and
as a result a downwards slope of at least 5° is recommended.
7XELQJFRQQHFWLRQV
The installation of the humidifier requires connection to the water supply and drain tubing.
With reference to Fig. 3.3.1, which represents the lower
view of the base of the machine, the supply water may be
connected using a rigid or flexible pipe with a minimum
recommended internal diameter of 6 mm. This must be
fitted with a shut-off tap to allow the appliance to be
disconnected during maintenance operations.
To simplify installation, it is recommended to use Carel
flexible tubing with an internal diameter of 6 mm and an
external diameter of 8 mm (code 1312350APN) and the
¾G revolving fitting, either straight (code 9995727ACA)
or elbow (code 9995728ACA), available on request.
$PHFKDQLFDOILOWHUVKRXOGEHLQVWDOOHGWRWUDSDQ\VROLG
LPSXULWLHV
The drain water is connected using a section of rubber or
plastic tubing resistant to 100°C, with a recommended
internal diameter of 36 mm.
This section of tubing must be fastened using metal pipe
clamps:
•
above, to the outlet of the appliance;
•
below, onto the rigid tubing, so as to create a minimum
slope of 5°.
)LJ
water supply fitting
drain fitting