FLSTDMFC0A pCO² refrigeration system
cod. Carel +030221991 rel. 1.0 dated 27/07/01
44
J20-
B9
passive analogue input 9 (NTC, PT1000, ON/OFF)
Thermal overload Klixon fan 1
J20-
BC9
common analogue input 9
J20-
B10
passive analogue input 9 (NTC, PT1000, ON/OFF)
Thermal overload Klixon fan 2
J20-
BC10
common analogue input 10
* NTC, 0÷1 V, 0÷10V, 0÷20mA, 4÷20mA
7DEOH
Analogue outputs
FRQQHFWRU
FRGH W\SHRIDQDORJXHRXWSXW
'HVFULSWLRQ
J4
VG
power to optically-isolated analogue output, 24Vac/Vdc
J4
VG0
power to optically-isolated analogue output, 0Vac/Vdc
J4
Y1
analogue output no. 1 0÷10V
fan inverter
J4
Y2
analogue output no. 2 0÷10V
compressor inverter
7DEOH
Digital inputs
FRQQHFWRU FRGH
type of digital input
'HVFULSWLRQ
J5
ID1
digital input no. 1, 24Vac/Vdc
thermal overload comp. 1
J5
ID2
digital input no. 2, 24Vac/Vdc
thermal overload comp. 2
J5
ID3
digital input no. 3, 24Vac/Vdc
thermal overload comp. 3
J5
ID4
digital input no. 4, 24Vac/Vdc
thermal overload comp. 4
J5
ID5
digital input no. 5, 24Vac/Vdc
thermal overload comp. 5
J5
ID6
digital input no. 6, 24Vac/Vdc
oil differential 1
J5
ID7
digital input no. 7, 24Vac/Vdc
oil differential 2
J5
ID8
digital input no. 8, 24Vac/Vdc
oil differential 3
J5
IDC1
common for digital inputs 1 to 8
J7
ID9
digital input no. 9, 24Vac/Vdc
oil differential 4
J7
ID10
digital input no. 10, 24Vac/Vdc
oil differential 5
J7
ID11
digital input no. 11, 24Vac/Vdc
High-low pressure switch 1
J7
ID12
digital input no. 12, 24Vac/Vdc
High-low pressure switch 2
J7
IDC9
common for digital inputs 9 to 12
J8
ID13
digital input 13, 24Vac/Vdc
High-low pressure switch 3
J8
IDC13
common for digital inputs 13 and 14
J8
ID14
digital input 14, 24Vac/Vdc
High-low pressure switch 4
J19
ID15
digital input 15, 24Vac/Vdc
High-low pressure switch 5
J19
IDC15
common for digital inputs 15 and 16
J19
ID16
digital input 16, 24Vac/Vdc
Liquid level alarm
J20
ID17
digital input 17, 24Vac/Vdc
Thermal overload Klixon fan 4
J20
ID18
digital input 18, 24Vac/Vdc
Thermal overload Klixon fan 3
J20
IDC17
common for digital inputs 17 and 18
7DEOH
Digital outputs
FRQQHFWRU
FRGH W\SHRIGLJLWDORXWSXW
'HVFULSWLRQ
J12
C1
common relay: 1, 2, 3
J12
NO1
normally-open contact, relay no. 1
compressor 1
J12
NO2
normally-open contact, relay no. 2
capacity-control 1 compressor 1
J12
NO3
normally-open contact, relay no. 3
compressor 2
J12
C1
common relay: 1, 2, 3
J13
C4
common relay: 4, 5, 6
J13
NO4
normally-open contact, relay no. 4
capacity-control 1 compressor 2
J13
NO5
normally-open contact, relay no. 5
compressor 3
J13
NO6
normally-open contact, relay no. 6
capacity-control 1 compressor 3
J13
C4
common relay: 4, 5, 6
J14
C7
common relay no. 7
J14
NO7
normally-open contact, relay no. 7
compressor 4
J14
C7
common relay no. 7
J15
NO8
normally-open contact, relay no. 8
capacity-control 1 compressor 4
J15
C8
common relay no. 8
J16
C9
common relay no. 9
J16
NO9
normally-open contact, relay no. 9
compressor 5
J16
NO10 normally-open contact, relay no. 10
capacity-control 1 compressor 4
J16
NO11 normally-open contact, relay no. 11
J16
C9
common relay no. 9
J17
NO12 normally-open contact, relay no. 12
/
J17
C12
common relay no. 12
J18
NO13 normally-open contact, relay no. 13
/
J18
C13
common relay no. 13